Plan Review Notes
Plan Review Notes For Permit 15030257
Permit Number 15030257
Review Stop B
Sequence Number 1
Notes
Date Text
2015-03-27 17:35:41NEW SINGLE FAMILY RESIDENCE (R3), BUILDING REVIEW
 COMMENTS.
 CODE: 2010 FBC.
  
 1- BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG RD.)
 FOR IMPACT FEES ASSESSMENT. BRING BACK COUNTY STAMPED
 PLANS AND COPY OF PAID RECEIPT IF FEES ARE DUE. COUNTY
 IMPACT FEE ORDINANCE OF THE UNIFIED LAND DEVELOPMENT
 CODE.
  
 2- PROPERTY IS LOCATED IN FLOOD ZONE A5. (BASE FLOOR
 ELEVATION 7'-0"). PROVIDE COMPLETE INFORMATION SHOWING
 COMPLIANCE WITH SEC. R322 OF 2010 FBC-RESIDENTIAL.
 CLEARLY IDENTIFY FINISH FLOOR ELEVATION FOR MAIN HOUSE,
 GARAGE AND EQUIPMENT. NOTE: CITY ORDINANCE REQUIRES
 FINISH FLOOR TO BE MINIMUM 6" ABOVE BASE FLOOD
 ELEVATION. ELEVATION CERTIFICATES WILL BE REQUIRED
 DURING CONSTRUCTION.
  
 3- WINDOWS ON BEDROOM #2, #3 AND #4 DON'T SEEM TO
 COMPLY WITH THE EGRESS REQUIREMENTS OF SEC. R310 OF
 2010 FBC-RESIDENTIAL. SHOW COMPLIANCE. CLEARLY SPECIFY
 SIZE OF WINDOWS AND PROVIDE WINDOW MANUFACTURER'S CUT
 SHEETS FOR THE SIZE OF WINDOWS SPECIFIED.
  
 4- BUILDING IS LOCATED IN EXPOSURE "D" NOT "C". REVISE
 ALL THE INFORMATION ON SHEETS A3 AND A4. SEC.
 R301.2.1.4 OF 2010 FBC-RESIDENTIAL.
 NOTE: REVISE WINDOWS AND DOORS DESIGN PRESSURES
 ACCORDING TO BUILDING HEIGHT AND OPENING LOCATION.
 (INTERIOR /END LOCATION).
  
 5- SHEET S11:
 A) SPECIFY ALL DEAD AND LIVE LOADS, INCLUDING THE ATTIC
 LIVE LOADS AS REQUIRED BY TABLE R301.5 OF 2010
 FBC-RESIDENTIAL (NOTE: SEE FOOTNOTES B AND G OF TABLE
 R301.5).
  
 B) BUILDING EXPOSURE IS "D" NOT "C". SEC. R301.2.1.4.
 REVISE AS REQUIRED.
  
 C) CLEARLY IDENTIFY THE ULTIMATE AND THE NOMINAL WIND
 LOADS. SEC. R301.2.1.3.
  
 D) REVISE THE ROOF WIND DESIGN PRESSURES. BUILDING
 LOCATED IN EXPOSURE "D" NOT "C". SEC. R301.2.1.4.
  
 E) FASTENER SCHEDULE: (1) SPECIFY SIZE OF GARAGE
 STRUCTURAL BUCK. (2) CLARIFY NOTE #7: WHY AN EXTERIOR
 DOOR WITH A WOOD DOOR FRAME DOESN'T REQUIRE A BUCK THAT
 PROVIDE FULL SUPPORT T OF THE DOOR FRAME AS REQUIRED BY
 SEC. R612.10.2.1 OF 2010 FBC-RESIDENTIAL.
  
 6- SHEET D1:
 A) PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE
 SOFFIT CONSTRUCTION SHOWING COMPLIANCE WITH SEC.
 R703.1.3 OF 2010 FBC-RESIDENTIAL.
  
