Plan Review Notes
Plan Review Notes For Permit 15030034
Permit Number 15030034
Review Stop B
Sequence Number 2
Notes
Date Text
2015-04-01 07:17:06****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FROM PREVIOUS LIST:
  
 1. PLANS TO BE ARCHITECTURAL QUALITY TO SCALE. ONE
 APPLICATION (15030034) IS FOR "MINOR DRYWALL REPAIR"
 BUT NOTHING ON PLAN SHOWING SCOPE / LOCATION. THERE
 SHOULD BE AN EXISTING AND PROPOSED PLAN. APPLICATION TO
 INCLUDE ALL WORK INCLUDED IN THE VIOLATION ISSUED. FBC
 107
  
 2ND REVIEW, NOTE STATES "MINOR DRYWALL REPAIRS (HOLES)"
 - DOES NOT SHOW LOCATIONS. IF A PART OF A FIRE RATED
 TENANT SEPARATION WALL, A DETAIL WILL BE REQUIRED. PER
 INSPECTOR AND PHOTOGRAPHS OF THE JOB, DRYWALL REPAIR
 WAS MORE EXTENSIVE THAN INDICATED ON THE PLANS. SCOPE
 ALSO INCLUDED WALL FRAMING. SEE FIRST LIST; PROVIDE AN
 ARCHITECTURAL PLAN WHICH SHOWS WORK STARTED WITHOUT
 PERMIT.
  
 2. OK
  
 NEW COMMENT:
  
 3. VALUE TOO LOW. PROVIDE A REASONABLE VALUE OR A
 VALUATION WILL BE DETERMINED FOR YOU, FBC 109.
  
 4. THE RESUBMITTAL SHEET STATES THAT ASPHALT WILL BE
 REPLACED WITH GRASS AND PAVERS. A FENCE SKETCH WAS
 PROVIDED. BOTH REQUIRE SEPARATE PERMITS.
  
 5. THE NEW PLAN SHOWS TILE FLOORS. IS THIS EXISTING OR
 PROPOSED? IF PROPOSED, TEST REPORTS REQUIRED FOR 2ND
 FLOOR UNITS:
  
 A. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR
 BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90.
 IF A SUSPENDED CEILING WAS USED AS A PART OF THE TEST,
 PROVIDE INFORMATION AS TO HOW IT HAS BEEN DETERMINED
 THAT THIS CONDITION CURRENTLY EXISTS AND HOW IT CAN BE
 GUARANTEED THAT THE CONDITIONS IN THE UNIT BELOW WILL
 NOT BE ALTERED.
  
 PLEASE PROVIDE A COPY OF THE TEST REPORT.
  
 B. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN
 DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC
 OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN
 IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN
 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH
 ASTM E 492. IF A SUSPENDED CEILING WAS USED AS A PART
 OF THE TEST, PROVIDE INFORMATION AS TO HOW IT HAS BEEN
 DETERMINED THAT THIS CONDITION CURRENTLY EXISTS AND HOW
 IT CAN BE GUARANTEED THAT THE CONDITIONS IN THE UNIT
 BELOW WILL NOT BE ALTERED.
  
 PLEASE PROVIDE A COPY OF THE TEST REPORT.
  
 IF TILE EXISTING, REVISE PLAN TO INCLUDE THAT
 INFORMATION. SCOPE WILL BE CONFIRMED WITH THE INSPECTOR
 / PHOTOGRAPHS.
  
  
  