| Plan Review Notes For Permit 15030257 |
| Permit Number |
15030257 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-04-16 18:36:17 | PLAN REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC 2010 | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | APPROVED WITH EXCEPTION. THIS PLAN HAS BEEN APPROVED | | | PROVISIONALLY. FAILURE TO CORRECT THE LISTED | | | DEFICIENCIES IN THIS PLAN PRIOR TO INSPECTION WILL | | | RESULT IN FAILED INSPECTION(S) AND ASSESSMENT OF | | | RE-INSPECTION FEE(S). | | | ELECTRICAL REVISION REQUIRED | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | 1) NEC 310.15(B)(6) FEEDER FROM METER TO DISCONNECT TO | | | BE 250 THWN CU OR EQUAL. | | | 2) FBC-R 315.1 PROVIDE CARBON MONOXIDE ALARMS WITHIN 10 | | | FEET OF EACH SLEEPING ROOM. | | | 3) NEC 410.16 (A) - (C) - LUMINAIRES IN CLOTHES CLOSETS | | | SHALL BE OF THE TYPE PERMITTED AND LOCATED AS REQUIRED. | | | 4) NEC 314.27(C) FLOOR RECEPTACLES REQUIRE FLOOR BOXES | | | LISTED FOR THIS APPLICATION. | | | 5) NEC 250.104(B) THE GAS PIPING IS REQUIRED TO BE | | | BONDED. | | | 6) NEC 440.11 & 440.14 THE REQUIRED A/C EQUIPMENT | | | DISCONNECTING MEANS SHALL BE READILY ACCESSIBLE. | | | 7) NEC 110.33(B) PERMANENT LADDERS OR STAIRWAYS ARE | | | REQUIRED FOR ELECTRICAL EQUIPMENT LOCATED IN ATTICS. | | | 8) NEC 210.63 - PROVIDE A SERVICE OUTLET AT AN | | | ACCESSIBLE LOCATION WITHIN 25' OF MECHANICAL EQUIPMENT. | | | (ATTIC A/H) | | | 9) NEC 210.11 (C) (3) AT LEAST ONE 20 - AMP BRANCH | | | CIRCUIT SHALL BE PROVIDED TO SUPPLY BATHROOM RECEPTACLE | | | OUTLETS. | | | | | | |
|