2015-04-02 13:56:2315030102
 5801 @ ERNST ST.
 GENERATOR FOR TOWER #2
  
 PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING
 REVIEW COMMENTS.
  
 A DISCONNECTING MEANS IS REQUIRED AT THE GENERATOR. NEC
 445.18
  
 THE AMPACITY OF THE CONDUCTORS TO THE THE FIRST
 DISTRIBUTION DEVICE WITH OVERCURRENT PROTECTION SHALL
 NOT BE LESS THAT 115% OF THE NAMEPLATE CURRENT RATING
 OF THE GENERATOR. NEC 445.13
  
 INDICATE THE SIZE OF THE CONDUIT AND WIRING METHOD
 PROPOSED FROM THE GENERATOR TO THE MODULAR BUILDING.
 NEC 215.5
  
 PROVIDE A GROUNDING SYSTEM FOR THE GENERATOR. NEC
 250.20, 250.30
  
  