| 2015-09-24 08:57:35 | NEW SINGLE FAMILY RESIDENCE (R3) THIRD BUILDING REVIEW |
| | CHECKLIST. |
| | CODE: 2010 FBC. |
| | |
| | 1- PLANS SUBMITTED ARE MISSING THE SEAL OF THE ENGINEER |
| | OF RECORD AS REQUIRED BY CHAPTER 471 F.S. SEAL ALL |
| | PLANS. |
| | |
| | 2- PROPERTY IS LOCATED IN FLOOD ZONE A5. (BASE FLOOR |
| | ELEVATION 7'-0"). ACCORDING TO REVISED SURVEY SUBMITTED |
| | THE GARAGE FINISH FLOOR ELEVATION IS BELOW THE BASE |
| | FLOOD ELEVATION. PROVIDE COMPLETE DETAILS AND |
| | SPECIFICATIONS SHOWING COMPLIANCE WITH SEC. R322.2.2 OF |
| | 2010 FBC-RESIDENTIAL. ALSO, PROVIDE PRODUCT APPROVAL |
| | FOR THE FLOOD VENTS. |
| | |
| | ***RESPONSE: |
| | RESPONSE LETTER SAID THAT SURVEY WAS REVISED TO RAISE |
| | THE FINISH FLOOR ELEVATION OF THE GARAGE. SURVEY |
| | SUBMITTED WAS NOT REVISED. |
| | |
| | 3- SINGLE HUNG WINDOWS 24EH SPECIFIED ON BEDROOM #2, #3 |
| | AND #4 DON'T COMPLY WITH THE EGRESS REQUIREMENTS OF |
| | SEC. R310 OF 2010 FBC-RESIDENTIAL. LETTER PROVIDED BY |
| | WINDOW MANUFACTURER SHOW CLEAR OPENING OF 5.58 S.F. |
| | THEY DON'T MEET THE OVERALL CLEAR OPENING OF 5.7 S.F. |
| | AS REQUIRED BY SEC. R310.1.1 OF 2010 FBC-RESIDENTIAL. |
| | |
| | ***RESPONSE: |
| | RESPONSE LETTER STATED THAT WINDOWS WERE CHANGED TO |
| | CASEMENT WINDOWS. WINDOW SPECIFICATIONS SHOWN ON FLOOR |
| | PLANS ARE NOT CLEAR. THEY DON'T SPECIFY THE TYPE OF |
| | WINDOWS AND THERE IS NOT WAY TO IDENTIFY SIZES |
| | SPECIFIED WITH SIZES SHOWN ON THE PRODUCT APPROVAL. THE |
| | WAY WINDOWS ARE SPECIFIED ON PLANS IS THE TYPICAL WAY |
| | TO SPECIFY SINGLE HUNG WINDOWS NOT CASEMENT WINDOWS. |
| | REVISE AS REQUIRED AND PROVIDE COMPLETE AND CLEAR |
| | WINDOW SCHEDULE. SEC. 107.2.1 CITY AMENDMENTS. |
| | |
| | 4- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| | FAC 61G20-3.002(33) FOR: |
| | A) FLOOD VENTS. COORDINATE WITH ITEM #2 ABOVE REGARDING |
| | GARAGE FINISH FLOOR ELEVATION. |
| | |
| | B) SINGLE INSWING DOOR THAT MEETS THE DESIGN PRESSURES |
| | CALCULATED BY THE ENGINEER FOR CABANA DOOR THAT IS |
| | LOCATED 6 FT WITHIN CORNERS. DOOR WITH FLORIDA PRODUCT |
| | APPROVAL FL14665.1 SUBMITTED DOESN'T MEET THE |
| | CALCULATED DESIGN PRESSURES. |
| | |
| | C) ENTRY OUTSWING DOOR THAT MEETS THE DESIGN PRESSURES |
| | CALCULATED BY THE ENGINEER. DOOR WITH FLORIDA PRODUCT |
| | APPROVAL FL12334.9 SUBMITTED DOESN'T MEET THE |
| | CALCULATED DESIGN PRESSURES. |
| | |
| | 5- DESIGNER OF RECORD TO APPROVE ABOVE PRODUCT |
| | APPROVALS. SEC. 107.3.4.1 CITY AMENDMENTS. |
| | |
| | IMPORTANT: |
| | (1) CONTRACTOR WILL BE REQUIRED TO HIRE AN SPECIAL |
| | INSPECTOR FOR THE CONSTRUCTION AND INSTALLATION OF PILE |
| | DRIVING. SEC. 110.3.9 CITY AMENDMENTS. PLEASE |
| | COORDINATE WITH CHIEF BUILDING INSPECTOR KEN CONRAD |
| | (561)805-6666 FOR APPROVAL PRIOR TO ANY INSPECTIONS TO |
| | AVOID CONFLICTS OR DELAYS DURING CONSTRUCTION. |
| | |
| | (2) ELEVATION CERTIFICATES WILL BE REQUIRED DURING |
| | CONSTRUCTION. PLEASE COORDINATE WITH SAMANTHA HILL |
| | (561)805-6724 OR [email protected] FOR REVIEW OF INITIAL |
| | ELEVATION CERTIFICATES TO AVOID CONFLICTS OR DELAYS. |
| | |
| | ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH |
| | COMMENT TO EXPEDITE THE REVIEW PROCESS. |
| | ***PLEASE REPLACE AND REMOVE ANY REVISED DRAWING. |
| | RE-SUBMIT OLD DRAWINGS FOR REFERENCE |
| | |