| Plan Review Notes For Permit 15030292 |
| Permit Number |
15030292 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-04-08 18:07:52 | PLAN REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC 2010 | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS | | | FOR THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE 9N-3 | | | THAT HAVE BEEN REVIEWED AND APPROVED IN WRITING BY THE | | | DESIGNER OF RECORD. PROVIDE TWO COMPLETE PRODUCT | | | APPROVALS WITH FL OR NOA NUMBERS INCLUDING INSTALLATION | | | INSTRUCTIONS AND MAXIMUM DESIGN PRESSURES FOR EACH OF | | | THE DIFFERENT ROOFING MATERIALS, WINDOW/GLASS TYPES, | | | STRUCTURAL MULLIONS AND EXTERIOR DOOR TYPES. | | | A) THE PLANS SPECIFY SINGLE HUNG WINDOWS AND PRODUCT | | | APPROVALS WERE SUBMITTED FOR CASEMENT WINDOWS. FBC | | | 107.2.1 | | | B) PRODUCT APPROVALS WERE SUBMITTED FOR GLAZED FRENCH | | | DOORS. THE ELEVATIONS SHOW A FLUSH DOOR AND TWO (2) | | | PANEL DOORS. ONE OF THE PANEL DOORS HAS AN ARCHED TOP. | | | | | | 2) SHOW COMPLIANCE WITH FBC EXISTING BUILDING 604.1 AND | | | FBC-R310.1 FOR EMERGENCY ESCAPE AND RESCUE AT THE | | | BEDROOM WINDOWS. | | | | | | IN ORDER TO REDUCE PLAN REVIEW TIMES AND PROVIDE | | | CLARIFICATION, PLEASE SUBMIT A RESPONSE LETTER | | | INDICATING HOW EACH OF THE REVIEW COMMENTS HAS BEEN | | | ADDRESSED. |
|