| 2015-03-30 10:28:15 | ****PROVISO**** |
| | ****ISSUED AT CONTRACTOR'S RISK**** |
| | ****REVISION REQUIRED PRIOR FINAL INSPECTION**** |
| | ****ITEM #8 REQUIRED PRIOR TO FIRST INSPECTION**** |
| | |
| | SAMANTHA HILL |
| | BUILDING PLANS EXAMINER |
| | [email protected] |
| | 561-805-6724 |
| | |
| | PLANS WERE NOT REVISED - SAME PLANS SUBMITTED |
| | COMMENTS FROM PREVIOUS LIST: |
| | |
| | 1. OK |
| | |
| | 2. FOOTINGS TO BE 12" BELOW UNDISTURBED GRADE, FBC |
| | 1809.4. |
| | |
| | 3. OK |
| | |
| | 4. FBC 3105.1.1.1, SHOW DISTANCE TO THE BOTTOM OF THE |
| | AWNING STRUCTURE. |
| | |
| | 2ND REVIEW - THIS WAS WRITTEN ONTO THE PLAN AS 7'8", |
| | AND ONLY ONE HAND REVISED SET WAS PROVIDED. ENGINEER IS |
| | TO INCORPORATE THIS CHANGE INTO HIS DRAWING. |
| | INDIVIDUALS OTHER THAN THE ENGINEER CANNOT REVISE THE |
| | ENGINEER'S PLAN; ENGINEER'S PLAN IS TO PROVIDE ENOUGH |
| | INFORMATION TO DEMONSTRATE CODE COMPLIANCE. |
| | |
| | 5. GAZEBO FOUNDATION, PROVIDE A STRUCTURAL DETAIL FBC |
| | 107. THE PLAN INDICATES THAT THIS IS "BY OTHERS." |
| | |
| | 2ND REVIEW, FOUNDATION PLAN FOR THE GAZEBO WAS NOT |
| | SUBMITTED, SO THERE IS NOTHING FOR EITHER REVIEW OR |
| | INSPECTION. THIS PORTION IS EXCLUDED FROM THIS PERMIT |
| | UNTIL A PLAN IS MADE AVAILABLE. |
| | |
| | 6. FBC 2010 ACCESSIBILITY FAIR HOUSING SECTION 3, ITEM |
| | C(1) REQUIRES THAT "THE PUBLIC AND COMMON USE AREAS ARE |
| | READILY ACCESSIBLE AND USABLE BY THE HANDICAPPED |
| | PERSONS". THE GAZEBO IS GRAPHICALLY SHOWN 6" ABOVE |
| | GRADE. PROVIDE A DETAIL FOR ACCESSIBLE ENTRY. |
| | |
| | 2ND REVIEW, NOT ADDRESSED. CONTRACTOR STATED THAT A |
| | RAMP WILL BE BUILT, AND AN EMAIL BETWEEN TWO |
| | INDIVIDUALS MAKING REFERENCE TO A RAMP WAS PROVIDED |
| | (RELATIONSHIP TO JOB UNCLEAR; NEITHER WAS THE |
| | CONTRACTOR OR THE ENGINEER). REVISION IS TO INCLUDE |
| | ACCESSIBLE ROUTE TO THE GAZEBO AS WELL AS GAZEBO |
| | FOUNDATION. |
| | |
| | 7. FLORIDA STATE OR LOCAL PRODUCT APPROVAL REQUIRED FOR |
| | THE GAZEBO SHINGLES, FAC9N-3. |
| | |
| | 2ND REVIEW, A FLORIDA STATE PRODUCT APPROVAL COVER |
| | SHEET WAS PROVIDED. THIS APPROVAL INCLUDES NINE |
| | DIFFERENT PRODUCTS; SPECIFIC PRODUCT PROPOSED NOT |
| | INDICATED AND THE EVALUATION REPORT/INSTALLATION |
| | INSTRUCTIONS WERE NOT PROVIDED. WITH EITHER THE |
| | REVISION OR THE ROOF PERMIT, PROVIDE A COMPLETE PRODUCT |
| | APPROVAL. THIS SHOULD BE REVIEWED BY EOR PRIOR TO |
| | SUBMITTAL, FBC 107.3.4. |
| | |
| | 8. ADJUST VALUE TO INCLUDE ALL PROPOSED IMPROVEMENTS. |
| | PROVIDE A COPY OF THE CONTRACT(S), FBC 109. |
| | |
| | 2ND REVIEW, NOT ADDRESSED. VALUE IS TO INCLUDE THE |
| | VALUE OF LABOR, MATERIALS, OVERHEAD, PROFIT, |
| | ENGINEERING - EVERYTHING EXCEPT FOR THE VALUE OF LAND. |
| | PROVIDE A COPY OF THE CONTRACT(S) FOR THIS JOB. |
| | |
| | 9. PROVIDE SLOPE AND CROSS SLOPE FOR SIDEWALKS, FBC |
| | 2010 ACCESSIBILITY FAIR HOUSING SECTION 3 (ACCESSIBLE |
| | ROUTE). |
| | |
| | 2ND REVIEW, NOT ADDRESSED. THIS PERMIT IS ISSUED AT |
| | CONTRACTOR'S RISK. |
| | |
| | NEW COMMENTS: |
| | |
| | A. PROVIDE AWNING FABRIC REMOVAL INSTRUCTIONS TO SHOW |
| | COMPLIANCE WITH FBC3105.4.2.1, QUICK RELEASE. THE |
| | INSTRUCTIONS SHOULD CONSIST OF A SERIES OF PHOTOGRAPHS. |
| | THIS IS TO BE APPROVED BY THE BUILDING OFFICIAL. |
| | |
| | B. PER BUILDING OFFICIAL, WE ARE TO PUT ON THE PERMIT |
| | FILE A LETTER, OR CONTRACTORS FORM, SIGNED BY THE OWNER |
| | (NOT THE TENANT) TO ACKNOWLEDGE THEIR RESPONSIBILITY TO |
| | HAVE THE AWNING COVER REMOVED PRIOR TO ANY WIND EVENT |
| | WITH PROJECTED WIND SPEEDS OF 75 MPH OR GREATER. THE |
| | LETTER/FORM MUST BE SIGNED BY THE OWNER BUT IT NEED NOT |
| | BE NOTARIZED. |
| | |
| | C. THE PLANS FOR THE GAZEBO AND PERGOLA ARE |
| | PHOTOCOPIES. DOCUMENTS PREPARED BY AN ENGINEER AND |
| | SUBMITTED FOR PUBLIC RECORD ARE TO BE SIGNED, SEALED, |
| | DATED ORIGINALS FS471. SUBMIT ORIGINALS WITH THE |
| | REVISION. |
| | |