Plan Review Notes
Plan Review Notes For Permit 15030257
Permit Number 15030257
Review Stop G
Sequence Number 1
Notes
Date Text
2015-04-04 10:18:491) SUBMIT MANUFACTURER'S SPECIFICATION SHEETS FOR ALL
 GAS APPLIANCES. GAS APPLIANCES SHALL BE LISTED AND
 LABELED PER THE 2010 FUEL GAS CODE SEC.301.3.
 2) SUBMIT MANUF. SPECIFICATIONS FOR THE 2 PSI REGULATOR
 AND INDICATE IF REGULATOR IS LOCATED ON THE INTERIOR OR
 EXTERIOR OF THE STRUCTURE. IF ON THE INTERIOR, THE
 REGULATOR SHALL BE VENTED PER THE 2010 FGC SEC.403.6.3,
 410.1. SHOW VENT PIPING ON PLANS IF ON INTERIOR.
 3) SHOW THE TYPE OF PIPING, SIZE, AND LENGTH OF THE
 SECTION TO THE WATER HEATER. COMPLY WITH 2010 FGC SEC.
 402.4 ( 2 ).
 4) SHOW THE TRANSITION POINT ON THE PIPING DIAGRAM
 WHERE THE PE PIPE TRANSITIONS TO ANOTHER TYPE OF PIPE
 ON THE PLANS. PE PIPE CAN ONLY BE USED OUTSIDE,
 UNDERGROUND. 2010 FGC SEC.404.15.1.
  