| Plan Review Notes For Permit 15030025 |
| Permit Number |
15030025 |
|
| Review Stop |
P |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2015-04-21 04:45:29 | 1) THE HAND SINK SHALL BE ADDED ONTO THE PERMIT | | | APPLICATION UNDER "DESCRIPTION OF WORK" SECTION. THE | | | VALUE OF THE JOB WAS ADJUSTED BUT THE SINK HAS NOT BEEN | | | ADDED TO THE DESCRIPTION. WPB AMEND. TO 2010 FBC SEC. | | | 107.2.1.2ND REQUEST. | | | 2) SUBMIT SIZING CALCULATIONS FOR THE GREASE | | | INTERCEPTOR IN ACCORDANCE WITH THE 2010 FL. PLUMBING | | | CODE SEC. 1003.3.4 AND SEC.1003.3.4.1. 3RD REQUEST. YOU | | | HAVE PROVIDED A MODEL NUMBER OF A UNIT THAT WILL BE | | | USED BUT HOW DID YOU DETERMINE THAT THE UNIT YOU ARE | | | SPECIFYING IS OF ADEQUATE CAPACITY? | | | 3) SUBMIT A FLOOR PLAN AND WATER AND SANITARY RISER FOR | | | THE INSTALLATION OF ALL APPLIANCES & EQUIPMENT.THESE | | | FIXTURES APPEAR TO BE NEW AND NOT REPLACEMENTS. SHOW | | | THE PIPE SIZES, LOCATION AND TERMINATION OF ALL VENTS, | | | AND THE CONNECTION POINT OF THE NEW PIPING TO THE | | | EXISTING SYSTEM. 3RD REQUEST.WPB AMEND. TO 2010 FBC | | | SEC. 107.2.1. | | | | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] | | | |
|