 B) SPECIFY ROOF VENTILATING AS REQUIRED BY SEC. R806 OF
 2010 FBC-RESIDENTIAL.
  
 C) REVISE STRUCTURAL BUCK DETAILS FOR DOORS. BUCK SIZE
 NEED TO PROVIDE FULL SUPPORT TO THE DOOR FRAME AS
 REQUIRED BY SEC. R612.10.2.1 OF 2010 FBC-RESIDENTIAL.
  
 7- NEED CARBON MONOXIDE ALARM WITHIN 10'-0" OF MASTER
 BEDROOM. SEC. R315 OF 2010 FBC-RESIDENTIAL.
  
 8- PROVIDE COMPLETE DETAIL AND SPECIFICATIONS FOR WOOD
 POST WD1. SPECIFY FOOTING AND TOP AND BOTTOM
 CONNECTIONS. NOTE: SIMPSON ABU46 BASE CONNECTOR
 SPECIFIED ON SHEET S3 IS NOT ADEQUATE FOR A 4"X8" WOOD
 POST. REVISE AS REQUIRED. SEC. R301.1 OF 2010
 FBC-RESIDENTIAL.
  
 9- DRAFSTOPPING SHALL DIVIDE THE CONCEALED SPACE INTO
 APPROXIMATELY EQUAL AREAS AS REQUIRED BY SEC. R302.12
 OF 2010 FBC-RESIDENTIAL. REVISE LOCATION OF
 DRAFSTOPPING ON SHEET S7. AND SPECIFY DRAFSTOPPING
 MATERIAL.
  
 10-ENERGY CALCULATIONS SUBMITTED:
 A) REVISE NUMBER OF BEDROOMS TO MATCH PLANS. SEC.
 103.2.2 OF 2010 FBC-ENERGY CONSERVATION.
  
 B) IF CALCULATIONS ARE NOT DONE AS A WORST CASE
 SCENARIO, THEN WHY IT WAS ROTATED 270 DEGREES?. REVISE
 AS REQUIRED. SEC. 103.2.2 OF 2010 FBC-ENERGY
 CONSERVATION.
  
 C) REVISE FIRST FLOOR CEILING AREA SHOWN ON PAGE 3 OF 6
 TO MATCH FLOOR PLAN ON SHEET A1. SEC. 103.2.2 OF 2010
 FBC-ENERGY CONSERVATION.
  
 D) REVISE DOOR TYPE SHOWN ON PAGE 3 OF 6 TO MATCH FLOOR
 PLANS AND PRODUCT APPROVALS SUBMITTED. SEC. 103.2.2 OF
 2010 FBC-ENERGY CONSERVATION. THERE ARE NOT WOOD DOORS.
  
 E) REVISE WINDOWS OVERHANG DEPTH AND SEPARATION TO
 MATCH PLANS. SEC. 103.2.2 OF 2010 FBC-ENERGY
 CONSERVATION.
  
 F) REVISE GARAGE AREA TO MATCH FLOOR PLAN ON SHEET A1.
 SEC. 103.2.2 OF 2010 FBC-ENERGY CONSERVATION.
  
 11- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE
 SCREEN ENCLOSURE IN THE LANAI AREA. SEC. R301.1 OF 2010
 FBC-RESIDENTIAL.
  
 12- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 DCA RULE 9N-3 FOR:
 A) METAL ROOF AS SPECIFIED ON PLANS. CLARIFY WHY
 SUBMITTING NOA FOR CONCRETE TILE?. AND WHY TWO
 DIFFERENT TILE NOA'S.?
  
 B) SLIDING GLASS DOORS. NOA 14-0123.10 SUBMITTED
 EXPIRED ON FEBRUARY 17, 2015. NEED CURRENT NOA.
  
