| 2015-06-25 16:24:36 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 15020941 |
| | ADD: 633 5TH ST. |
| | CONT: BUILT SOLID CONSTRUCTION |
| | TEL: (561)333-2593 |
| | E-MAIL: [email protected] |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 2ND REVIEW |
| | DATE: THURS. JUNE 25/ 2015 |
| | ACTION: DENIED |
| | |
| | 1) COMPLIED. |
| | |
| | 2) 2ND REQUEST. MISSING SOILS REPORT WITH THE MINIMUM |
| | SAFE BEARING VALUE. 2010 FBC-B 1803.5.2 QUESTIONABLE |
| | SOIL. WHERE THE CLASSIFICATION, STRENGTH OR |
| | COMPRESSIBILITY OF THE SOIL IS IN DOUBT OR WHERE A |
| | LOAD-BEARING VALUE SUPERIOR TO THAT SPECIFIED IN THIS |
| | CODE IS CLAIMED, THE BUILDING OFFICIAL SHALL BE |
| | PERMITTED TO REQUIRE THAT A GEOTECHNICAL INVESTIGATION |
| | BE CONDUCTED. |
| | |
| | 3-8) COMPLIED. |
| | |
| | 9) 2ND REQUEST. SHEET A-1 SHOWS A NEW RAMP WITH A |
| | HEIGHT OF 6 INCHES AND A 6 INCH STEP ADJACENT TO THE |
| | RAMP.THE 2010 FBC-B 1003.5 WHERE CHANGES IN ELEVATION |
| | OF LESS THAN 12 INCHES IN A MEANS OF EGRESS SLOPED |
| | SURFACES SHALL BE USED, NOT A STEP. |
| | NOTE IF THE FINISH FLOOR IS 6 INCHES OR LESS THAN |
| | HANDRAILS ARE NOT REQUIRED. IF WHEN IN THE FIELD THE |
| | RAMP IS EITHER GREATER THAN 6 INCHES IN HEIGHT OR 72 |
| | INCHES IN LENGTH HANDRAILS WILL BE REQUIRED PER 1010.8 |
| | WITH THE REQUIRED BACKING FOR HANDRAILS. |
| | |
| | 10) 2ND REQUEST. SHEET A-1 SHOWS IN THE AREA OF WORK |
| | (2) EXTERIOR DOORWAYS WITH A 4INCH DROP, BOTH DOORS ARE |
| | SHOWN TO BE REQUIRED EXITS. PLEASE REVIEW: |
| | 2010 FBC-B 1008.1.5 FLOOR ELEVATION. THERE SHALL BE A |
| | FLOOR OR LANDING ON EACH SIDE OF A DOOR. SUCH FLOOR OR |
| | LANDING SHALL BE AT THE SAME ELEVATION ON EACH SIDE OF |
| | THE DOOR. LANDINGS SHALL BE LEVEL EXCEPT FOR EXTERIOR |
| | LANDINGS, WHICH ARE PERMITTED TO HAVE A SLOPE NOT TO |
| | EXCEED 1 UNIT VERTICAL IN 50 UNITS HORIZONTAL |
| | (2-PERCENT SLOPE). |
| | |
| | 11-14) COMPLIED. |
| | |
| | 15) WHEN RESUBMITTING PLANS PLEASE INDICATE THE |
| | REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES |
| | AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A |
| | RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| | THIS REVIEW. |
| | |
| | JAMES WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: (561) 805-6715 |
| | FAX: (561)805-6676 |
| | E-MAIL: [email protected] |
| | DEVELOPMENT SERVICES HOME PAGE |
| | HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP |
| | |
| | |
| | |
| | |
| | |
| | |
| | |