| Plan Review Notes For Permit 15030257 |
| Permit Number |
15030257 |
|
| Review Stop |
M |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2015-10-19 15:44:13 | 10/19/15 TALKED TO ERIC COLLIN. HE SAID OK TO ISSUE | | | PERMIT WITH PROVISO. AND, SUBMIT PLANS AND | | | COMPLETE/CORRECT A/C CALCULATIONS UNDER A SEPARATE | | | PERMIT. HE ESTIMATED $11,000 FOR A/C WORK. THIS AMOUNT | | | WILL BE DEDUCTED FROM THE MAIN PERMIT. JG. | | | | | | | | | | | | | | | NEW SINGLE FAMILY RESIDENCE, THIRD MECHANICAL REVIEW | | | CHECKLIST. | | | CODE: 2010 FBC. | | | | | | 1- REVISE EQUIPMENT SIZING CALCULATIONS: | | | A) THIS IS A SINGLE FAMILY RESIDENCE. THERE ARE NOT 24 | | | OCCUPANTS ON THE FIRST FLOOR PLUS 2 OCCUPANTS ON THE | | | MASTER BEDROOM AND 26 OCCUPANTS ON THE SECOND FLOOR. | | | REVISE AS REQUIRED. CODE DOESN'T ALLOW FOR ANY FACTORS | | | THAT WILL AFFECT EQUIPMENT SIZING. SEC. 403.6.1 OF 2010 | | | FBC-ENERGY CONSERVATION. | | | RESPONSE: (NUMBER OF OCCUPANTS (18) STILL TOO HIGH FOR | | | A SINGLE FAMILY RESIDENCE. | | | | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | (561)805-6712 | | | [email protected] |
|