| Plan Review Notes For Permit 15030181 |
| Permit Number |
15030181 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-03-10 12:39:37 | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, | | | FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | PLEASE CONSIDER THE FOLLOWING AS PROVISO: | | | | | | ALL WATER LINE CONNECTED TO A FIRE HYDRANT AND/OR FDC | | | IS CONSIDERED AND INSPECTED AS A FIRE LINE PER NFPA 24 | | | AND SHALL BE INSPECTED AND APPROVED BY A WEST PALM | | | BEACH FIRE INSPECTOR PRIOR TO COVERING OVER. ALL JOINTS | | | SHALL BE VISIBLE AND ACCESSIBLE. | | | | | | PROVIDE MANUFACTURES CUT SHEETS FOR FIRE INSPECTOR | | | REVIEW AND CONFIRMATION WHEN ON SITE. | | | | | | PROVIDE A TORQUE WRENCH TO VERIFY PROPER BOLT | | | TIGHTNESS. | | | | | | PROVIDE THE MEANS AND VERIFICATION OF FIRE LINE | | | FLUSHING PER NFPA 24 @10FT/SEC. |
|