| 2015-03-27 15:19:21 | 1ST REVIEW: FBC 2010 |
| | |
| | THE PLAN IS DEFICIENT IN TERMS OF DETAIL AND CLARITY: |
| | |
| | FBC107.2.1 - INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN |
| | UPON SUITABLE MATERIAL. ELECTRONIC MEDIA DOCUMENTS |
| | SHALL BE SUBMITTED WHEN APPROVED BY THE BUILDING |
| | OFFICIAL. CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT |
| | CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF |
| | THE WORK PROPOSED AND SHOW IN DETAIL THAT IT WILL |
| | CONFORM TO THE PROVISIONS OF THIS CODE AND RELEVANT |
| | LAWS, ORDINANCES, RULES AND REGULATIONS, AS DETERMINED |
| | BY THE BUILDING OFFICIAL. SUCH DRAWINGS AND |
| | SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM |
| | OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS, |
| | WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE |
| | TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC, |
| | AND THE TECHNICAL CODES SHALL NOT BE CITED AS A WHOLE |
| | OR IN PART, NOR SHALL THE TERM "LEGAL" OR ITS |
| | EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC |
| | INFORMATION. ALL INFORMATION, DRAWINGS, SPECIFICATIONS |
| | AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE |
| | OF THE PERSON RESPONSIBLE FOR THE DESIGN. (SEE ALSO |
| | SECTION 107.3.5). |
| | |
| | FBC 107.2.1.4 QUALITY OF BUILDING PLANS. BUILDING PLANS |
| | SHALL BE DRAWN TO A MINIMUM 1/8 INCH SCALE UPON |
| | SUBSTANTIAL PAPER, CLOTH OR OTHER ACCEPTABLE MEDIUM. |
| | THIS POLICY MAY INCLUDE SUCH THINGS AS MINIMUM SIZE, |
| | SHAPE, CONTRAST, CLARITY, OR OTHER ITEMS RELATED TO |
| | RECORDS MANAGEMENT. |
| | |
| | 1) REGARDING THE REPLACEMENT OF FASCIA BOARD IS |
| | SUFFICIENT, HOWEVER, BE ADVISED IT MUST BE DECAY |
| | RESISTANT WOOD AND FASTENED EQUALLY AS STRONG AS THE AS |
| | ORIGINALLY. IT WOULD BE HELPFUL IF YOU PROVIDE A DETAIL |
| | SPECIFYING THE WOOD TYPE AND DIMENSIONS AND FASTENERS |
| | PROPOSED. |
| | |
| | 2) I DO NOT UNDERSTAND WHAT "VAINLY" IS BUT I PRESUME |
| | YOU MAY MEAN VINYL. PLEASE PROVIDE A DETAIL SHOWING THE |
| | SUBSTRATE MATERIAL: IS IT PLYWOOD, IS IT BLOCK? PROVIDE |
| | A SECTION SHOWING THE PROPOSED VAPOR BARRIER IF NEEDED, |
| | MESH IF PROPOSED, AND STUCCO THICKNESS. |
| | |
| | 3) REGARDING THE LIVING ROOM WINDOW, YOU MUST SUPPLY |
| | DETAILS TO DEMONSTRATE THE PROPOSED STRUCTURAL |
| | MODIFICATIONS TO THE OPENING. ADDITIONALLY, YOU MUST |
| | PROVIDE COPIES OF THE PRODUCT APPROVAL FOR THE WINDOW. |
| | |
| | 4) REGARDING THE REMOVAL OF THE BEDROOM WALLS, IN |
| | ADDITION TO PROVIDING ELECTRICAL INFORMATION AS |
| | OTHERWISE REQUESTED, PLEASE PROVIDE A MORE DETAILED |
| | FLOOR PLAN TO DEMONSTRATE THE PROPOSED REMOVAL OF WALLS |
| | AND RE-DESIGNATION OF SPACE. |
| | |
| | |
| | STEVEN KENNEDY, CBO |
| | CHIEF PLANS EXAMINER |
| | (561) 805-6710 |