| 2015-04-11 14:17:27 | 4/11/2015 |
| | PROJECT: NICHOLAS KASSALTY RESIDENCE |
| | PERMIT#: 15030075 |
| | CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC |
| | ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| | ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| | 1ST ELECTRICAL PLAN REVIEW |
| | ACTION: DENIED |
| | |
| | 1) RECESSED LUMINAIRES INSTALLED IN THE BUILDING |
| | THERMAL ENVELOPE SHALL BE SEALED TO LIMIT AIR LEAKAGE |
| | BETWEEN CONDITIONED AND UNCONDITIONED SPACES. FBC-E |
| | 502.3.8. |
| | |
| | 2) INDICATE POWER OUTLET AND CIRCUIT DESIGNATION FOR |
| | IGNIGHTER FOR GAS RANGE. |
| | |
| | 3) RECEPTACLES THROUGHOUT THE HOUSE SHALL BE INSTALLED |
| | SUCH THAT NO POINT MEASURED HORIZONTALLY ALONG THE |
| | FLOOR LINE IN ANY WALL SPACE IS MORE THAN 1.8 M (6 FT) |
| | FROM A RECEPTACLE OUTLET. NEC 210.52 |
| | |
| | 4) RECEPTACLE OUTLETS IN THE KITCHEN SHALL BE INSTALLED |
| | SO THAT NO POINT ALONG THE WALL LINE IS MORE THAN 600 |
| | MM (24 IN.) MEASURED HORIZONTALLY FROM A RECEPTACLE |
| | OUTLET IN THAT SPACE. NEC 210.52 |
| | |
| | 6) EVERY CIRCUIT AND CIRCUIT MODIFICATION SHALL BE |
| | LEGIBLY IDENTIFIED AS TO ITS CLEAR, EVIDENT, AND |
| | SPECIFIC PURPOSE OR USE. NEC 408.4 |
| | |
| | 7) INDICATE THE LOCATION OF THE ELECTRICAL PANEL ON THE |
| | FLOOR PLAN. |
| | |
| | 8) THE ELECTROICAL PANEL AND GROUNDING ELECTRODE SYSTEM |
| | APEAR CONFUSING. REVISE THE RISER DIAGRAM TO INDICATE |
| | COMPLIANCE WITH THE NEC 250.50 |
| | |
| | 9) WHEN ALTERATIONS, REPAIRS, OR ADDITIONS REQUIRING A |
| | PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING ROOMS ARE |
| | ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL |
| | DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE ALARMS |
| | LOCATED AS REQUIRED FOR NEW DWELLINGS. FBC-RESIDENTIAL |
| | 314 AND 315. |
| | |
| | 10) SEPARATE PERMIT APPLICATIONS ACCOMPANIED BY |
| | MANUFACTURERS EQUIPMENT SUBMITTALS, AND SHOP DRAWINGS |
| | ARE REQUIRED FOR LIGHTNING PROTECTION SYSTEM. |
| | |
| | IN ADDITION TO THE LIGHTNING PROTECTION SYSTEM, ANY |
| | OTHER SYSTEMS PROPSED SUCH AS GENERATORS. ACCESS |
| | CONTROL, SECURITY, CCTV, AUDIO/VIDEO, NETWORK, DATA, OR |
| | COMMUNICATION SYSTEMS ALL REQUIRE SEPARATE PERMIT |
| | APPLICATIONS ACCOMPANIED BY MANUFACTURERS EQUIPMENT |
| | SUBMITTALS, AND SHOP DRAWINGS. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. SEE LINK: |
| | HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ |
| | 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| | |
| | ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED |
| | PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE |
| | PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE |
| | REVIEW. |
| | |
| | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| | 561-805-6717 OR [email protected] |
| | |