| Plan Review Notes For Permit 15030102 |
| Permit Number |
15030102 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-04-02 13:56:23 | 15030102 | | | 5801 @ ERNST ST. | | | GENERATOR FOR TOWER #2 | | | | | | PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING | | | REVIEW COMMENTS. | | | | | | A DISCONNECTING MEANS IS REQUIRED AT THE GENERATOR. NEC | | | 445.18 | | | | | | THE AMPACITY OF THE CONDUCTORS TO THE THE FIRST | | | DISTRIBUTION DEVICE WITH OVERCURRENT PROTECTION SHALL | | | NOT BE LESS THAT 115% OF THE NAMEPLATE CURRENT RATING | | | OF THE GENERATOR. NEC 445.13 | | | | | | INDICATE THE SIZE OF THE CONDUIT AND WIRING METHOD | | | PROPOSED FROM THE GENERATOR TO THE MODULAR BUILDING. | | | NEC 215.5 | | | | | | PROVIDE A GROUNDING SYSTEM FOR THE GENERATOR. NEC | | | 250.20, 250.30 | | | | | | | | | ROBERT LECKY, CBO | | | ELECTRICAL PLANS REVIEW | | | 561-373-3701 | | | [email protected] | | | | | | |
|