| Plan Review Notes For Permit 15030161 |
| Permit Number |
15030161 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-05-12 18:51:00 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC 2010 | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY ELECTRIC | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) THE SQUARE FOOTAGE SPECIFIED FOR THE GENERAL | | | LIGHTING CALCULATIONS DOES NOT MATCH THE SQUARE FOOTAGE | | | LISTED IN THE AREA CALCULATIONS. THE AVANTI ( LEFT AND | | | RIGHT ) HAS 1764 AND NOT 1867. THE CASSANDRA PLANS ARE | | | MISSING FROM THIS SUBMITTAL. THE MADERA ( RIGHT ) HAS | | | 1836 AND NOT 1764 ( CHECK ADDITION ). THE MADERA ( LEFT | | | ) HAS 1764 AND SHOULD BE 1765 ( CHECK ADDITION ). FBC | | | 107.2.1 | | | | | | 2) THE BREAKER PANEL IS NOT SHOWN ON THE ELECTRICAL | | | FLOOR PLAN THE WAY IT IS DESIGNATED IN THE ELECTRICAL | | | LEGEND ON THE A1 PLANS. | | | |
|