| 2015-09-24 17:44:53 | NEW SINGLE FAMILY RESIDENCE, THIRD MECHANICAL REVIEW |
| | CHECKLIST. |
| | CODE: 2010 FBC. |
| | |
| | 1- REVISE EQUIPMENT SIZING CALCULATIONS: |
| | A) THIS IS A SINGLE FAMILY RESIDENCE. THERE ARE NOT 24 |
| | OCCUPANTS ON THE FIRST FLOOR PLUS 2 OCCUPANTS ON THE |
| | MASTER BEDROOM AND 26 OCCUPANTS ON THE SECOND FLOOR. |
| | REVISE AS REQUIRED. CODE DOESN'T ALLOW FOR ANY FACTORS |
| | THAT WILL AFFECT EQUIPMENT SIZING. SEC. 403.6.1 OF 2010 |
| | FBC-ENERGY CONSERVATION. |
| | |
| | B) WHAT KIND OF APPLIANCES ARE CONSIDERED FOR THE |
| | MASTER BEDROOM?. REVISE AS REQUIRED. CODE DOESN'T ALLOW |
| | FOR ANY FACTORS THAT WILL AFFECT EQUIPMENT SIZING. SEC. |
| | 403.6.1 OF 2010 FBC-ENERGY CONSERVATION. |
| | |
| | C) CEILING AREA FOR ROOM #1 IS INCORRECT. THE FIRST |
| | FLOOR WAS DIVIDED INTO TWO ZONES. THE MASTER BEDROOM IS |
| | ONE ZONE AND THE REST OF THE FIRST FLOOR IS THE SECOND |
| | ZONE. 2855 S.F IS FOR THE ENTIRE FIRST FLOOR. NEED TO |
| | SPLIT THE CEILING AREA BETWEEN ROOM # 1 AND ROOM #3. |
| | REVISE AS REQUIRED. CODE DOESN'T ALLOW FOR ANY FACTORS |
| | THAT WILL AFFECT EQUIPMENT SIZING. SEC. 403.6.1 OF 2010 |
| | FBC-ENERGY CONSERVATION. |
| | |
| | D) FLOOR PLANS WERE REVISED BY THE OWNER. THERE ARE NOT |
| | LONGER TWO SOLID DOORS LEADING FROM THE GARAGE TO THE |
| | MAIN HOUSE. REVISE INFORMATION ON EQUIPMENT SIZING |
| | CALCULATIONS AS REQUIRED. SEC. 403.6.1 OF 2010 |
| | FBC-ENERGY CONSERVATION. |
| | |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT |