| 2015-03-05 10:50:41 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | SHEET A-1, THERE IS INCORRECT REFERENCE TO FIRE CODES - |
| | THE PROPOSED PROJECT SHALL MEET THE REQUIREMENTS OF THE |
| | 5TH EDITION OF FLORIDA FIRE PREVENTION CODE INCLUDING |
| | THE 2012 EDITION OF NFPA 1 AND NFPA 101 AND ALL OTHER |
| | APPLICABLE CODES OR STANDARDS. |
| | |
| | FIRE SPRINKLER WORK SHALL COMPLY WITH THE REQUIREMENTS |
| | OF NFPA 13, 2010 EDITION. |
| | |
| | FIRE ALARM WORK SHALL COMPLY WITH THE REQUIREMENTS OF |
| | NFPA 72, 2010 EDITION. |
| | |
| | CONSTRUCTION WORK SHALL COMPLY WITH THE REQUIREMENTS OF |
| | NFPA 241, 2009 EDITION. |
| | |
| | FIRE EXTINGUISHERS SHALL COMPLY WITH THE REQUIREMENTS |
| | OF NFPA 10, 2010 EDITION. |
| | |
| | ELECTRIC WORK SHALL COMPLY WITH NFPA 70, 2011 EDITION. |
| | |
| | SHEET A-1 REFERNECES THAT THE BUILDING IS SPRINKLERS - |
| | THE NATURE OF THE REMODEL REQUIRES AN EVALUATION OF THE |
| | FIRE ALARM AND SPRINKLER SYSTEM FOR CODE COVERAGE AND |
| | COMPLIANCE. |
| | |
| | PLEASE INDICATE ON THE PLANS THAT THE LIFE SAFETY |
| | SYSTEMS, FIRE ALARM AND/OR FIRE SPRINKLER SHALL REMAIN |
| | ACTIVE THROUGHOUT THE CONSTRUCTION PERIOD. |
| | |
| | ANY AND ALL WORK ON THE FIRE ALARM AND FIRE SPRINKLER |
| | SYSTEMS SHALL BE DONE UNDER SEPARATE SHOP DRAWINGS AND |
| | BY CERTIFIED LIFE SAFETY CONTRACTORS. |
| | |
| | ANY TIME THAT WORK ON THE LIFE SAFETY SYSTEMS, |
| | SPRINKLER AND/OR FIRE ALARM, EXCEEDS 4 HOURS, A FIRE |
| | WATCH SHALL BE IMPLEMENTED AND MAINTAINED UNTIL FULL |
| | AND COMPLETE PROTECTION IS RETURNED. |
| | |
| | SHEET E-1, P-1 INDICATES A PIECE OF EQUIPMENT IN THE |
| | KITCHEN AREA MARK WITH A RED LETTER "F". WHAT IS THIS |
| | PIECE OF EQUIRPMENT? WHAT ADDITONAL PIECES OF EQUIPMENT |
| | PROPOSED FOR THE KITCHEN? WHAT IS THE PROPOSED COOKING |
| | IN THIS KITCHEN? COOKING MEETING THE PROTECTION |
| | REQUIREMENTS CONTAINED WITHIN NFPA 96 SHALL COMPLY WITH |
| | THAT CODE.. |
| | |
| | SHEET A-2 DOES NOT INDICATE ANY EXIT SIGNS WITHIN THE |
| | KITCHEN AREA. THIS AREA HAS ACCESS TO 2 EXITS. ONE |
| | ADDITIONAL EXIT SIGN SHALL BE ADDED TO THE KITCHEN AREA |
| | AT THE AREA OF THE CORRIDOR. |
| | |
| | SHEET A-2 INDICATES THE ADDITION OF A NEW WALL |
| | SEPARATING THE KITCHEN AND THE WAREHOUSE. PLEASE |
| | PROVIDE THE REQUIRED FIRE RATING OF THIS WALL AND THE |
| | DOOR. |
| | |