2015-03-27 18:04:20NEW SINGLE FAMILY RESIDENCE, MECHANICAL REVIEW COMMENTS
 CODE: 2010 FBC.
  
 1- EQUIPMENT SIZING CALCULATIONS NEED TO BE DONE BASED
 ON THE BUILDING LOADS FOR THE DIRECTIONAL ORIENTATION
 OF THE BUILDING AS REQUIRED BY SEC. 403.6 OF 2010
 FBC-ENERGY CONSERVATION. ENERGY CALCULATIONS WERE DONE
 WITH THE BUILDING ROTATION OF 270 DEGREES. SAME NUMBERS
 WERE USED FOR THE EQUIPMENT SIZING. NEED TO REVISE AS
 REQUIRED
  
 2- REVISE NUMBER OF OCCUPANTS USED FOR THE EQUIPMENT
 SIZING CALCULATIONS. THERE ARE NO THAT MANY PEOPLE IN A
 SINGLE FAMILY RESIDENCE. SEC. 403.6 OF 2010 FBC-ENERGY
 CONSERVATION.
  
 3- PROVIDE MANUFACTURER SPECS FOR THE BBQ GRILL SHOWING
 THAT IS DESIGNED TO BE INSTALLED IN THE SCREENED LANAI
 AREA AS SHOWN ON PLANS. SEC. 107.2.1 CITY AMENDMENTS
 AND SEC. M1901.2 OF 2010 FBC-RESIDENTIAL.
  
 4- A/C PLAN TO HAVE THE NAME AND SIGNATURE OF THE
 PERSON RESPONSIBLE FOR THE DESIGN AS REQUIRED BY SEC.
 107.2.1 CITY AMENDMENTS TO FBC.
  
  
 ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 ***PLEASE REPLACE AND REMOVE ANY REVISED DRAWING.
 RE-SUBMIT OLD DRAWINGS FOR REFERENCE
  