Plan Review Notes
Plan Review Notes For Permit 15030207
Permit Number 15030207
Review Stop E
Sequence Number 1
Notes
Date Text
2015-03-23 12:48:243/23/2015
 PROJECT: TENANT IMPROVEMENT SUITE 5600
 PERMIT#: 15030207
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 1ST ELECTRICAL PLAN REVIEW
 ACTION: APPROVED WITH EXCEPTION
  
 THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO
 CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO
 INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE
 ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE
 ADDITIONAL REVIEWS WITH ASSOCIATED FEES. REVISION
 REQUIRED BEFORE FRAMING INSPECTION.
  
 1) FBC-ENERGY
 505.2 LIGHTING CONTROLS (MANDATORY).
 SHOW COMPLIANCE WITH THE FLC-ENERGY SECTION 505. 2.2.
 AUTOMATIC LIGHTING SHUTOFF.
 BUILDINGS LARGER THAN 5,000 SQUARE FEET (465 M2) SHALL
 BE EQUIPPED WITH AN AUTOMATIC CONTROL DEVICE TO SHUT
 OFF LIGHTING IN THOSE AREAS.
  
 2) NEC 700.12
 THE BRANCH CIRCUIT FEEDING THE UNIT EQUIPMENT SHALL BE
 THE SAME BRANCH CIRCUIT AS THAT SERVING THE NORMAL
 LIGHTING IN THE AREA AND CONNECTED AHEAD OF ANY LOCAL
 SWITCHES
  
 3) NEC 700.16
 EMERGENCY LIGHTING SYSTEMS SHALL BE DESIGNED AND
 INSTALLED SO THAT THE FAILURE OF ANY INDIVIDUAL
 LIGHTING ELEMENT, SUCH AS THE BURNING OUT OF A LAMP,
 CANNOT LEAVE IN TOTAL DARKNESS ANY SPACE THAT REQUIRES
 EMERGENCY ILLUMINATION.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]