| 2015-03-13 10:21:07 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 15020941 |
| | ADD: 633 5TH ST. |
| | CONT: BUILT SOLID CONSTRUCTION |
| | TEL: (561)333-2593 |
| | E-MAIL: [email protected] |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | IMPORTANT NOTICE: EFFECTIVE MARCH 30, 2015 |
| | ALL PERMIT APPLICATION PLAN REVIEWS WILL BE PERFORMED |
| | ELECTRONICALLY |
| | UPON APPLICATION AND FEE PAYMENT DESIGN DOCUMENTS |
| | SUBMISSION OPTIONS ARE AS FOLLOWS: |
| | 1 UPLOAD VIA THE PROJECT DOX PORTAL WITH DIGITAL |
| | SIGNATURES OF DESIGN PROFESSIONALS AS APPLICABLE; USE |
| | THE REQUIRED NAMING CONVENTION FOR EACH DOCUMENT |
| | 2 INCLUDE ON A CD IF DESIGN PROFESSIONAL DIGITAL |
| | SIGNATURES ARE PROVIDED AS REQUIRED; USE THE REQUIRED |
| | NAMING CONVENTION FOR EACH DOCUMENT |
| | 3 INCLUDE ON A CD WITH ONE SET OF TRADITIONAL PAPER |
| | DESIGN DOCUMENTS SIGNED AND SEALED AS REQUIRED; USE THE |
| | REQUIRED NAMING CONVENTION FOR EACH DOCUMENT |
| | 4 ONE SET OF TRADITIONAL PAPER DESIGN DOCUMENTS SUBJECT |
| | TO ADMINISTRATIVE FEES TO DIGITIZE THE DOCUMENTS |
| | ADDITIONAL INFORMATION WILL BE PROVIDED WHEN IT BECOMES |
| | AVAILABLE |
| | |
| | 1ST REVIEW |
| | DATE: FRI. MARCH 13/ 2015 |
| | ACTION: DENIED |
| | |
| | 1) THE ARCHITECT OF RECORD FOR THIS PROJECT HAS ON HER |
| | TITLE BLOCK INDICATED THAT : DRAWINGS ARE SIGNED ND |
| | SEALED FOR STRUCTURE ONLY. |
| | DOES THE ARCHIEC TO RECORD HAVE A ENGINEERING LICENSE |
| | AND REGISTRATION IN THE STATE OF FLORIDA? |
| | ARCHITECTS SEAL 61G1-16.003 USE OF SEAL. |
| | AN ARCHITECT OR INTERIOR DESIGNER SHALL NOT USE HIS |
| | SEAL OR DO ANY OTHER ACT AS AN ARCHITECT OR INTERIOR |
| | DESIGNER UNLESS HOLDING AT THE TIME A CERTIFICATE OF |
| | REGISTRATION AND ALL REQUIRED RENEWALS THEREOF. |
| | |
| | 61G1-16.003 USE OF SEAL. |
| | THE PERSONAL SEAL, SIGNATURE AND DATE OF THE ARCHITECT |
| | OR INTERIOR DESIGNER SHALL APPEAR ON ALL ARCHITECTURAL |
| | OR INTERIOR DESIGN DOCUMENTS TO BE FILED FOR PUBLIC |
| | RECORD AND SHALL BE CONSTRUED TO OBLIGATE HIS PARTNERS |
| | OR HIS CORPORATION. A CORPORATE SEAL ALONE IS |
| | INSUFFICIENT. DOCUMENTS SHALL BE SIGNED PERSONALLY AND |
| | SEALED BY THE RESPONSIBLE ARCHITECT OR INTERIOR |
| | DESIGNER. FINAL OFFICIAL RECORD DOCUMENTS (NOT |
| | TRACINGS, ETC.) SHALL BE SO SIGNED. THE SIGNING AND |
| | SEALING OF THE SPECIFICATION INDEX SHEETS SHALL BE |
| | CONSIDERED ADEQUATE. ALL DRAWING SHEETS AND PAGES SHALL |
| | BE SO SIGNED AND SEALED. AN ARCHITECT OR INTERIOR |
