| 2015-03-12 13:14:01 | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, |
| | FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | PLEASE CONSIDER THE FOLLOWING AS PROVISO: |
| | |
| | SHEET A2-0 & E2-0 - NEED TO ADD 5 EXIT SIGNS IN THE |
| | PATH OF EGRESS AS INDICATED ON THE LIFE SAFETY PLAN. |
| | |
| | SHEET A2-0 - NEED TO INSTALL FIRE EXTINGUISHERS EVERY |
| | 75' WALKING DISTANCE. |
| | |
| | SHEET 5-0 - NEED TO ENSURE TO INSTALL FIRE SPRINKLERS |
| | UNDER THE NEWLY CREATED ROOF/PORCH ARE AS IT IS AN |
| | EXTENSION OF AND ATTACHED TO THE FULLY SPRINKLERED |
| | BUILDING. |
| | |
| | PER FLORIDA STATUTUE 69A-60.0081, NOTICE SIGNAGE IS |
| | REQUIRED FOR STRUCTURES WITH LIGHT-FRAME TRUSS-TYPE |
| | CONSTRUCTION. ANY COMMERCIAL, INDUSTRIAL, OR ANY |
| | MULTIUNIT RESIDENTIAL STRUCTURE OF THREE UNITS OR MORE |
| | WHICH USES HORIZONTAL OR VERTICAL LIGHT-FRAME |
| | TRUSS-TYPE CONSTRUCTION IN ANY PORTION SHALL BE MARKED |
| | WITH A MALTESE CROSS SIGN MEASURING 8 INCHES |
| | HORIZONTALLY AND 8 INCHES VERTICALLY, OF A BRIGHT RED |
| | REFLECTIVE COLOR. THE APPROVED SYMBOL SHALL BE PLACED |
| | WITHIN 24 INCHES TO THE LEFT OF THE MAIN ENTRY DOOR. |
| | 1. STRUCTURES WITH LIGHT-FRAME TRUSS ROOFS SHALL BE |
| | MARKED WITH THE LETTER "R". |
| | 2. STRUCTURES WITH LIGHT-FRAME TRUSS FLOOR SYSTEMS |
| | SHALL BE MARKED WITH THE LETTER "F". |
| | 3. STRUCTURES WITH LIGHT-FRAME TRUSS FLOOR AND ROOF |
| | SYSTEMS SHALL BE MARKED WITH THE LETTERS "R/F". |
| | |
| | |
| | |