Plan Review Notes
Plan Review Notes For Permit 15030360
Permit Number 15030360
Review Stop E
Sequence Number 1
Notes
Date Text
2015-04-29 12:46:394/29/2015
 PROJECT: FERGUSON SHOWROOM
 PERMIT#: 13110271
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 1ST ELECTRICAL PLAN REVIEW OF REVISION TRACKING NUMBER
 15030360
 ACTION: DENIED
  
 E1-2
 PROVIDE CIRCUIT NUMBERS FOR JUNCTION BOXES NOTED FOR
 "HEATERS"
 PROVIDE CIRCUITS AND CONTROLS FOR FANS INDICATED BY THE
 "F" SYMBOL AND NOTE "5" TO BE INSTALLED IN SEVERAL
 LOCATIONS ALL THROUGHOUT AREA TO BE RENNOVATED.
  
 E-1-3
 FBC-ENERGY
 FBC-E 505.2 LIGHTING CONTROLS (MANDATORY).
 1) PROVIDE A MEANS OF LIGHTING CONTROL IN COMPLIANCE
 WITH THE FBC-ENERGY 505.2. LIGHTING SYSTEMS SHALL BE
 PROVIDED WITH CONTROLS AS REQUIRED IN SECTIONS 505.2.1,
 505.2.2, 505.2.3 AND 505.2.4.
 FBC-E 502.3.8 RECESSED LIGHTING.
 2) ALL RECESSED LUMINAIRES SHALL BE IC-RATED. ALL
 RECESSED LUMINAIRES SHALL BE SEALED WITH A GASKET OR
 CAULK BETWEEN THE HOUSING AND INTERIOR WALL OR CEILING
 COVERING.
  
 E2-0
 NEC 700.12
 1) THE FIRE PLANS EXAMINER HAS ADDED EMERGENCY AND EXIT
 LIGHTING TO THE LIGHTING PLAN. SEE NEC 700.12 THE
 BRANCH CIRCUIT FEEDING EMERGENCY AND EXIT LIGHTING
 SHALL BE THE SAME BRANCH CIRCUIT AS THAT SERVING THE
 NORMAL LIGHTING IN THE AREA AND CONNECTED AHEAD OF ANY
 LOCAL SWITCHES.
 NEC 220.43(B)
 2) REVISE THE BRANCH CIRCUIT LOAD FOR THE TRACK
 LIGHTING THROUGHOUT. A SINGLE 20AMP BRANCH CIRCUIT CAN
 CARRY A MAXIMUM OF 25 LINIAL FT. THERE ARE SECTIONS OF
 TRACK CONNECTED TO A SINGLE 120V 20AMP BRANCH CIRCUIT
 IN EXCESS OF 80 LINIAL FT. SEE NEC 220.43(B)
  
 E2-1
 ELECTRICAL DETAIL 1A
 PROVIDE CIRCUITS AND CONTROLS FOR FANS INDICATED BY THE
 "F" SYMBOLS AND NOTES TO BE INSTALLED IN SEVERAL
 LOCATIONS ALL THROUGHOUT AREA TO BE RENNOVATED.
  
 E4-0
 WPB AMENDMENTS TO FBC 107.3.5.1.2
 1) THE RISER DIGRAM INDICATES THE INSTALLATION OF FIVE
 (5) NEW ELECTRICAL PANELS. PROVIDE A SUMMARY LOAD
 CALCULATION THAT INDICATES THE ADDITION OF THE LOAD OF
 ALL FIVE(5) OF THE NEW PANELS.
 2) PROVIDE A PANEL DIRECTORY AND LOAD CALCULATION FOR
 PANEL MDP-B. NEC 408.4
 3) PROVIDE THE SERVICE ENTRANCE AND GROUNDING ELECTRODE
 SIZE AND TYPES.
 4) PROVIDE THE SIZE OF THE FEEDERS TO MDP -A AND MDP-B
 5) PROVIDE SAFETY LABELING FOR ARC FLASH PROTECTION FOR
 THE PANEL BOARDS AND MAIN DISCONNECTING MEANS. NEC
 110.16.
  
 SEPARATE PERMIT APPLICATIONS ACCOMPANIED BY
 MANUFACTURERS EQUIPMENT SUBMITTALS, AND SHOP DRAWINGS
 ARE REQUIRED FOR LOW VOLTAGE SPECIALTY PERMITS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED
 PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE
 PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE
 REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  