Plan Review Notes
Plan Review Notes For Permit 15030010
Permit Number 15030010
Review Stop B
Sequence Number 1
Notes
Date Text
2015-03-12 10:53:33BUILDING PLAN REVIEW
 W. P. B. REVISION: 15030010
 W. P. B. PERMIT: 14110440
 ADD: 4115 GEORGIA AVE.
 CONT: T D GONE BUILDING
 TEL: (561)436-4047
 E-MAIL: [email protected]
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE:
 ACTION: DENIED
  
 IMPORTANT NOTICE: EFFECTIVE MARCH 30, 2015
 ALL PERMIT APPLICATION PLAN REVIEWS WILL BE PERFORMED
 ELECTRONICALLY
 UPON APPLICATION AND FEE PAYMENT DESIGN DOCUMENTS
 SUBMISSION OPTIONS ARE AS FOLLOWS:
 1 UPLOAD VIA THE PROJECT DOX PORTAL WITH DIGITAL
 SIGNATURES OF DESIGN PROFESSIONALS AS APPLICABLE; USE
 THE REQUIRED NAMING CONVENTION FOR EACH DOCUMENT
 2 INCLUDE ON A CD IF DESIGN PROFESSIONAL DIGITAL
 SIGNATURES ARE PROVIDED AS REQUIRED; USE THE REQUIRED
 NAMING CONVENTION FOR EACH DOCUMENT
 3 INCLUDE ON A CD WITH ONE SET OF TRADITIONAL PAPER
 DESIGN DOCUMENTS SIGNED AND SEALED AS REQUIRED; USE THE
 REQUIRED NAMING CONVENTION FOR EACH DOCUMENT
 4 ONE SET OF TRADITIONAL PAPER DESIGN DOCUMENTS SUBJECT
 TO ADMINISTRATIVE FEES TO DIGITIZE THE DOCUMENTS
 ADDITIONAL INFORMATION WILL BE PROVIDED WHEN IT BECOMES
 AVAILABLE
  
 1) 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS. CONSTRUCTION
 DOCUMENTS SHALL BE OF SUFFICIENT CLARITY TO INDICATE
 THE LOCATION, NATURE AND EXTENT OF THE WORK PROPOSED
 AND SHOW IN
 DETAIL THAT IT WILL CONFORM TO THE PROVISIONS OF THIS
 CODE AND RELEVANT LAWS, ORDINANCES, RULES AND
 REGULATIONS, AS DETERMINED BY THE BUILDING OFFICIAL.
 SUCH DRAWINGS AND SPECIFICATIONS SHALL CONTAIN
 INFORMATION, IN THE FORM OF NOTES OR OTHERWISE, AS TO
 THE QUALITY OF MATERIALS, WHERE QUALITY IS ESSENTIAL TO
 CONFORMITY WITH THE TECHNICAL CODES.
  
 1A) THE SUBMITTED NOA 11-1013.14 PGT SH-700 ALUMINUM
 SINGLE HUNG WINDOWS. IDENTIFY WIDTH, LENGTH, TYPE OF
 GLAZING, TYPE OF ANCHORS AND ASSOCIATED PRESSURES.
  
 1B) PGT MULLIONS NOA 13-0815.05 PGT MULLIONS IDENTIFY
 WIDTH, LENGTH, TYPE OF GLAZING, TYPE OF ANCHORS AND
 ASSOCIATED PRESSURES.
  
 1C) PGT ALUMINUM OUTSWING STOREFRONT W/ TRANSOM NOA
 12-1005.02 IS FOR DOOR AND TRANSOM THE ARCHITECTURAL
 SHEET A2 SHOW 8 FT TALL DOUBLE DOORS NO TRANSOM.
 DENTIFY WIDTH, LENGTH, TYPE OF GLAZING, TYPE OF ANCHORS
 AND ASSOCIATED PRESSURES.
  
 1D) BEST ROLLING DOOR NOA 12-0124.10 TECHNICAL SHEET 3
 OF 3 IS ILLIGABLE 107.2.1.4 QUALITY OF BUILDING PLANS.
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: (561) 805-6715
 FAX: (561)805-6676
 E-MAIL: [email protected]