| 2015-03-31 12:41:35 | RESIDENTIAL (R3) ADDITION/ALTERATION BUILDING REVIEW |
| | COMMENTS. |
| | CODE: 2010 FBC. |
| | |
| | 1- BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG RD.) |
| | FOR IMPACT FEES ASSESSMENT. BRING BACK COUNTY STAMPED |
| | PLANS AND COPY OF PAID RECEIPT IF FEES ARE DUE. COUNTY |
| | IMPACT FEE ORDINANCE OF THE UNIFIED LAND DEVELOPMENT |
| | CODE. |
| | |
| | 2- DESIGNER OF RECORD TO ELECT ALTERATION LEVEL AS |
| | REQUIRED BY SEC. 401.4 OF 2010 FBC-EXISTING BUILDING. |
| | |
| | 3- PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC. |
| | 101.4.3 OF 2010 FBC-ENERGY CONSERVATION. |
| | |
| | 4- PLANS TO SPECIFY WALL, CEILING AND CRAWL SPACE |
| | INSULATION. COORDINATE WITH INFORMATION ON ENERGY |
| | CALCULATIONS. SEC. 103.2.2 OF 2010 FBC-ENERGY |
| | CONSERVATION. |
| | |
| | 5- CLARIFY ENERGY NOTE UNDER PROJECT DATA ON SHEET T1. |
| | THERE ARE NOT PERMITS ISSUED FOR NEW WINDOWS AND DOORS. |
| | SEC. 107.2.1 CITY AMENDMENTS TO FBC. IF THEY WERE |
| | REPLACED, THEN IT WAS DONE WITHOUT PERMITS. PROPER |
| | PERMITS WILL BE REQUIRED. |
| | |
| | 6- CLARIFY IF SCOPE OF WORK INCLUDES EXISTING WINDOWS |
| | AND DOORS REPLACEMENT. COORDINATE WITH ITEM #5 ABOVE. |
| | IF WINDOW AND DOOR REPLACEMENT IS ADDED, THEN REVISE |
| | VALUATION AS REQUIRED BY SEC. 109.3 CITY AMENDMENTS. |
| | AND, CLEARLY SPECIFY TYPE AND SIZE OF EXISTING WINDOWS |
| | AND TYPE AND SIZE OF PROPOSED WINDOWS TO VERIFY |
| | COMPLIANCE WITH EGRESS REQUIREMENTS OF SEC. 604.1 OF |
| | 2010 FBC-EXISTING BUILDING. |
| | |
| | 7- WIND DESIGN INFORMATION ON SHEET A4: |
| | A) REVISE THE WIND EXPOSURE AND DESIGN PRESSURES. THIS |
| | BUILDING IS LOCATED IN EXPOSURE "C" NOT "B". SEC. |
| | R301.2.1.4 OF 2010 FBC- RESIDENTIAL. |
| | |
| | B) PROVIDE CORRECT MEAN ROOF HEIGHT. THIS IS A 2 STORY |
| | HOUSE. 0'-15' MEAN ROOF HEIGHT IS INCORRECT. |
| | |
| | C) UPDATE INFORMATION ON NOTES #2, #4 AND #5. THERE IS |
| | NOT SBBCCI. SIMPSON CONNECTORS ARE NOT MANUFACTURED BY |
| | HUGHES. ROOF SHEATHING REQUIRES 8D RING SHANK NAILS. |
| | SEC. R803.2.3.1 OF 2010 FBC-RESIDENTIAL. |
| | |
| | 8- NEED CARBON MONOXIDE ALARMS INSTALLED WITHIN 10 FEET |
| | OF EACH ROOM USED FOR SLEEPING AS REQUIRED BY SEC. R315 |
| | OF 2010 FBC-RESIDENTIAL. |
| | |
| | 9- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| | DCA RULE 9N-3 FOR: |
| | A) SINGLE HUNG WINDOWS. PROVIDE LEGIBLE DRAWINGS. |
| | DRAWINGS SUBMITTED WITH NOA 11-1013.12 ARE TOO SMALL |
| | AND ARE NOT LEGIBLE. NEED LARGER DRAWINGS FOR PROPER |
| | RECORDS RETENTION. SEC. 107.2.1.4 CITY AMENDMENTS. |
| | PLEASE PRINT DRAWINGS IN LANDSCAPE FORMAT. DRAWINGS |
| | WILL BE MORE LEGIBLE. |
| | |
| | B) HURRICANE SHUTTERS AND PROVIDE COMPLETE INSTALLATION |
| | SCHEDULE. NOA 11-1013.12 SUBMITTED FOR SINGLE HUNG |
| | WINDOWS WITHOUT IMPACT GLASS. NEW WINDOWS REQUIRE |
| | IMPACT PROTECTION. SEC R301.2.1.2 OF 2010 |
| | FBC-RESIDENTIAL. |
| | |
| | C) SINGLE CABANA DOOR (MODEL CD290). PROVIDE COMPLETE |
| | APPROVED PRODUCT APPROVAL. INFORMATION SUBMITTED IS NOT |
| | AN APPROVED PRODUCT APPROVAL. PROVIDE THE MIAMI-DADE |
| | NOA NUMBER OR FLORIDA PRODUCT APPROVAL NUMBER. IF THERE |
| | IS NONE, THEN MANUFACTURER MAY APPLY FOR LOCAL PRODUCT |
| | APPROVAL. CONTACT ME (JULIO GOMEZ) FOR MORE INFORMATION |
| | REGARDING LOCAL PRODUCT APPROVAL PROCESS. |
| | |
| | D) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON ALL |
| | FRAMING PLANS AND DETAILS.. PROVIDE ONLY THE FLORIDA |
| | PRODUCT APPROVAL COVER PAGE AND PAGE SHOWING THE |
| | SPECIFIED CONNECTOR OR DESIGNER OF RECORD MAY LIST THE |
| | FLORIDA PRODUCT APPROVAL NEXT TO THE SPECIFIED |
| | CONNECTOR. |
| | |
| | 10- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS |
| | REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS. |
| | |
| | ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH |
| | COMMENT TO EXPEDITE THE REVIEW PROCESS. |
| | ****PLEASE REPLACE AND REMOVE ANY REVISED DRAWING. |
| | SUBMIT OLD COPY FOR REFERENCE. |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | (561)805-6712 |
| | [email protected] |