| 2015-07-20 14:48:51 | 2ND REVIEW: FBC 2010 MECHANICAL | | | | | | 1) SHOW THE BRANCH DUCT SIZES ON THE PLAN. | | | 2) THE 16X6" TRANSFER GRILL IS UNDERSIZED FOR 287 | | | CFM'S- SEE SECTION 601.4 FBC-10 MECHANICAL. | | | 3) PROVIDE TIE DOWN ENGINEERING FOR ANCHORING THE | | | CONDENSERS TO THE PADS- SECTION 301.12. | | | 4) SHOW THE LOCATIONS OF ALL FOUR CONDENSERS ON THE | | | PLANS- ONLY ONE OF THE FOUR IS SHOWN. | | | 5) THE PLAN INDICATES A 3/8" CONDENSATE PIPE, MINIMUM | | | 3/4" IS REQUIRED- SECTION 307. | | | | | | | | | | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | | | | |
|