2015-04-16 18:36:17PLAN REVIEW COMMENTS
  
 1ST REVIEW: FBC 2010
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 APPROVED WITH EXCEPTION. THIS PLAN HAS BEEN APPROVED
 PROVISIONALLY. FAILURE TO CORRECT THE LISTED
 DEFICIENCIES IN THIS PLAN PRIOR TO INSPECTION WILL
 RESULT IN FAILED INSPECTION(S) AND ASSESSMENT OF
 RE-INSPECTION FEE(S).
 ELECTRICAL REVISION REQUIRED
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
 1) NEC 310.15(B)(6) FEEDER FROM METER TO DISCONNECT TO
 BE 250 THWN CU OR EQUAL.
 2) FBC-R 315.1 PROVIDE CARBON MONOXIDE ALARMS WITHIN 10
 FEET OF EACH SLEEPING ROOM.
 3) NEC 410.16 (A) - (C) - LUMINAIRES IN CLOTHES CLOSETS
 SHALL BE OF THE TYPE PERMITTED AND LOCATED AS REQUIRED.
 4) NEC 314.27(C) FLOOR RECEPTACLES REQUIRE FLOOR BOXES
 LISTED FOR THIS APPLICATION.
 5) NEC 250.104(B) THE GAS PIPING IS REQUIRED TO BE
 BONDED.
 6) NEC 440.11 & 440.14 THE REQUIRED A/C EQUIPMENT
 DISCONNECTING MEANS SHALL BE READILY ACCESSIBLE.
 7) NEC 110.33(B) PERMANENT LADDERS OR STAIRWAYS ARE
 REQUIRED FOR ELECTRICAL EQUIPMENT LOCATED IN ATTICS.
 8) NEC 210.63 - PROVIDE A SERVICE OUTLET AT AN
 ACCESSIBLE LOCATION WITHIN 25' OF MECHANICAL EQUIPMENT.
 (ATTIC A/H)
 9) NEC 210.11 (C) (3) AT LEAST ONE 20 - AMP BRANCH
 CIRCUIT SHALL BE PROVIDED TO SUPPLY BATHROOM RECEPTACLE
 OUTLETS.
  
  