| Plan Review Notes For Permit 15030357 |
| Permit Number |
15030357 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-03-20 15:51:26 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | 1. ON THE INSTALLATION SCHEDULE, SPAN IS THE DISTANCE | | | FROM ANCHOR TO ANCHOR. SEE, FOR EXAMPLE, OPENING 11. | | | VERTICAL INSTALLATION, SPAN FOR A 60" OPENING WILL | | | EXCEED 3'. | | | | | | 2. SHUTTER CONNECTION MOUNTING TYPE SHOULD CORRELATE | | | WITH THE ANCHOR CHARTS. IN THIS CASE, BASED ON THE | | | MARKS ON THE PRODUCT APPROVAL, IT APPEARS THAT THE | | | CONNECTION TYPES PROPOSED ARE C4 / C1. IF A VERTICAL | | | INSTALLATION IS PROPOSED AS STATED, AND SPAN EXCEEDS | | | 5', 12" ANCHOR SPACING IS NOT ADEQUATE FOR C4 | | | CONNECTION. | | | | | | FBC 2010 RESIDENTIAL 301. | | | |
|