| 2015-07-20 12:02:01 | 07/20/2015 |
| | PROJECT: NICHOLAS KASSALTY RESIDENCE |
| | PERMIT#: 15030075 |
| | CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC |
| | ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| | ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| | 3RD ELECTRICAL PLAN REVIEW |
| | ACTION: APPROVED WITH EXCEPTION. THE PLANS HAVE BEEN |
| | APPROVED PROVISIONALLY. FAILURE TO CORRECT THE LISTED |
| | DEFICIENCIES PRIOR TO INSPECTION WILL RESULT IN FAILED |
| | INSPECTION(S) AND THE ASSESSMENT OF RE-INSPECTION |
| | FEE(S). |
| | |
| | 1) VERIFY THE TYPE OF DRYER TO BE INSTALLED. VERIFY THE |
| | LOAD ON THE ELECTRICAL SERVICE. IF AN ELECTRICAL DRYER |
| | IS TO BE INSTALLED, REVISE THE LOAD CALCULATION TO |
| | INCLUDE THE 5000VA REQUIRED FOR THE DRYER LOAD. |
| | REVISE THE PANEL SCHEDULE TO INCLUDE THE ELECTRICAL |
| | CIRCUIT FOR THE DRYER. |
| | |
| | 2) VERIFY RISER DIAGRAM TO INDICATE COMPLIANCE WITH THE |
| | NEC. IT IS NOT CLEAR IF THE EXISTING CONDUIT FROM THE |
| | SERVICE MAIN TO THE EXISTING (OLD PANEL/JBOX) IS METAL. |
| | METAL ENCLOSURES AND RACEWAYS FOR OTHER THAN SERVICE |
| | CONDUCTORS SHALL BE CONNECTED TO THE EQUIPMENT |
| | GROUNDING CONDUCTOR. NEC 250.86 |
| | METAL RACEWAYS AND ENCLOSURES, THAT ARE TO SERVE AS |
| | GROUNDING CONDUCTORS SHALL BE BONDED WHERE NECESSARY TO |
| | ENSURE ELECTRICAL CONTINUITY AND THE CAPACITY TO |
| | CONDUCT SAFELY ANY FAULT CURRENT LIKELY TO BE IMPOSED |
| | ON THEM. NEC 250.96 |
| | |
| | 3) VERIFY ALL REQUIRED SMOKE DETECTORS. WHEN |
| | ALTERATIONS, REPAIRS, OR ADDITIONS REQUIRING A PERMIT |
| | OCCUR, OR WHEN ONE OR MORE SLEEPING ROOMS ARE ADDED OR |
| | CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL DWELLING |
| | UNIT SHALL BE EQUIPPED WITH SMOKE ALARMS LOCATED AS |
| | REQUIRED FOR NEW DWELLINGS. FBC-RESIDENTIAL 314 AND |
| | 315. |
| | |
| | 4) VERIFY THE A/C CU LOCATIONS AT THE EXTERIOR OF THE |
| | DWELLING. INDICATE THE REQUIRED GFI OUTLETS WITHIN |
| | SIGHT OF THE A/C EQUIPMENT. NEC 210.63 |
| | |
| | 5) ALL NEW GENERAL PURPOSE OUTLETS MUST BE TAMPER |
| | RESISTANT NEC 406.11 |
| | |
| | 6) ALL 15 AND 20 AMP BRANCH CIRCUITS SUPPLYING OUTLETS |
| | INSTALLED IN THE DWELLING UNIT SHALL BE PROTECTED BY A |
| | LISTED ARC-FAULT CIRCUIT INTERRUPTER. NEC 210.12 |
| | |
| | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| | 561-805-6717 OR [email protected] |
| | |