| | DESIGNER SHALL NOT AFFIX, OR PERMIT TO BE AFFIXED, HIS |
| | SEAL OR NAME TO ANY PLAN, SPECIFICATIONS, DRAWINGS, OR |
| | OTHER RELATED DOCUMENT WHICH WAS NOT PREPARED BY HIM OR |
| | UNDER HIS RESPONSIBLE SUPERVISING CONTROL AS PROVIDED |
| | IN RULE CHAPTER 61G1-23, F.A.C. AN ARCHITECT OR |
| | INTERIOR DESIGNER SHALL NOT USE HIS SEAL OR DO ANY |
| | OTHER ACT AS AN ARCHITECT OR INTERIOR DESIGNER UNLESS |
| | HOLDING AT THE TIME A CERTIFICATE OF REGISTRATION AND |
| | ALL REQUIRED RENEWALS THEREOF. |
| | |
| | ENGINEERING 471.003 471.003?QUALIFICATIONS FOR |
| | PRACTICE; EXEMPTIONS. (3) HOWEVER, NO ENGINEER SHALL |
| | PRACTICE ARCHITECTURE OR USE THE DESIGNATION |
| | ?ARCHITECT? OR ANY TERM DERIVED THEREFROM, AND NO |
| | ARCHITECT SHALL PRACTICE ENGINEERING OR USE THE |
| | DESIGNATION ?ENGINEER? OR ANY TERM DERIVED THEREFROM. |
| | |
| | 2) MISSING SOILS REPORT WITH THE MINIMUM SAFE BEARING |
| | VALUE. 2010 FBC-B 1803.5.2 QUESTIONABLE SOIL. WHERE THE |
| | CLASSIFICATION, STRENGTH OR COMPRESSIBILITY OF THE SOIL |
| | IS IN DOUBT OR WHERE A LOAD-BEARING VALUE SUPERIOR TO |
| | THAT SPECIFIED IN THIS CODE IS CLAIMED, THE BUILDING |
| | OFFICIAL SHALL BE PERMITTED TO REQUIRE THAT A |
| | GEOTECHNICAL INVESTIGATION BE CONDUCTED. |
| | |
| | 3) THE ENERGY DOCUMENTS SUBMITTED SHOW A ELITE SOFTWARE |
| | PROGRAM. UNDER THE 2010 FBC- ENERGY SHALL COMPLY WITH : |
| | 103.2.1.2.1 BUILDING THERMAL ENVELOPE ALTERNATIVE. |
| | AN ACCURATELY COMPLETED COMMERCIAL BUILDING FORM 502 |
| | SHALL BE SUBMITTED TO THE BUILDING OFFICIAL TO |
| | DEMONSTRATE CODE COMPLIANCE BY THIS METHOD. |
| | |
| | 103.2.2.2 SIMULATED PERFORMANCE ALTERNATIVE, COMMERCIAL |
| | AND HIGH-RISE RESIDENTIAL. |
| | AN ACCURATELY COMPLETED COMMERICAL BUILDING FORM 506 |
| | (GENERATED BY COMMISSION APPROVED SOFTWARE) |
| | DEMONSTRATING THAT CODE COMPLIANCE HAS BEEN ACHIEVED |
| | SHALL BE SUBMITTED TO THE BUILDING OFFICIAL FOR |
| | COMPLIANCE BY SECTION 506. |
| | 06.3.2 ENVELOPE LIMITATION. |
| | FOR NEW BUILDINGS OR ADDITIONS, THE BUILDING ENERGY |
| | COST BUDGET METHOD RESULTS SHALL NOT BE SUBMITTED FOR |
| | BUILDING PERMIT APPROVAL TO THE CODE OFFICIAL PRIOR TO |
| | SUBMITTAL FOR APPROVAL OF THE BUILDING ENVELOPE DESIGN. |
| | |
| | 4A) NOTE THE WINDOW AND DOOR PRODUCT APPROVALS |
| | SUBMITTED, DOES NOT HAVE THE SHOP DRAWING STAMP OF |
| | APPROVAL FROM THE DESIGNER OF RECORD. |
| | SHOP DRAWING STAMP OF APPROVAL |
| | 106.3* PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE |
