2015-03-04 06:06:141) SUBMIT A FLOOR PLAN DRAWING SHOWING THE LOCATION OF
 THE 3 COMPARTMENT SINK. WPB AMEND. TO 2010 FBC
 SEC.107.2.1.
 2) SUBMIT A PLUMBING RISER DIAGRAM FOR THE
 INSTALLATION. SHOW THE PIPE SIZES, LOCATION &
 TERMINATION POINTS OF THE VENT, AND THE CONNECTION TO
 THE PLUMBING SYSTEM. WPB AMEND. TO 2010 FBC SEC.
 107.3.5.1.3.
 3) INDICATE ON THE PLAN IF THE 3 COMPARTMENT SINK IS
 NEW OR EXISTING. WPB AMEND. TO 201 FBC SEC. 107.2.1.
 4) SUBMIT 2 COPIES OF THE INSTALLATION INSTRUCTIONS FOR
 THE TANKLESS WATER HEATER PER WPB AMEND. TO 201 FBC
 SEC. 107.2.1, FPC SEC.502.1.
 5) INDICATE ON THE PLANS IF THE 3 COMPARTMENT SINK IS
 NEW OR EXISTING. IF NEW, SUBMIT A WATER PIPING
 RISER.WPB AMEND. TO 2010 FBC SEC.107.5.1.3.
 6) A SEPARATE ELECTRIC PERMIT WILL BE REQUIRED FOR THE
 GREASE INTERCEPTOR.
 7) SUBMIT SIZING CALCULATIONS FOR THE GREASE
 INTERCEPTOR PER THE 2010 FPC SEC. 1003.3.4., 103.3.4.1.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  
  