| 2015-04-29 12:46:39 | 4/29/2015 |
| | PROJECT: FERGUSON SHOWROOM |
| | PERMIT#: 13110271 |
| | CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC |
| | ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| | ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| | 1ST ELECTRICAL PLAN REVIEW OF REVISION TRACKING NUMBER |
| | 15030360 |
| | ACTION: DENIED |
| | |
| | E1-2 |
| | PROVIDE CIRCUIT NUMBERS FOR JUNCTION BOXES NOTED FOR |
| | "HEATERS" |
| | PROVIDE CIRCUITS AND CONTROLS FOR FANS INDICATED BY THE |
| | "F" SYMBOL AND NOTE "5" TO BE INSTALLED IN SEVERAL |
| | LOCATIONS ALL THROUGHOUT AREA TO BE RENNOVATED. |
| | |
| | E-1-3 |
| | FBC-ENERGY |
| | FBC-E 505.2 LIGHTING CONTROLS (MANDATORY). |
| | 1) PROVIDE A MEANS OF LIGHTING CONTROL IN COMPLIANCE |
| | WITH THE FBC-ENERGY 505.2. LIGHTING SYSTEMS SHALL BE |
| | PROVIDED WITH CONTROLS AS REQUIRED IN SECTIONS 505.2.1, |
| | 505.2.2, 505.2.3 AND 505.2.4. |
| | FBC-E 502.3.8 RECESSED LIGHTING. |
| | 2) ALL RECESSED LUMINAIRES SHALL BE IC-RATED. ALL |
| | RECESSED LUMINAIRES SHALL BE SEALED WITH A GASKET OR |
| | CAULK BETWEEN THE HOUSING AND INTERIOR WALL OR CEILING |
| | COVERING. |
| | |
| | E2-0 |
| | NEC 700.12 |
| | 1) THE FIRE PLANS EXAMINER HAS ADDED EMERGENCY AND EXIT |
| | LIGHTING TO THE LIGHTING PLAN. SEE NEC 700.12 THE |
| | BRANCH CIRCUIT FEEDING EMERGENCY AND EXIT LIGHTING |
| | SHALL BE THE SAME BRANCH CIRCUIT AS THAT SERVING THE |
| | NORMAL LIGHTING IN THE AREA AND CONNECTED AHEAD OF ANY |
| | LOCAL SWITCHES. |
| | NEC 220.43(B) |
| | 2) REVISE THE BRANCH CIRCUIT LOAD FOR THE TRACK |
| | LIGHTING THROUGHOUT. A SINGLE 20AMP BRANCH CIRCUIT CAN |
| | CARRY A MAXIMUM OF 25 LINIAL FT. THERE ARE SECTIONS OF |
| | TRACK CONNECTED TO A SINGLE 120V 20AMP BRANCH CIRCUIT |
| | IN EXCESS OF 80 LINIAL FT. SEE NEC 220.43(B) |
| | |
| | E2-1 |
| | ELECTRICAL DETAIL 1A |
| | PROVIDE CIRCUITS AND CONTROLS FOR FANS INDICATED BY THE |
| | "F" SYMBOLS AND NOTES TO BE INSTALLED IN SEVERAL |
| | LOCATIONS ALL THROUGHOUT AREA TO BE RENNOVATED. |
| | |
| | E4-0 |
| | WPB AMENDMENTS TO FBC 107.3.5.1.2 |
| | 1) THE RISER DIGRAM INDICATES THE INSTALLATION OF FIVE |
| | (5) NEW ELECTRICAL PANELS. PROVIDE A SUMMARY LOAD |
| | CALCULATION THAT INDICATES THE ADDITION OF THE LOAD OF |
| | ALL FIVE(5) OF THE NEW PANELS. |
| | 2) PROVIDE A PANEL DIRECTORY AND LOAD CALCULATION FOR |
| | PANEL MDP-B. NEC 408.4 |
| | 3) PROVIDE THE SERVICE ENTRANCE AND GROUNDING ELECTRODE |
| | SIZE AND TYPES. |
| | 4) PROVIDE THE SIZE OF THE FEEDERS TO MDP -A AND MDP-B |
| | 5) PROVIDE SAFETY LABELING FOR ARC FLASH PROTECTION FOR |
| | THE PANEL BOARDS AND MAIN DISCONNECTING MEANS. NEC |
| | 110.16. |
| | |
| | SEPARATE PERMIT APPLICATIONS ACCOMPANIED BY |
| | MANUFACTURERS EQUIPMENT SUBMITTALS, AND SHOP DRAWINGS |
| | ARE REQUIRED FOR LOW VOLTAGE SPECIALTY PERMITS. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. SEE LINK: |
| | HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ |
| | 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| | |
| | ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED |
| | PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE |
| | PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE |
| | REVIEW. |
| | |
| | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| | 561-805-6717 OR [email protected] |
| | |