| | REGULATED BY DCA RULE 9N-3 SHALL BE REVIEWED AND |
| | APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO |
| | SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | |
| | 4B) ROOFING PRODUCT APPROVAL, 2 DIFFERENT ROOFING |
| | SHINGLE NOAS WERE SUBMITTED, NOA:14-1022.20 GAF |
| | TIMBERLINE & NOA 11-0913.12 TAMCO ELITE GLASS-SEAL ROOF |
| | SHINGLES. THE TAMCO ELITE SHINGLE DOES HAVE THE SHOP |
| | DRAWING STAMP OF APPROVAL. WHICH IS TO BE INSTALLED? |
| | 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED. |
| | |
| | 5) SHEET A-5 INDICATES THIS TO BE THE FOUNDATION PLAN. |
| | THERE ARE NO NOTES IN REGARD TO THE MINIMUM BEARING |
| | VALUE OF THE SOIL, VAPOR BARRIER REQUIREMENTS NOR THE |
| | TYPE OF TERMITE TREATMENT FOR THE SLAB. |
| | 1816.1 TERMITE PROTECTION. |
| | 1910.1 MINIMUM SLAB PROVISIONS. |
| | 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| | CODE, CHAPTER 1, ADMINISTRATION, |
| | 107.3.5.1 COMMERCIAL BUILDINGS: |
| | 107.3.5.1.1 BUILDING |
| | STRUCTURAL REQUIREMENTS SHALL INCLUDE: |
| | SOIL CONDITIONS/ANALYSIS |
| | TERMITE PROTECTION |
| | DESIGN LOADS |
| | WIND REQUIREMENTS |
| | |
| | 6) SHEET A-5 INDICATES IN A WALL SECTION SHEET S-1 |
| | DETAIL 1 MISSING THERE IS NO S-1 SHEET. 107.2.1.3 |
| | ADDITIONAL INFORMATION IS REQUIRED. |
| | |
| | 7) MISSING BEAM SCHEDULE, THE COLUMN SCHEDULE IS |
| | PRINTED TWICE. NOT THERE IS ALSO NO LINTEL SCHEDULE FOR |
| | WINDOWS NOR IS THERE A TRUSS LAYOUT WITH THE LOADS TO |
| | BE RESISTED, GRAIVITY, UPLIFT OR LATERAL LOADS. |
| | 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| | CODE, CHAPTER 1, ADMINISTRATION, |
| | 107.3.5.1 COMMERCIAL BUILDINGS: |
| | 107.3.5.1.1 BUILDING |
| | STRUCTURAL REQUIREMENTS SHALL INCLUDE: |
| | DESIGN LOADS |
| | WIND REQUIREMENTS |
| | BUILDING ENVELOPE |
| | WALL SYSTEMS |
| | ROOF SYSTEMS TRUSSES, DROPPED TRUSSES FOR GABLE |
| | OVERHANG OF 2 FT |
| | MWFRS MAIN WIND FORCE RESISTING SYSTEM |
| | |
| | 8) THE COVERSHEET LIST THE NEW ADDITION AS A BUSINESS |
| | OCCUPANCY. 2010 FBC-B 1004.1.1 AREAS WITHOUT SEATING |
| | NEED TO BE EVALUATED IN THE WORST CASE SCENARIO, THIS |
| | AREA MAY BE USED AS A SUNDAY SCHOOL CLASS, AS A |
| | FELLOWSHIP HALL OR FOR OTHER FUNCTIONSOF A A3 |
| | OCCUPANCY. SEE TABLE 1004.1.1 AREAS WHERE UN |
| | CONCENTRATED SEATING TABLE AND CHAIRS PLEASE USE 15 |
| | NET. |
| | |
| | 9) SHEET A-1 SHOWS A NEW RAMP WITH A HEIGHT OF 6 |
| | INCHES. NOTE IF THE FINISH FLOOR IS 6 INCHES OR LESS |
| | THAN HANDRAILS ARE NOT REQUIRED. IF WHEN IN THE FIELD |
| | THE RAMP IS EITHER GREATER THAN 6 INCHES IN HEIGHT OR |
| | 72 INCHES IN LENGTH HANDRAILS WILL BE REQUIRED PER |
| | 1010.8 WITH THE REQUIRED BACKING FOR HANDRAILS. |
| | |
| | 10) SHEET A-1 SHOWS INTHE AREA OF WORK (2) EXTERIOR |
| | DOORWAYS WITH A 4INCH DROP, BOTH DOORS ARE SHOWN TO BE |
| | REQUIRED EXITS. NOTE WITH THE ASSEMBLY OCCUPANCY THIS |
| | AREA WILL HAVE A OCCUPANT LOAD GREATERTHAN 50 REQUIRING |
| | (2) EXITS. PLEASE REVIEW: |
| | |
| | 2010 FBC-B 1008.1.5 FLOOR ELEVATION. THERE SHALL BE A |
| | FLOOR OR LANDING ON EACH SIDE OF A DOOR. SUCH FLOOR OR |
| | LANDING SHALL BE AT THE SAME ELEVATION ON EACH SIDE OF |
| | THE DOOR. LANDINGS SHALL BE LEVEL EXCEPT FOR EXTERIOR |
| | LANDINGS, WHICH ARE PERMITTED TO HAVE A SLOPE NOT TO |
| | EXCEED 1 UNIT VERTICAL IN 50 UNITS HORIZONTAL |
| | (2-PERCENT SLOPE). |
| | |
| | 11) SHEET A-1 DOES NOT SHOW THE DOOR HARDWARE FOR THE |
| | NEW DOOR OPENINGS. 2010 FBC-B 1008.1.9.1, 1008.1.9.3 |
| | AND 1008.1.10. |
| | |
| | 12) SHEET A-2 INDICATES THE USE OF EAVE VENTS BUT DOES |
| | NOT SHOW COMPLIANCE WITH THE UPPER PORTION OF THE ROOF |
| | BEING VENTED. 2010 FBC-B 1203.2 ATTIC SPACES. THE NET |
| | FREE VENTILATING AREA SHALL NOT BE LESS THAN 1/300 OF |
| | THE AREA OF THE SPACE VENTILATED, WITH 50 PERCENT OF |
| | THE REQUIRED VENTILATING AREA PROVIDED BY VENTILATORS |
| | LOCATED IN THE UPPER PORTION OF THE SPACE TO BE |
| | VENTILATED AT LEAST 3 FEET (914 MM) ABOVE EAVE OR |
| | CORNICE VENTS WITH THE BALANCE OF THE REQUIRED |
| | VENTILATION PROVIDED BY EAVE OR CORNICE VENTS. |
| | |
| | 13) SHEET A-2 ALSO FAILS TTO SHOW COMPLIANCE WITH 2010 |
| | FBC-B 1209.2 ATTIC SPACES. |
| | AN OPENING NOT LESS THAN 20 INCHES BY 30 INCHES (559 MM |
| | BY 762 MM) SHALL BE PROVIDED TO ANY ATTIC AREA HAVING A |
| | CLEAR HEIGHT OF OVER 30 INCHES (762 MM). A 30-INCH (762 |
| | MM) MINIMUM CLEAR HEADROOM IN THE ATTIC SPACE SHALL BE |
| | PROVIDED AT OR ABOVE THE ACCESS OPENING. |
| | |
| | 14) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT |
| | FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL |
| | PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND |
| | A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT |
| | APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | 15) WHEN RESUBMITTING PLANS PLEASE INDICATE THE |
| | REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES |
| | AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A |
| | RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| | THIS REVIEW. |
| | |