2015-09-24 08:57:35NEW SINGLE FAMILY RESIDENCE (R3) THIRD BUILDING REVIEW
 CHECKLIST.
 CODE: 2010 FBC.
  
 1- PLANS SUBMITTED ARE MISSING THE SEAL OF THE ENGINEER
 OF RECORD AS REQUIRED BY CHAPTER 471 F.S. SEAL ALL
 PLANS.
  
 2- PROPERTY IS LOCATED IN FLOOD ZONE A5. (BASE FLOOR
 ELEVATION 7'-0"). ACCORDING TO REVISED SURVEY SUBMITTED
 THE GARAGE FINISH FLOOR ELEVATION IS BELOW THE BASE
 FLOOD ELEVATION. PROVIDE COMPLETE DETAILS AND
 SPECIFICATIONS SHOWING COMPLIANCE WITH SEC. R322.2.2 OF
 2010 FBC-RESIDENTIAL. ALSO, PROVIDE PRODUCT APPROVAL
 FOR THE FLOOD VENTS.
  
 ***RESPONSE:
 RESPONSE LETTER SAID THAT SURVEY WAS REVISED TO RAISE
 THE FINISH FLOOR ELEVATION OF THE GARAGE. SURVEY
 SUBMITTED WAS NOT REVISED.
  
 3- SINGLE HUNG WINDOWS 24EH SPECIFIED ON BEDROOM #2, #3
 AND #4 DON'T COMPLY WITH THE EGRESS REQUIREMENTS OF
 SEC. R310 OF 2010 FBC-RESIDENTIAL. LETTER PROVIDED BY
 WINDOW MANUFACTURER SHOW CLEAR OPENING OF 5.58 S.F.
 THEY DON'T MEET THE OVERALL CLEAR OPENING OF 5.7 S.F.
 AS REQUIRED BY SEC. R310.1.1 OF 2010 FBC-RESIDENTIAL.
  
 ***RESPONSE:
 RESPONSE LETTER STATED THAT WINDOWS WERE CHANGED TO
 CASEMENT WINDOWS. WINDOW SPECIFICATIONS SHOWN ON FLOOR
 PLANS ARE NOT CLEAR. THEY DON'T SPECIFY THE TYPE OF
 WINDOWS AND THERE IS NOT WAY TO IDENTIFY SIZES
 SPECIFIED WITH SIZES SHOWN ON THE PRODUCT APPROVAL. THE
 WAY WINDOWS ARE SPECIFIED ON PLANS IS THE TYPICAL WAY
 TO SPECIFY SINGLE HUNG WINDOWS NOT CASEMENT WINDOWS.
 REVISE AS REQUIRED AND PROVIDE COMPLETE AND CLEAR
 WINDOW SCHEDULE. SEC. 107.2.1 CITY AMENDMENTS.
  
 4- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.002(33) FOR:
 A) FLOOD VENTS. COORDINATE WITH ITEM #2 ABOVE REGARDING
 GARAGE FINISH FLOOR ELEVATION.
  
 B) SINGLE INSWING DOOR THAT MEETS THE DESIGN PRESSURES
 CALCULATED BY THE ENGINEER FOR CABANA DOOR THAT IS
 LOCATED 6 FT WITHIN CORNERS. DOOR WITH FLORIDA PRODUCT
 APPROVAL FL14665.1 SUBMITTED DOESN'T MEET THE
 CALCULATED DESIGN PRESSURES.
  
 C) ENTRY OUTSWING DOOR THAT MEETS THE DESIGN PRESSURES
 CALCULATED BY THE ENGINEER. DOOR WITH FLORIDA PRODUCT
 APPROVAL FL12334.9 SUBMITTED DOESN'T MEET THE
 CALCULATED DESIGN PRESSURES.
  
 5- DESIGNER OF RECORD TO APPROVE ABOVE PRODUCT
 APPROVALS. SEC. 107.3.4.1 CITY AMENDMENTS.
  
 IMPORTANT:
 (1) CONTRACTOR WILL BE REQUIRED TO HIRE AN SPECIAL
 INSPECTOR FOR THE CONSTRUCTION AND INSTALLATION OF PILE
 DRIVING. SEC. 110.3.9 CITY AMENDMENTS. PLEASE
 COORDINATE WITH CHIEF BUILDING INSPECTOR KEN CONRAD
 (561)805-6666 FOR APPROVAL PRIOR TO ANY INSPECTIONS TO
 AVOID CONFLICTS OR DELAYS DURING CONSTRUCTION.
  
 (2) ELEVATION CERTIFICATES WILL BE REQUIRED DURING
 CONSTRUCTION. PLEASE COORDINATE WITH SAMANTHA HILL
 (561)805-6724 OR [email protected] FOR REVIEW OF INITIAL
 ELEVATION CERTIFICATES TO AVOID CONFLICTS OR DELAYS.
  
 ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 ***PLEASE REPLACE AND REMOVE ANY REVISED DRAWING.
 RE-SUBMIT OLD DRAWINGS FOR REFERENCE
  