| Date |
Text |
| 2015-08-20 19:16:33 | PLEASE NOTE THAT I, MIKE ALBARRAN, ELECTRICAL PLANS |
| | EXAMINER HAVE COMPLETED THE REVIEW OF THE ABOVE |
| | MENTIONED JOB. BELOW ARE THE COMMENTS WITH REGARDS TO |
| | THE REQUIRED CORRECTIONS. THE FOLLOWING ITEMS SHALL BE |
| | CORRECTED AND THE PLANS RESUBMITTED FOR ANOTHER REVIEW. |
| | |
| | 1. ACCORDING TO A LETTER FROM MR. DANILO ALCANTARA, |
| | EACH SUB WILL SUBMIT THEIR OWN DRAWING AND THEREFORE |
| | APPLY FOR THEIR OWN PERMIT. THE FOLLOWING REVIEW IS FOR |
| | THE DRAWING PRESENTLY SUBMITTED, THOUGH IF THIS |
| | STATEMENT IS TRUE, THE RESULTS OF THIS REVIEW WILL |
| | DIFFER. PLEASE ADVISE IF THE PREVIOUSLY SUBMITTED |
| | LETTER ATTESTING TO THIS REMAINS IN EFFECT. |
| | 2. THE WORD "ROMEX" AS USED IN THIS NOTE IS TO IDENTIFY |
| | A TYPE OF CABLE. ROMEX IS A BRAND NAME AND NOT A TYPE |
| | OF CABLE, REFER TO CABLE TYPES "NM", "NMC" OR "NMS". |
| | 3. THE TITLE BLOCK INDICATES THAT THIS IS A 4 PLEX |
| | REMODEL. THE SUBMITTED DRAWING IS INCOMPLETE. IT |
| | REFLECTS ONLY TWO UNITS. |
| | 4. YOU SHALL SUBMIT A SITE SPECIFIC RISER DIAGRAM |
| | 5. YOU SHALL PROVIDE SITE SPECIFIC LOAD CALCS FOR EACH |
| | UNIT AND THEN THE FOR THE SINGLE SERVICE FOR THE |
| | MULTI-UNIT DWELLING. |
| | 6. AS CIRCUIT DIRECTORY AS DESCRIBED IN NEC 408.4 SHALL |
| | BE SUBMITTED FOR EACH UNIT. |
| | 7. EVERY CEILING LUMINAIRE OUTLET SHALL BE LISTED TO |
| | SUPPORT A MINIMUM OF 50 LBS. AS INDICATED IN NEC 314.27 |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |
| | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| | CONTACT ME DIRECTLY. |
| | |