 C) OVERHEAD GARAGE DOOR SIZE AS SHOWN ON PLANS. NOA
 12-0228.15 SUBMITTED IS FOR 16"-0" DOORS. NEED 18'-0"
 DOOR.
  
 D) PRECAST LINTELS AS SPECIFIED ON PLANS. NOTE:
 DESIGNER OF RECORD MAY LIST THE NOA OR FLORIDA PRODUCT
 APPROVAL NUMBER NEXT TO THE SPECIFIED LINTEL.
  
 E) ALL USP AND SIMPSON STRUCTURAL CONNECTORS SPECIFIED
 ON FRAMING PLANS AND ALL DETAILS. NOTE: PROVIDE ONLY
 THE FLORIDA PRODUCT APPROVAL COVER PAGE AND PAGE
 SHOWING THE SPECIFIED CONNECTOR OR DESIGNER OF RECORD
 MAY LIST FLORIDA PRODUCT APPROVAL NUMBER NEXT TO THE
 SPECIFIED CONNECTOR IN ALL DETAILS.
  
 F) BAHAMA SHUTTERS AND COLONIAL SHUTTERS AS SHOWN ON
 PLANS. AND PROVIDE COMPLETE INSTALLATION SCHEDULE.
 CONTRACTOR MAY USE THE CITY SAMPLE FOR SHUTTERS
 INSTALLATION OR PROVIDE ALL THE REQUIRED INFORMATION IN
 A DIFFERENT FORMAT.
  
 13- CLARIFY WHY SUBMITTING PRODUCT APPROVAL FOR FIXED
 WINDOWS. THERE ARE NOT FIXED WINDOWS SHOWN ON PLANS.
 SEC. 107.2.1 CITY AMENDMENTS.
  
 14- DESIGNER OF RECORD TO REVIEW AND APPROVE ABOVE
 PRODUCT APPROVALS. SEC. 107.3.4.1 CITY AMENDMENTS.
  
 15- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE
 CONSTRUCTION AND INSTALLATION OF THE LATTICE SHOWN ON
 FRONT ELEVATION. SEC. R301.1 OF 2010 FBC-RESIDENTIAL.
  
 16- SPECIFY ATTIC ACCESS SIZE ON ALL LOCATIONS SHOWN ON
 PLANS. SEC. R807 OF 2010 FBC RESIDENTIAL.
  
 17- PROVIDE DRAINAGE PLAN. SEC. R401.3 OF 2010
 FBC-RESIDENTIAL.
  
 18- PROVIDE SPECIFICATIONS FOR THE GARAGE DOORS LEADING
 TO THE KITCHEN AREA AND LAUNDRY AREA TO SHOW COMPLIANCE
 WITH SEC. R302.5.1 OF 2010 FBC-RESIDENTIAL.
  
 19- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE
 CONSTRUCTION AND INSTALLATION OF GUARDRAILS SHOWING
 COMPLIANCE WITH THE DESIGN LOADS OF TABLE R301.5 AND
 THE REQUIREMENTS OF SEC. R312 OF 2010 FBC-RESIDENTIAL.
  
 20- PROVIDE COMPLETE DETAILS S AND SPECIFICATIONS FOR
 THE BALCONY'S' FINISH MATERIALS. SPECIFY WATERPROOFING
 AND FINISH MATERIALS. AND PROVIDE CORRESPONDING PRODUCT
 APPROVALS.
  
 21- CONTRACTOR WILL BE REQUIRED TO HIRE AN SPECIAL
 INSPECTOR FOR THE CONSTRUCTION AND INSTALLATION OF PILE
 DRIVING. SEC. 110.3.9 CITY AMENDMENTS. PLEASE
 COORDINATE WITH CHIEF BUILDING INSPECTOR KEN CONRAD
 (561)805-6666.
  
 ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 ***PLEASE REPLACE AND REMOVE ANY REVISED DRAWING.
 RE-SUBMIT OLD DRAWINGS FOR REFERENCE
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712
 [email protected]