| | PROJECT: NICHOLAS KASSALTY RESIDENCE |
| | PERMIT#: 15030075 |
| | CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC |
| | ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| | ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| | 2ND ELECTRICAL PLAN REVIEW |
| | ACTION: DENIED |
| | |
| | 1) RECESSED LUMINAIRES INSTALLED IN THE BUILDING |
| | THERMAL ENVELOPE SHALL BE SEALED TO LIMIT AIR LEAKAGE |
| | BETWEEN CONDITIONED AND UNCONDITIONED SPACES. FBC-E |
| | 502.3.8. |
| | |
| | 2) THE ELECTRICAL PANEL AND GROUNDING ELECTRODE SYSTEM |
| | APEAR CONFUSING. REVISE THE RISER DIAGRAM TO INDICATE |
| | COMPLIANCE WITH THE NEC 250.50 THE GROUNDING ELECTRODE |
| | IS INDICATED AS BEING INSTALLED AFTER THE 1ST MEANS OF |
| | DISCONNECT. THE GROUNDING ELECTRODE SYSTEM SHALL BE |
| | INSTALLED AS CLOSE AS PRCTICABLE TO THE SERVICE |
| | ENTRANCE. |
| | |
| | 3) INDICATE ALL REQUIRED SMOKE DETECTORS. WHEN |
| | ALTERATIONS, REPAIRS, OR ADDITIONS REQUIRING A PERMIT |
| | OCCUR, OR WHEN ONE OR MORE SLEEPING ROOMS ARE ADDED OR |
| | CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL DWELLING |
| | UNIT SHALL BE EQUIPPED WITH SMOKE ALARMS LOCATED AS |
| | REQUIRED FOR NEW DWELLINGS. FBC-RESIDENTIAL 314 AND |
| | 315. |
| | |
| | 4) SEPARATE PERMIT APPLICATIONS ACCOMPANIED BY |
| | MANUFACTURERS EQUIPMENT SUBMITTALS, AND SHOP DRAWINGS |
| | ARE REQUIRED FOR LIGHTNING PROTECTION SYSTEM. |
| | |
| | IN ADDITION TO THE LIGHTNING PROTECTION SYSTEM, ANY |
| | OTHER SYSTEMS PROPSED SUCH AS GENERATORS. ACCESS |
| | CONTROL, SECURITY, CCTV, AUDIO/VIDEO, NETWORK, DATA, OR |
| | COMMUNICATION SYSTEMS ALL REQUIRE SEPARATE PERMIT |
| | APPLICATIONS ACCOMPANIED BY MANUFACTURERS EQUIPMENT |
| | SUBMITTALS, AND SHOP DRAWINGS. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. SEE LINK: |
| | HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ |
| | 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| | |
| | ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED |
| | PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE |
| | PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE |
| | REVIEW. |
| | |
| | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |