| 2016-12-02 17:41:34 | 1ST REVIEW |
| | |
| | GEORGE JOHNSON |
| | PLUMBING PLANS EXAMINER LL |
| | CITY OF WEST PALM BEACH |
| | DEVELOPMENT SERVICES |
| | BUILDING DIVISION |
| | 561-805-6711 |
| | [email protected] |
| | |
| | PLUMBING COMMENTS: |
| | |
| | 1. THE BATHROOMS IN THE CLASS ROOMS ON FIRST FLOOR |
| | SHOULD COMPLY WITH THE REQUIREMENTS FOR THE YOUNGER |
| | CHILDREN IN THE ADVISORY CHART FBC ACC 604.9 |
| | |
| | 2. THE RIM OF LAVATORY'S IN ALL THE CHILDREN'S |
| | BATHROOMS SHOULD BE SET AT 31" ABOVE FINISHED FLOOR. |
| | PER FBC ACC 606.2 |
| | |
| | 3. SEPARATE FACILITIES FOR EACH SEX ARE REQUIRED FOR |
| | THE STAFF BATHROOMS. PER FBC PL 403.2 |
| | |
| | 4. SHT. A4.2 DETAIL 03 PLEASE PROVIDE THE DIMENSION |
| | FROM THE SIDE WALL OF TOILET TO THE PARTITION NEXT TO |
| | LAV IT SHALL BE A MIN OF 84" 85 " TO ALLOW FOR |
| | CONSTRUCTION TOLERANCES. PER FBC PL 604.3.1 |
| | |
| | 5. SHT. A4.2 DETAIL 01 THE WIDTH OF 6' 8" DOES NOT |
| | ALLOW FOR COMPLIANCE WITH FBC PL 604.3.1 IT SHALL BE |
| | 84" 85 " TO ALLOW FOR CONSTRUCTION TOLERANCES. |
| | |
| | 6.SHT A4.2 DETAIL 04 PROVIDE DIMENSION FROM SIDEWALL OF |
| | TOILET TO THE PARTITION TO COMPLY WITH FBC PL604.3.1 |
| | |
| | 7. SHT. 3.1 SANITARY RISER |
| | A) FIRST FLOOR RM 180 THE FLOOR DRAIN SHALL BE |
| | INDIVIDUALLY VENTED. PER FBC PL 901.2 AND 901.2.1 |
| | B)FIST FLOOR RM 181 THE FLOOR DRAIN SHALL CONNECT WITH |
| | FIXTURE BRANCH OF SERVICE SINK NO BUILDING DRAIN. PER |
| | FBC PL 901.2 AND 901.2.1 |
| | C)SECONDD FLOOR IN ROOM 280 THE FLOOR DRAIN SHALL BE |
| | INDIVIDUALLY VENTED. PER FBC PL 901.2 AND 901.2.1 |
| | D) SECON FLOOR THE EWC SHALL CONNECT DOWN STREAM OF THE |
| | BATHROOM GROUPS.FBC PL 909.1 |
| | |
| | 8 SHT. P8.1 DETAIL 7 THE HOT WATER RECIRCULATION RETURN |
| | LINE SHALL CONNECT TO COLD WATER INLET OF WATER HEATER |
| | AND THE TEMPERING VALVE. PER FBC PL 607.2.3 |
| | |
| | 9. SHT.P5.1 ROOF AREAS G,F,I,J HAVE A NOTE ON THEM THAT |
| | STATES HORIZONTAL STORM DRAIN SIZE = 3" 657 SF MAX THIS |
| | IS UNDER THE SF OF THESE AREAS PLEASE CLARIFY. PER WPB |
| | AMEND TO FBC 107.2.1 |
| | |
| | 10. SHT. P5.1 THE OVERFLOW DRAIN SHALL BE SIZED THE |
| | SAME AS THE PRIMARY DRAIN. PER FBC PL 1107.3 |
| | |
| | 11. PLEASE PROVIDE SF AND SLOPE ON THE STORM RISER |
| | DIAGRAM. PER WPB AMEND TO FBC 107.2.1 |
| | |
| | 12. SHT. P6.1 DETAIL 1 THE NOTE ON 1" CD DN TO FIRST |
| | FLOOR SHOULD READ DN FROM 2ND FLOOR PLEASE CLARIFY. PER |
| | WPB AMEND TO FBC 107.2.1 |
| | |
| | 13. ARE ANY OF THE CLASSROOMS BEING USED AS A SCIENCE |
| | LAB THAT WILL USW CHEMICALS IF SO PLEASE PROVIDE TYPE |
| | OF CHEMICAL MSDS SHEETS THE AMOUNTS AND HOW THERE BEING |
| | STORED. PER WPB AMEND TO FBC 107.2.1 |
| | |
| | |