| 2015-04-25 10:34:16 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 15030326 |
| | ADD: 5335 N. MILITARY TRL. SUITE # 33 |
| | CONT: MIKE MOORE CONSTRUCTION |
| | TEL: (561)301-9468 |
| | E-MAIL: [email protected] |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | BUILDING PROVISO: |
| | AT RATED WALLS PLEASE HAVE THE FIRE STOPPING |
| | MANUFACTURER SPEC SHEET IN COMPLIANCE WITH: |
| | 2010FBC-B 713.3.1.2 THROUGH-PENETRATION FIRESTOP |
| | SYSTEM. THROUGH PENETRATIONS SHALL BE |
| | PROTECTED BY AN APPROVED PENETRATION FIRESTOP SYSTEM |
| | INSTALLED AS TESTED IN ACCORDANCE |
| | WITH ASTM E 814 OR UL 1479, WITH A MINIMUM POSITIVE |
| | PRESSURE DIFFERENTIAL OF 0.01 INCH OF |
| | WATER AND SHALL HAVE AN F RATING OF NOT LESS THAN THE |
| | REQUIRED FIRE-RESISTANCE RATING OF THE |
| | |
| | WALL PENETRATED. |