Plan Review Notes
Plan Review Notes For Permit 15030253
Permit Number 15030253
Review Stop B
Sequence Number 1
Notes
Date Text
2015-03-09 14:09:42RE-ROOF BUILDING REVIEW COMMENTS
 CODE: 2010 FBC.
  
 1- MODIFIED BITUMEN ROOF SYSTEM FL10497-R2 SUBMITTED:
 THE DESIGN PRESSURES OF SELECTED ROOF ASSEMBLY W-12 ARE
 -60 PSF. NEED TO PROVIDE SIGNED AND SEALED RAS 117
 CALCULATIONS AS REQUIRED BY NOTE #8 (PAGE 2 OF 16) TO
 MEET THE DESIGN PRESSURES REQUIRED BY SEC. 1609 OF 2010
 FBC.
  
 2- BORAL ROOFING UNDERLAYMENT FL14317-R5: IF USING A
 DIRECT-BOND TO DECK UNDERLAYMENT, THEN SEE DESIGN
 PRESSURES ON LIMITATIONS 5.5. SELECTED UNDERLAYMENT
 NEEDS TO MEET THE DESIGN PRESSURES OF ALL ROOF ZONES
 INCLUDING PERIMETER AND CORNER AREAS. IF SELECTED
 UNDERLAYMENT DOESN'T MEET THE DESIGN PRESSURES OF ALL
 ROOF ZONES, THEN IT CAN'T BE USED.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT