Plan Review Notes
Plan Review Notes For Permit 15030301
Permit Number 15030301
Review Stop M
Sequence Number 3
Notes
Date Text
2015-07-20 14:48:512ND REVIEW: FBC 2010 MECHANICAL
  
 1) SHOW THE BRANCH DUCT SIZES ON THE PLAN.
 2) THE 16X6" TRANSFER GRILL IS UNDERSIZED FOR 287
 CFM'S- SEE SECTION 601.4 FBC-10 MECHANICAL.
 3) PROVIDE TIE DOWN ENGINEERING FOR ANCHORING THE
 CONDENSERS TO THE PADS- SECTION 301.12.
 4) SHOW THE LOCATIONS OF ALL FOUR CONDENSERS ON THE
 PLANS- ONLY ONE OF THE FOUR IS SHOWN.
 5) THE PLAN INDICATES A 3/8" CONDENSATE PIPE, MINIMUM
 3/4" IS REQUIRED- SECTION 307.
  
  
  
  