| Plan Review Notes For Permit 15020941 |
| Permit Number |
15020941 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2015-06-26 14:57:53 | 1ST REVIEW: FBC 2010 MECHANICAL | | | 6/26/15 | | | | | | 1) THE MECHANICAL CLOSET LOUVERED DOOR #2 SHALL BE OF | | | NON-COMBUSTIBLE MATERIALS: THE DOOR SCHEDULE IS | | | INDICATING A WOOD DOOR- REFERENCE SECTIONS 202, 602, | | | AND 603.1 FBC-10 MECHANICAL. | | | 2) INDICATE HOW THE O/A DAMPER IS BEING CONTROLLED- | | | REFER TO SECTION 503.2.5.4 FBC-10 ENERGY CONSERVATION. | | | 3) THE TOILET EXHAUST FAN FOR BATH 1 SHALL HAVE A | | | MINIMUM EXHAUST CAPACITY OF 100 CFM'S PER TABLE 403.3 | | | FOOTNOTE E. 50 CFM PER TOILET OR URINAL. | | | 4) PROVIDE TIE DOWN ENGINEERING FOR THE AC CONDENSERS- | | | SECTION 301.12 | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | | | | |
|