Plan Review Notes
Plan Review Notes For Permit 15030301
Permit Number 15030301
Review Stop E
Sequence Number 3
Notes
Date Text
2015-09-17 19:22:50SO AS NOT TO HOLD THE PERMIT FROM BEING ISSUED, THIS
 APPLICATION IS BEING APPROVED WITH THE FOLLOWING
 PROVISOS:
 1. IF THE CORNER AREA BEHIND THE KITCHEN SINK IS 12
 INCHES OR GREATER AS SPECIFIED IN NEC 210.52(C), IT
 SHALL HAVE AN OUTLET.
 2. EACH CONDENSING UNIT SHALL HAVE WITHIN 25' A SERVICE
 OUTLET AS REQUIRED BY NEC 210.63. THIS OUTLET SHALL BE
 SERVED FROM THE RESPECTIVE UNIT'S ELECTRIC SERVICE.
 I CAN SUGGEST GE MODEL # TFN60RGFRCP, 60 AMP 240-VOLT
 NON-FUSE AC DISCONNECT WITH GFCI RECEPTACLE OR
 EQUIVALENT.