| 2015-05-28 16:48:32 | NEW SINGLE FAMILY RESIDENCE (R3) SECOND BUILDING REVIEW |
| | COMMENTS. |
| | CODE: 2010 FBC. |
| | |
| | 1- PROPERTY IS LOCATED IN FLOOD ZONE A5. (BASE FLOOR |
| | ELEVATION 7'-0"). ACCORDING TO REVISED SURVEY SUBMITTED |
| | THE GARAGE FINISH FLOOR ELEVATION IS BELOW THE BASE |
| | FLOOD ELEVATION. PROVIDE COMPLETE DETAILS AND |
| | SPECIFICATIONS SHOWING COMPLIANCE WITH SEC. R322.2.2 OF |
| | 2010 FBC-RESIDENTIAL. ALSO, PROVIDE PRODUCT APPROVAL |
| | FOR THE FLOOD VENTS. |
| | |
| | 2- SINGLE HUNG WINDOWS 24EH SPECIFIED ON BEDROOM #2, #3 |
| | AND #4 DON'T COMPLY WITH THE EGRESS REQUIREMENTS OF |
| | SEC. R310 OF 2010 FBC-RESIDENTIAL. LETTER PROVIDED BY |
| | WINDOW MANUFACTURER SHOW CLEAR OPENING OF 5.58 S.F. |
| | THEY DON'T MEET THE OVERALL CLEAR OPENING OF 5.7 S.F. |
| | AS REQUIRED BY SEC. R310.1.1 OF 2010 FBC-RESIDENTIAL. |
| | |
| | 3- SHEET S11: |
| | A) REVISE THE ATTIC LIVE LOAD TO SHOW COMPLIANCE WITH |
| | TABLE R301.5 OF 2010 FBC-RESIDENTIAL (NOTE: SEE |
| | FOOTNOTES B AND G OF TABLE R301.5). |
| | |
| | B) REVISE THE ROOF WIND DESIGN PRESSURES TO CORRESPOND |
| | TO EXPOSURE "D" NOT "C". SEC. R301.2.1.4. |
| | |
| | 4- DRAFSTOPPING TO COMPLY WITH SEC. R302.12 OF 2010 |
| | FBC-RESIDENTIAL. LOCATION OF DRAFSTOPPING SHOWN ON |
| | SHEET S7 IS EXCEEDING 1000 S.F. NEED TO SHOW |
| | DRAFSTOPPING BY BEDROOM #2 WING. |
| | |
| | 5- ENERGY CALCULATIONS SUBMITTED: |
| | A) CALCULATIONS NEED TO BE DONE FOR THE ACTUAL |
| | ORIENTATION OF THE BUILDING NOT ROTATED 180 DEGREES. |
| | ORIENTATION OF BUILDING NEED TO BE TRUE NORTH, EAST, |
| | WEST AND SOUTH AS SHOWN ON SURVEY NOT N=>S, E=>W, ETC. |
| | REVISE AS REQUIRED. SEC. 103.2.2 OF 2010 FBC-ENERGY |
| | CONSERVATION. |
| | |
| | B) REVISE ROOF MATERIAL TO MATCH REVISED ROOF MATERIAL |
| | SPECIFIED ON PLANS. |
| | |
| | 6- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| | DCA RULE 9N-3 FOR: |
| | A) OVERHEAD GARAGE DOOR THAT MEETS THE DESIGN PRESSURES |
| | CALCULATED BY THE ENGINEER ON SHEET A3 AND A4. NOA |
| | 13-0503.05 DOESN'T MEET THOSE DESIGN PRESSURES. |
| | |
| | B) FLOOD VENTS. |
| | |
| | C) SINGLE INSWING DOOR THAT MEETS THE DESIGN PRESSURES |
| | CALCULATED BY THE ENGINEER. DOOR WITH FLORIDA PRODUCT |
| | APPROVAL FL7630.1 SUBMITTED DOESN'T MEET THE CALCULATED |
| | DESIGN PRESSURES. |
| | |
| | D) ENTRY OUTSWING DOOR THAT MEETS THE DESIGN PRESSURES |
| | CALCULATED BY THE ENGINEER. DOOR WITH FLORIDA PRODUCT |
| | APPROVAL FL15037.3 SUBMITTED DOESN'T MEET THE |
| | CALCULATED DESIGN PRESSURES. |
| | |
| | 7- DESIGNER OF RECORD TO REVIEW AND APPROVE ABOVE |
| | PRODUCT APPROVALS. SEC. 107.3.4.1 CITY AMENDMENTS. |
| | |
| | |
| | IMPORTANT: |
| | (1) CONTRACTOR WILL BE REQUIRED TO HIRE AN SPECIAL |
| | INSPECTOR FOR THE CONSTRUCTION AND INSTALLATION OF PILE |
| | DRIVING. SEC. 110.3.9 CITY AMENDMENTS. PLEASE |
| | COORDINATE WITH CHIEF BUILDING INSPECTOR KEN CONRAD |
| | (561)805-6666 FOR APPROVAL PRIOR TO ANY INSPECTIONS TO |
| | AVOID CONFLICTS OR DELAYS DURING CONSTRUCTION. |
| | |
| | (2) ELEVATION CERTIFICATES WILL BE REQUIRED DURING |
| | CONSTRUCTION. PLEASE COORDINATE WITH SAMANTHA HILL |
| | (561)805-6724 OR [email protected] FOR REVIEW OF INITIAL |
| | ELEVATION CERTIFICATES TO AVOID CONFLICTS OR DELAYS. |
| | |
| | ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH |
| | COMMENT TO EXPEDITE THE REVIEW PROCESS. |
| | ***PLEASE REPLACE AND REMOVE ANY REVISED DRAWING. |
| | RE-SUBMIT OLD DRAWINGS FOR REFERENCE |
| | |