Plan Review Notes
Plan Review Notes For Permit 15030257
Permit Number 15030257
Review Stop B
Sequence Number 2
Notes
Date Text
2015-05-28 16:48:32NEW SINGLE FAMILY RESIDENCE (R3) SECOND BUILDING REVIEW
 COMMENTS.
 CODE: 2010 FBC.
  
 1- PROPERTY IS LOCATED IN FLOOD ZONE A5. (BASE FLOOR
 ELEVATION 7'-0"). ACCORDING TO REVISED SURVEY SUBMITTED
 THE GARAGE FINISH FLOOR ELEVATION IS BELOW THE BASE
 FLOOD ELEVATION. PROVIDE COMPLETE DETAILS AND
 SPECIFICATIONS SHOWING COMPLIANCE WITH SEC. R322.2.2 OF
 2010 FBC-RESIDENTIAL. ALSO, PROVIDE PRODUCT APPROVAL
 FOR THE FLOOD VENTS.
  
 2- SINGLE HUNG WINDOWS 24EH SPECIFIED ON BEDROOM #2, #3
 AND #4 DON'T COMPLY WITH THE EGRESS REQUIREMENTS OF
 SEC. R310 OF 2010 FBC-RESIDENTIAL. LETTER PROVIDED BY
 WINDOW MANUFACTURER SHOW CLEAR OPENING OF 5.58 S.F.
 THEY DON'T MEET THE OVERALL CLEAR OPENING OF 5.7 S.F.
 AS REQUIRED BY SEC. R310.1.1 OF 2010 FBC-RESIDENTIAL.
  
 3- SHEET S11:
 A) REVISE THE ATTIC LIVE LOAD TO SHOW COMPLIANCE WITH
 TABLE R301.5 OF 2010 FBC-RESIDENTIAL (NOTE: SEE
 FOOTNOTES B AND G OF TABLE R301.5).
  
 B) REVISE THE ROOF WIND DESIGN PRESSURES TO CORRESPOND
 TO EXPOSURE "D" NOT "C". SEC. R301.2.1.4.
  
 4- DRAFSTOPPING TO COMPLY WITH SEC. R302.12 OF 2010
 FBC-RESIDENTIAL. LOCATION OF DRAFSTOPPING SHOWN ON
 SHEET S7 IS EXCEEDING 1000 S.F. NEED TO SHOW
 DRAFSTOPPING BY BEDROOM #2 WING.
  
 5- ENERGY CALCULATIONS SUBMITTED:
 A) CALCULATIONS NEED TO BE DONE FOR THE ACTUAL
 ORIENTATION OF THE BUILDING NOT ROTATED 180 DEGREES.
 ORIENTATION OF BUILDING NEED TO BE TRUE NORTH, EAST,
 WEST AND SOUTH AS SHOWN ON SURVEY NOT N=>S, E=>W, ETC.
 REVISE AS REQUIRED. SEC. 103.2.2 OF 2010 FBC-ENERGY
 CONSERVATION.
  
 B) REVISE ROOF MATERIAL TO MATCH REVISED ROOF MATERIAL
 SPECIFIED ON PLANS.
  
 6- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 DCA RULE 9N-3 FOR:
 A) OVERHEAD GARAGE DOOR THAT MEETS THE DESIGN PRESSURES
 CALCULATED BY THE ENGINEER ON SHEET A3 AND A4. NOA
 13-0503.05 DOESN'T MEET THOSE DESIGN PRESSURES.
  
 B) FLOOD VENTS.
  
 C) SINGLE INSWING DOOR THAT MEETS THE DESIGN PRESSURES
 CALCULATED BY THE ENGINEER. DOOR WITH FLORIDA PRODUCT
 APPROVAL FL7630.1 SUBMITTED DOESN'T MEET THE CALCULATED
 DESIGN PRESSURES.
  
 D) ENTRY OUTSWING DOOR THAT MEETS THE DESIGN PRESSURES
 CALCULATED BY THE ENGINEER. DOOR WITH FLORIDA PRODUCT
 APPROVAL FL15037.3 SUBMITTED DOESN'T MEET THE
 CALCULATED DESIGN PRESSURES.
  
 7- DESIGNER OF RECORD TO REVIEW AND APPROVE ABOVE
 PRODUCT APPROVALS. SEC. 107.3.4.1 CITY AMENDMENTS.
  
  
 IMPORTANT:
 (1) CONTRACTOR WILL BE REQUIRED TO HIRE AN SPECIAL
 INSPECTOR FOR THE CONSTRUCTION AND INSTALLATION OF PILE
 DRIVING. SEC. 110.3.9 CITY AMENDMENTS. PLEASE
 COORDINATE WITH CHIEF BUILDING INSPECTOR KEN CONRAD
 (561)805-6666 FOR APPROVAL PRIOR TO ANY INSPECTIONS TO
 AVOID CONFLICTS OR DELAYS DURING CONSTRUCTION.
  
 (2) ELEVATION CERTIFICATES WILL BE REQUIRED DURING
 CONSTRUCTION. PLEASE COORDINATE WITH SAMANTHA HILL
 (561)805-6724 OR [email protected] FOR REVIEW OF INITIAL
 ELEVATION CERTIFICATES TO AVOID CONFLICTS OR DELAYS.
  
 ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 ***PLEASE REPLACE AND REMOVE ANY REVISED DRAWING.
 RE-SUBMIT OLD DRAWINGS FOR REFERENCE
  