2015-06-23 17:28:54RESIDENTIAL (R3) ALTERATION/ADDITION SECOND BUILDING
 REVIEW COMMENTS.
 CODE: 2010 FBC.
  
 1- ENERGY CALCULATIONS SUBMITTED:
 A) CONDITIONED FLOOR AREA IS INCORRECT.. ENERGY
 CALCULATIONS ARE FOR THE FIRST FLOOR ALTERATION. AREA
 SHOWN IS NOT INCLUDING THE NEW ENCLOSED DINING ROOM.
 REVISE AS REQUIRED. SEC. 103.2.1.1.2 OF 2010 FBC-ENERGY
 CONSERVATION.
  
 B) RAISED FLOOR AREA IS INCORRECT. COORDINATE WITH ITEM
 1A ABOVE. SEC. 103.2.1.1.2 OF 2010 FBC-ENERGY
 CONSERVATION.
  
 C) OWNER/AGENT TO SIGN AND DATE BOTTOM OF FORM. (PERMIT
 CAN NOT BE ISSUED WITHOUT THIS CODE COMPLIANCE
 CERTIFICATION. SEE SEC. 103.2.3.2 OF 2010 FBC-ENERGY
 CONSERVATION).
  
 D) ROOF INFORMATION ON PAGE 2 OF 5 IS INCORRECT. THIS A
 FLAT ROOF. IT'S NOT A METAL ROOF. THE METAL ROOF IS ON
 THE MANSARDS ONLY AND IS NOT PART OF THE BUILDING
 THERMAL ENVELOPE. REVISE AS REQUIRED. SEC. 103.2.1.1.2
 OF 2010 FBC-ENERGY CONSERVATION
  
 E) COMPLETE THE CHECKLIST ON PAGE 5 OF 5. SEC. 103.2.2
 OF 2010 FBC-ENERGY CONSERVATION
  
 IMPORTANT: LABEL FOR WINDOWS AND DOORS U-FACTOR AND
 SHGC FACTOR WILL BE REQUIRED AT TIME OF INSPECTION WHEN
 THE ENERGY CALCULATIONS ARE NOT USING THE DEFAULT
 FACTOR. SEC. 303.1.3 OF 2010 FBC-ENERGY CONSERVATION
  
 2- PLANS TO SPECIFY WALL, CEILING AND CRAWL SPACE
 INSULATION. COORDINATE WITH INFORMATION ON ENERGY
 CALCULATIONS. SEC. 103.2.2 OF 2010 FBC-ENERGY
 CONSERVATION. (REPEAT COMMENT. IT'S NOT THE
 CONTRACTOR'S RESPONSIBILITY. IT'S PART OF THE
 CONSTRUCTION DOCUMENTS. )
  
 3- NEED CARBON MONOXIDE ALARMS INSTALLED WITHIN 10 FEET
 OF EACH ROOM USED FOR SLEEPING AS REQUIRED BY SEC. R315
 OF 2010 FBC-RESIDENTIAL. (REPEAT COMMENT. IT DOESN'T
 HAVE TO BE WORK TO BE DONE IN THE BEDROOMS. THE
 HABITABLE AREA OF THE FIRST FLOOR WAS INCREASED).
  
 4- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 DCA RULE 9N-3 FOR:
 A) HURRICANE SHUTTERS AND PROVIDE COMPLETE INSTALLATION
 SCHEDULE. NOA 11-1013.12 SUBMITTED FOR SINGLE HUNG
 WINDOWS WITHOUT IMPACT GLASS. NEW WINDOWS REQUIRE
 IMPACT PROTECTION. SEC R301.2.1.2 OF 2010
 FBC-RESIDENTIAL. (REPEAT COMMENT. NOT ADDRESSED).
  
 B) SINGLE CABANA DOOR (MODEL CD290). PROVIDE COMPLETE
 APPROVED PRODUCT APPROVAL. INFORMATION SUBMITTED IS NOT
 AN APPROVED PRODUCT APPROVAL. PROVIDE THE MIAMI-DADE
 NOA NUMBER OR FLORIDA PRODUCT APPROVAL NUMBER. IF THERE
 IS NONE, THEN MANUFACTURER MAY APPLY FOR LOCAL PRODUCT
 APPROVAL. CONTACT ME (JULIO GOMEZ) FOR MORE INFORMATION
 REGARDING LOCAL PRODUCT APPROVAL PROCESS. (REPEAT
 COMMENT. NOT ADDRESSED).
  
 5- DESIGNER OF RECORD TO APPROVE ABOVE PRODUCT
 APPROVALS AS REQUIRED BY SEC. 107.3.4.1 CITY
 AMENDMENTS.
  
 ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 ****PLEASE REPLACE AND REMOVE ANY REVISED DRAWING.
 SUBMIT OLD COPY FOR REFERENCE.
  