| 2015-04-02 07:00:57 | 1) SUBMIT DETAIL OF BREAKROOM SINK. SINK SHALL COMPLY |
| | W/ FAC SEC.212 & 606. |
| | 2) SHOW THE DIMENSIONS ( L X W) OF THE TOILET ROOMS ON |
| | SHEET A-3.1. |
| | 3) SHT. D-1 - THE BREAK ROON SINK COUNTERTOP SHALL BE |
| | AT A HEIGHT OF 34INCHES MAXIMUM ABOVE THE FINISH FLOOR |
| | PER THE 2010 FAC SEC.212 7 606. |
| | 4) THE TOILET ROOMS DO NOT APPEAR TO BE WIDE ENOUGH TO |
| | PROVIDE THE REQUIRED CLEAR FLOOR SPACE FOR THE WATER |
| | CLOSET AND THE SPACING OF THE FIXTURES. A MINIMUM WIDTH |
| | OF 85 INCHES IS REQUIRED WHEN THE LAVATORY AND WATER |
| | CLOSET ARE ON THE SAME WALL. CLARIFY. |
| | 5) SHT. A-1 - THE LOCATION OF THE URINAL IN THE MEN'S |
| | RESTROOM DOES NOT APPEAR TO PROVIDE THE REQUIRED |
| | PRIVACY AS SPECIFIED IN THE 2010 FPC SEC.310.5.THE LINE |
| | OF SIGHT TO THE URINAL WHEN THE DOOR IS OPEN IS CLEAR |
| | TO THE URINAL. |
| | 6) SHT.A-3.1 - THE GRAB BARS SHALL BE MEASURED TO THE |
| | TOP OF THE GRIPPING SURFACE OF THE GRAB BAR PER THE |
| | 2010 FAC SEC.609.4. SEE DETAILS #2 & # 4 ON SHT. A3-1. |
| | 7) SHT.A-3.1 - DETAIL #6 - THE LAVATORY CLEARANCES |
| | SHALL COMPLY WITH THE FAC SEC.606.3 (MAXIMUM 34" TO THE |
| | RIM OF THE LAVATORY). |
| | 8) SHT. A-3.1 - DETAIL #8 SHOWS AN OPTIONAL CUP |
| | DISPENSER. THIS IS NOT PERMNITTED PER THE 2010 FAC |
| | SEC.211.2. A MINIMUM OF 2 DRINKING FOUNTAINS ARE |
| | REQUIRED. |
| | 9) SHT. P-1 - ETAIL #3 - THE LAVATORY IN THE MEN'S |
| | RESSTROOM STALL IS NOT VENTED PER THE 2010 FPC |
| | SEC.901.2, 901.2.1. |
| | 10) THE SANITARY SHOWS 3" VTR'S FOR 2" STACKS.LARIFY. |
| | 11) THE URINAL IS NOT ON THE SANITARY RISER. |
| | 12) CLEANOUTS ARE REQUIRED IN THE BASE OF ALL STACKS. |
| | 2010 FPC SEC.708.3.4. |
| | 13) SUBMIT A WATER RISER DIAGRAM FOR REVIEW. WPB AMEND. |
| | TO 2010 FBC SEC. 107.3.5.1.3. |
| | |
| | PLUMBING PLAN REVIEW |
| | TIM LARGE |
| | CHIEF PLUMBING INSPECTOR |
| | 561-805-6692 |
| | [email protected] |
| | |