| Plan Review Notes For Permit 15030257 |
| Permit Number |
15030257 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2015-05-30 11:23:15 | NEW SINGLE FAMILY RESIDENCE, SECOND MECHANICAL REVIEW | | | COMMENTS | | | CODE: 2010 FBC. | | | | | | 1- EQUIPMENT SHOWN ON THE A/C PLAN EXCEEDS THE | | | CALCULATIONS. SEC. 403.6..1.1 OF 2010 FBC-ENERGY | | | CONSERVATION. | | | | | | 2- THERE IS NO INSULATED -EXTERIOR DOOR. SEE PLANS AND | | | PRODUCT APPROVALS. REVISE AS REQUIRED.SEC. 103.2.2 OF | | | 2010 FBC-ENERGY CONSERVATION. | | | | | | 3- ROOF WAS CHANGED FROM METAL TO CONCRETE TILE. REVISE | | | AS REQUIRED. SEC. 103.2.2 OF 2010 FBC-ENERGY | | | CONSERVATION. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561)805-6712 | | | [email protected] |
|