| 2015-04-08 09:57:24 | REPEAT OF ORIGINAL COMMENTS. SIZING/DESIGN FOR THIS | | | TYPE OF SEPARATOR MUST BE BASED ON ANTICIPATED | | | OIL/GREASE LOADING FROM RESTAURANT. LOADING IS USUALLY | | | DETERMINED FROM NUMBER AND TYPE OF MEALS SERVED. |
|