2015-10-19 15:44:1310/19/15 TALKED TO ERIC COLLIN. HE SAID OK TO ISSUE
 PERMIT WITH PROVISO. AND, SUBMIT PLANS AND
 COMPLETE/CORRECT A/C CALCULATIONS UNDER A SEPARATE
 PERMIT. HE ESTIMATED $11,000 FOR A/C WORK. THIS AMOUNT
 WILL BE DEDUCTED FROM THE MAIN PERMIT. JG.
  
  
  
  
 NEW SINGLE FAMILY RESIDENCE, THIRD MECHANICAL REVIEW
 CHECKLIST.
 CODE: 2010 FBC.
  
 1- REVISE EQUIPMENT SIZING CALCULATIONS:
 A) THIS IS A SINGLE FAMILY RESIDENCE. THERE ARE NOT 24
 OCCUPANTS ON THE FIRST FLOOR PLUS 2 OCCUPANTS ON THE
 MASTER BEDROOM AND 26 OCCUPANTS ON THE SECOND FLOOR.
 REVISE AS REQUIRED. CODE DOESN'T ALLOW FOR ANY FACTORS
 THAT WILL AFFECT EQUIPMENT SIZING. SEC. 403.6.1 OF 2010
 FBC-ENERGY CONSERVATION.
 RESPONSE: (NUMBER OF OCCUPANTS (18) STILL TOO HIGH FOR
 A SINGLE FAMILY RESIDENCE.
  
  