| 2015-03-13 07:50:23 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 15030301 |
| | ADD: 3805 S OLIVE AVE. |
| | CONT: DELTA MG |
| | TEL: ( 561)239-4947 |
| | E-MAIL:[email protected] |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 2ND REVIEW |
| | DATE: MON. APRIL 27/ 2015 |
| | ACTION: DENIED |
| | |
| | 1-3) COMPLIED> |
| | |
| | 4) 2ND REQUEST. SEMI- COMPLIED. THE (3) REPORTS |
| | SUBMITTED FOR WHISPER MAT: |
| | |
| | 4A) COMPLIED. SURFACE BURNING CHARACTERISTICS OF |
| | BURNING MATERIALS ASTM E 84 : FLAME SPREAD 0 & SMOKE |
| | DEVELOPED INDEX 0. |
| | |
| | 4B) SEMI-COMPLIED. THE SOUND TRANSMISSION LOSS TEST, |
| | ASTM E-90, WITH A STC= 57 DB. THE SYSTEM THAT WAS |
| | TESTED PAGE 2 OF 4 LIST THE COMPONENTS THAT MAKE UP THE |
| | TESTED ASSEMBLY, 1/4 IN. GLAZED TILE, 1/4 IN. POLYMER |
| | MODIFIED THIN SET, 2.5 MM (0.1 IN.), 5/8 IN. B. C. |
| | PLYWOOD, 3/4 IN. T & G OSB SUB-FLOOR, 3 1/2 IN. X 18 |
| | IN. X 12 FT. OPEN WEB TRUSSES, RESILIENT FURRING |
| | CHANNEL, 3 1/2 IN. OF FIBERGLASS INSULATION BATTS & 1 |
| | LAYER OF 5/8 IN. TYPE C WALLBOARD. |
| | SITE CONDITIONS WRITTEN ON THE FACE OF THE TEST REPORT |
| | 2X12 TRUSSES, (FLOOR JOIST/ I LOIST?) 5/8 PLYWOOD PLUS |
| | 1/2 IN. DUROCK. THE TESTED ASSMBLY HAS A 5/8 IN. B. C. |
| | FINISH PLYWOOD + 3/4 IN. OSB OPEN WEB JOIST, RESILIENT |
| | CHANNEL FURRING. PLEASE PROVIDE RANIONAL ANALYSIS AND |
| | PREFORM A ENGINEERED JUDGEMENT AS WHAT IT WILL TAKE TO |
| | MEET THE EQUIVALENCY OF THE TESTING. WE UNDERSTAND THAT |
| | YOU WILL NOT FIND A TESTED REPORT WITH THE SAME |
| | COMONENTS AS THE TEST SPECIMEN FOR THE WOOD PRODUCTS |
| | AND WITH DURAROCK AS A COMPONENT, PLEASE BE SPECIFIC AS |
| | TO HOW EACH OF THE MEMBERS ARE TO BE EITHER FASTENED |
| | AND OR ADHERRED TO EACH OTHER. |
| | |
| | 4C) THE SUBMITTED REPORT FOR WHISPER MAT FLOOR |
| | UNDERLAYMENT WITH A IIC RATING OF 49 TESTED TO ASTM E |
| | 492 DOES NOT MEET THE REQUIRED IIC RATING OF 50. |
| | AS STATED ABOVE THE TESTED ASSEMBLY IN THIS CASE DID |
| | NOT MEET THE REQUIREMENTS OF THE CODE WITH THE SAME |
| | CONFIGURATION. PLEASE PROVIDE RANIONAL ANALYSIS AND |
| | PREFORM A ENGINEERED JUDGEMENT AS WHAT IT WILL TAKE TO |
| | MEET THE REQUIREMENT OF ASTM E-492 WITH A IIC OF 50 DB |
| | MINIMUM. WE UNDERSTAND THAT YOU WILL NOT FIND A TESTED |
| | REPORT WITH THE SAME COMONENTS AS THE TEST SPECIMEN FOR |
| | THE WOOD PRODUCTS AND WITH DURAROCK AS A COMPONENT, |
| | PLEASE BE SPECIFIC AS TO HOW EACH OF THE MEMBERS ARE TO |
| | BE EITHER FASTENED AND OR ADHERRED TO EACH OTHER. |
| | ------------------------------------------------------- |
| | ------------------------------------------------------- |
| | ------------------------------------------------------- |
| | ------------------------------- |
| | 4) 1ST REVIEW COMMENTS. 2010 1207.3 STRUCTURE BORN |
| | SOUND REPORT FOR PROFLEX . PLEASE PROVIDE THE SLAB |
| | THICKNESS. THIS REPORT DECLARES A IIC RATING OF 68DB |
| | WHEN APPLIED TO A 8 INCH SLAB AND A 5/8 IN DROP CEILING |
| | WITH 3 1/2 INCHES OF FIBERGLASS INSULATION (0.16PSF). |
| | PLEASE IDENTIFY THE ACTUAL FLOOR/ CEILING ASSEMBLY TO |
| | SEE IF THIS REPORT IS THE RIGHT CONFIGURATION, NOTE |
| | DROPED CEILINGS WOULD NEED TO BE THROUGH THE WHOLE UNIT |
| | WITH A 10 INCH PLENUM. 1207.3 STRUCTURE-BORNE SOUND. |
| | |
| | 5) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |