Plan Review Notes
Plan Review Notes For Permit 15030075
Permit Number 15030075
Review Stop E
Sequence Number 1
Notes
Date Text
2015-04-11 14:17:274/11/2015
 PROJECT: NICHOLAS KASSALTY RESIDENCE
 PERMIT#: 15030075
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 1ST ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 1) RECESSED LUMINAIRES INSTALLED IN THE BUILDING
 THERMAL ENVELOPE SHALL BE SEALED TO LIMIT AIR LEAKAGE
 BETWEEN CONDITIONED AND UNCONDITIONED SPACES. FBC-E
 502.3.8.
  
 2) INDICATE POWER OUTLET AND CIRCUIT DESIGNATION FOR
 IGNIGHTER FOR GAS RANGE.
  
 3) RECEPTACLES THROUGHOUT THE HOUSE SHALL BE INSTALLED
 SUCH THAT NO POINT MEASURED HORIZONTALLY ALONG THE
 FLOOR LINE IN ANY WALL SPACE IS MORE THAN 1.8 M (6 FT)
 FROM A RECEPTACLE OUTLET. NEC 210.52
  
 4) RECEPTACLE OUTLETS IN THE KITCHEN SHALL BE INSTALLED
 SO THAT NO POINT ALONG THE WALL LINE IS MORE THAN 600
 MM (24 IN.) MEASURED HORIZONTALLY FROM A RECEPTACLE
 OUTLET IN THAT SPACE. NEC 210.52
  
 6) EVERY CIRCUIT AND CIRCUIT MODIFICATION SHALL BE
 LEGIBLY IDENTIFIED AS TO ITS CLEAR, EVIDENT, AND
 SPECIFIC PURPOSE OR USE. NEC 408.4
  
 7) INDICATE THE LOCATION OF THE ELECTRICAL PANEL ON THE
 FLOOR PLAN.
  
 8) THE ELECTROICAL PANEL AND GROUNDING ELECTRODE SYSTEM
 APEAR CONFUSING. REVISE THE RISER DIAGRAM TO INDICATE
 COMPLIANCE WITH THE NEC 250.50
  
 9) WHEN ALTERATIONS, REPAIRS, OR ADDITIONS REQUIRING A
 PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING ROOMS ARE
 ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL
 DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE ALARMS
 LOCATED AS REQUIRED FOR NEW DWELLINGS. FBC-RESIDENTIAL
 314 AND 315.
  
 10) SEPARATE PERMIT APPLICATIONS ACCOMPANIED BY
 MANUFACTURERS EQUIPMENT SUBMITTALS, AND SHOP DRAWINGS
 ARE REQUIRED FOR LIGHTNING PROTECTION SYSTEM.
  
 IN ADDITION TO THE LIGHTNING PROTECTION SYSTEM, ANY
 OTHER SYSTEMS PROPSED SUCH AS GENERATORS. ACCESS
 CONTROL, SECURITY, CCTV, AUDIO/VIDEO, NETWORK, DATA, OR
 COMMUNICATION SYSTEMS ALL REQUIRE SEPARATE PERMIT
 APPLICATIONS ACCOMPANIED BY MANUFACTURERS EQUIPMENT
 SUBMITTALS, AND SHOP DRAWINGS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED
 PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE
 PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE
 REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  