Plan Review Notes
Plan Review Notes For Permit 15030166
Permit Number 15030166
Review Stop M
Sequence Number 1
Notes
Date Text
2015-04-28 18:31:41PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC 2010
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY MECHANICAL
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE ENERGY FORM IS MISSING THE FOLLOWING
 INFORMATION: OWNER, BUILDER NAME, PERMIT OFFICE ( CITY
 OF WEST PALM BEACH ), JURISDICTION ( 604700 ). FBC
 107.2.1.4
  
 2) THE PRODUCT APPROVAL THAT WAS SUBMITTED FOR THE
 FRONT DOOR IS FOR A GLAZED SINGLE FRENCH DOOR WHERE THE
 GLASS AREA IS EQUAL OR GREATER THAN ONE THIRD OF THE
 DOOR AREA. THIS DOOR IS REQUIRED TO BE INCLUDED IN THE
 GLAZING CALCULATION AS A TOTAL FENESTRATION. FBC ENERGY
 SECTION 405.5.3


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved