Plan Review Notes
Plan Review Notes For Permit 15030075
Permit Number 15030075
Review Stop E
Sequence Number 3
Notes
Date Text
2015-07-20 12:02:0107/20/2015
 PROJECT: NICHOLAS KASSALTY RESIDENCE
 PERMIT#: 15030075
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 3RD ELECTRICAL PLAN REVIEW
 ACTION: APPROVED WITH EXCEPTION. THE PLANS HAVE BEEN
 APPROVED PROVISIONALLY. FAILURE TO CORRECT THE LISTED
 DEFICIENCIES PRIOR TO INSPECTION WILL RESULT IN FAILED
 INSPECTION(S) AND THE ASSESSMENT OF RE-INSPECTION
 FEE(S).
  
 1) VERIFY THE TYPE OF DRYER TO BE INSTALLED. VERIFY THE
 LOAD ON THE ELECTRICAL SERVICE. IF AN ELECTRICAL DRYER
 IS TO BE INSTALLED, REVISE THE LOAD CALCULATION TO
 INCLUDE THE 5000VA REQUIRED FOR THE DRYER LOAD.
 REVISE THE PANEL SCHEDULE TO INCLUDE THE ELECTRICAL
 CIRCUIT FOR THE DRYER.
  
 2) VERIFY RISER DIAGRAM TO INDICATE COMPLIANCE WITH THE
 NEC. IT IS NOT CLEAR IF THE EXISTING CONDUIT FROM THE
 SERVICE MAIN TO THE EXISTING (OLD PANEL/JBOX) IS METAL.
 METAL ENCLOSURES AND RACEWAYS FOR OTHER THAN SERVICE
 CONDUCTORS SHALL BE CONNECTED TO THE EQUIPMENT
 GROUNDING CONDUCTOR. NEC 250.86
 METAL RACEWAYS AND ENCLOSURES, THAT ARE TO SERVE AS
 GROUNDING CONDUCTORS SHALL BE BONDED WHERE NECESSARY TO
 ENSURE ELECTRICAL CONTINUITY AND THE CAPACITY TO
 CONDUCT SAFELY ANY FAULT CURRENT LIKELY TO BE IMPOSED
 ON THEM. NEC 250.96
  
 3) VERIFY ALL REQUIRED SMOKE DETECTORS. WHEN
 ALTERATIONS, REPAIRS, OR ADDITIONS REQUIRING A PERMIT
 OCCUR, OR WHEN ONE OR MORE SLEEPING ROOMS ARE ADDED OR
 CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL DWELLING
 UNIT SHALL BE EQUIPPED WITH SMOKE ALARMS LOCATED AS
 REQUIRED FOR NEW DWELLINGS. FBC-RESIDENTIAL 314 AND
 315.
  
 4) VERIFY THE A/C CU LOCATIONS AT THE EXTERIOR OF THE
 DWELLING. INDICATE THE REQUIRED GFI OUTLETS WITHIN
 SIGHT OF THE A/C EQUIPMENT. NEC 210.63
  
 5) ALL NEW GENERAL PURPOSE OUTLETS MUST BE TAMPER
 RESISTANT NEC 406.11
  
 6) ALL 15 AND 20 AMP BRANCH CIRCUITS SUPPLYING OUTLETS
 INSTALLED IN THE DWELLING UNIT SHALL BE PROTECTED BY A
 LISTED ARC-FAULT CIRCUIT INTERRUPTER. NEC 210.12
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  