Plan Review Notes
Plan Review Notes For Permit 15030308
Permit Number 15030308
Review Stop G
Sequence Number 1
Notes
Date Text
2015-03-19 14:57:471) THE GAS DRAWING ON ONE OF THE PLANS IS DONE IN
 PENCIL. REDRAW THE PLAN IN INK.
 2) INDICATE THE PSI OF THE GAS ON THE PLAN. WPB AMEND.
 TO 2010 FBC SEC. 107.2.1.
 3) INDICATE ON THE PLANS THE APPLICABLE SIZING TABLE
 USED TO DETERMINE THE PIPE SIZE FOR THE GAS LINE. 2010
 FBCR SEC. GG2413.3 & G2413.4.
 4) THE BTU LOADS LISTED ON THE 8 1/2" X 11" SHEET DOES
 NOT MATCH THE BTU LOADS ON THE LYNX SIZING SHEET.YOU
 SHOW 65,000 FOR THE GRILL AND 30,000 FOR SIDEBURNER BUT
 THE LYNX SHEET DOES NOT HAVE THE SAME BTU LOAD.
 CLARIFY.
 5) THE SLEEVING OF GAS PIPING UNDER A BUILDING SHALL
 COMPLY WITH SEC.G 2415.6.1 OF THE 2010 FBCR.
  
 PLUMBING PLAN REVIEW