| Plan Review Notes For Permit 15030160 |
| Permit Number |
15030160 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-04-13 06:33:09 | 1) SUBMIT A WATER RISER FOR THE DIFFERENT MODELS. WPB | | | AMEND. TO 2010 FBC SEC. 107.3.5.3. | | | 2) THE LANDSCAPE PLAN SHOWS THE WATER SUPPLY FOR THE | | | IRRIGATION SYSTEM AS CITY WATER. THE IRRIGATION SYSTEM | | | SHALL BE PROTECTED AGAINST BACKFLOW PER THE CITY'S | | | CROSS CONNECTION MANUAL. CONTACT STEVEN HUNTER AT | | | 561-805-2240 FOR THE PROPER TYPE OF BACKFLOW DEVICE TO | | | BE INSTALLED. | | | 3) THE WATER HEATERS IN THE GARAGES SHALL BE PROTECTED | | | FROM VEHICLE IMPACT. | | | 4) SHOW THE LOCATION OF THE CONTROLLER AND RAIN SENSOR | | | FOR THE IRRIGATION SYSTEM. A RAIN SENSOR IS REQUIRED ON | | | THE IRRIGATION SYSTEM PER FL. STATUTE 373.62. | | | | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] | | | | | | |
|