2015-04-11 05:21:141) THE SITE PLAN ( LARGE PLAN ) SHOWS PE PIPING BEING
 INSTALLED UNDERGROUND AND UNDER THE PATIO SLAB. PE
 PIPING IS LIMITED TO INSTALLATION OUTDOORS UNDERGROUND
 ONLY PER THE 2010 FBCR SEC.G2415.15.1. SHOW CODE
 COMPLIANT PIPING MATERIAL ON THE PLANS.
 2) SUBMIT 2 COPIES OF THE MANUFACTURER'S
 SPECIFICATIONS/INSTALLATION MANUAL FOR THE GRILL. THE
 GRILL SHALL BE LISTED AND LABELED PER THE 2010 FBCR
 SEC.G2404.3.
 3) THE LARGE DRAWING (SITE PLAN) AND THE 8 1/2 " X 11"
 CONTAIN CONFLICTING INFORMATION. THE SMALLER SHEETS
 SHOW THE GAS LINE AS CSST AND THE LARGE SHEET SHOWS PE
 PIPE. CLARIFY.
 4) REMOVE THE EHD NUMBER ON THE LARGE SHEET IF YOU ARE
 NOT USING ANY CSST PIPE.
 5) THE LARGE PLAN SHOWS THE SLEEVE AS SCH. 40 PVC AND
 THE SMALL PLAN SHOWS THE SLEEVE AS SCH. 80 PVC WITH
 CSST PIPE.CLARIFY.
 6) PROVIDE A MORE DESCRIPTIVE EXPLANATION ON THE PERMIT
 APPLICATIONS. THE PLUMBING & GAS APPLICATIONS STATE
 "COVERED PATIO-GAS" AND "COVERED PATIO- PLUMBING." THE
 DESCRIPTION IS EXTREMELY VAGUE.
 7) REFER TO THE 2010 FL. BUILDING CODE RESIDENTIAL FOR
 THE INSTALLATION REQUIREMENTS FOR A SLEEVE FOR THE GAS
 LINE.SEE SEC. G2415.6.1.THE SLEEVE SHALL BE INSTALLED
 IN ACCORDANCE WITH THIS SECTION. READ THIS SECTION
 THOROUGHLY AND PLACE APPLICABLE NOTES ON THE PLAN
 REGARDING THE INSTALLATION.
  
 PLEASE DO NOT RESUBMIT THESE PLANS UNTIL ALL
 DEFICIENCIES HAVE BEEN CORRECTED.IF NEEDED, YOU CAN
 CONTACT ME AT THE NUMBER BELOW AND SET UP AN
 APPOINTMENT TO REVIEW THESE COMMENTS.
  