| 2015-03-23 12:48:24 | 3/23/2015 |
| | PROJECT: TENANT IMPROVEMENT SUITE 5600 |
| | PERMIT#: 15030207 |
| | CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC |
| | ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| | ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| | 1ST ELECTRICAL PLAN REVIEW |
| | ACTION: APPROVED WITH EXCEPTION |
| | |
| | THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO |
| | CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO |
| | INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE |
| | ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE |
| | ADDITIONAL REVIEWS WITH ASSOCIATED FEES. REVISION |
| | REQUIRED BEFORE FRAMING INSPECTION. |
| | |
| | 1) FBC-ENERGY |
| | 505.2 LIGHTING CONTROLS (MANDATORY). |
| | SHOW COMPLIANCE WITH THE FLC-ENERGY SECTION 505. 2.2. |
| | AUTOMATIC LIGHTING SHUTOFF. |
| | BUILDINGS LARGER THAN 5,000 SQUARE FEET (465 M2) SHALL |
| | BE EQUIPPED WITH AN AUTOMATIC CONTROL DEVICE TO SHUT |
| | OFF LIGHTING IN THOSE AREAS. |
| | |
| | 2) NEC 700.12 |
| | THE BRANCH CIRCUIT FEEDING THE UNIT EQUIPMENT SHALL BE |
| | THE SAME BRANCH CIRCUIT AS THAT SERVING THE NORMAL |
| | LIGHTING IN THE AREA AND CONNECTED AHEAD OF ANY LOCAL |
| | SWITCHES |
| | |
| | 3) NEC 700.16 |
| | EMERGENCY LIGHTING SYSTEMS SHALL BE DESIGNED AND |
| | INSTALLED SO THAT THE FAILURE OF ANY INDIVIDUAL |
| | LIGHTING ELEMENT, SUCH AS THE BURNING OUT OF A LAMP, |
| | CANNOT LEAVE IN TOTAL DARKNESS ANY SPACE THAT REQUIRES |
| | EMERGENCY ILLUMINATION. |
| | |
| | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| | 561-805-6717 OR [email protected] |