| Date |
Text |
| 2016-11-21 15:48:06 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | |
| | |
| | 1) SHEET LS 1.1 & OTHER A SHEETS - EXIT STAIR 1-003 |
| | INDICATES AN EXITING DOOR ON THE GROUND LEVEL. THERE IS |
| | AN SLIDING GLASS DOOR ASSEMBLY LOCATED WITHIN 10FT THAT |
| | IS NOT INDICATED A FIRE RATED. |
| | |
| | PER NFPA 101, CHAPTER 7 |
| | |
| | 7.2.2.5 ENCLOSURE AND PROTECTION OF STAIRS. |
| | 7.2.2.5.1 ENCLOSURES. |
| | 7.2.2.5.1.1 ALL INSIDE STAIRS SERVING AS AN EXIT OR |
| | EXIT COMPONENT SHALL BE ENCLOSED IN ACCORDANCE WITH |
| | 7.1.3.2. |
| | |
| | 7.2.2.5.2* EXPOSURES. |
| | 7.2.2.5.2.1 WHERE NONRATED WALLS OR UNPROTECTED |
| | OPENINGS ENCLOSE THE EXTERIOR OF A STAIRWAY, OTHER THAN |
| | AN EXISTING STAIRWAY, AND THE WALLS OR OPENINGS ARE |
| | EXPOSED BY OTHER PARTS OF THE BUILDING AT AN ANGLE OF |
| | LESS THAN 180 DEGREES, THE BUILDING ENCLOSURE WALLS |
| | WITHIN 10 FT (3050 MM) HORIZONTALLY OF THE NONRATED |
| | WALL OR UNPROTECTED OPENING SHALL BE CONSTRUCTED AS |
| | REQUIRED FOR STAIRWAY ENCLOSURES, INCLUDING OPENING |
| | PROTECTIVES. |
| | 7.2.2.5.2.2 CONSTRUCTION SHALL EXTEND VERTICALLY FROM |
| | THE FINISHED GROUND LEVEL TO A POINT 10 FT (3050 MM) |
| | ABOVE THE TOPMOST LANDING OF THE STAIRS OR TO THE |
| | ROOFLINE, WHICHEVER IS LOWER. |
| | 7.2.2.5.2.3 THE FIRE RESISTANCE RATING OF THE |
| | SEPARATION EXTENDING 10 FT (3050 MM) FROM THE STAIRS |
| | SHALL NOT BE REQUIRED TO EXCEED 1 HOUR WHERE OPENINGS |
| | HAVE A MINIMUM ?-HOUR FIRE PROTECTION RATING. |
| | |
| | PLEASE PROVIDE FOR THE REQUIRED RATING. |
| | |
| | |
| | 2) SHEET LS 1.2 & OTHER A SHEETS - THERE ARE WINDOWS |
| | INDICATEDAS "J" WITHIN THE EXIT ENCLOSURES 1-003 & |
| | 1-006. THOSE WINDOWS CAN NOT BE FOUND ON THE SCHEDULE |
| | AS HAVING ANY KIND OF FIRE RATING THAT IS EQUAL TO THE |
| | WALL RATING. |
| | |
| | PER NFPA 101, CHAPTER 7 |
| | |
| | 7.2.2.5 ENCLOSURE AND PROTECTION OF STAIRS. |
| | 7.2.2.5.1 ENCLOSURES. |
| | 7.2.2.5.1.1 ALL INSIDE STAIRS SERVING AS AN EXIT OR |
| | EXIT COMPONENT SHALL BE ENCLOSED IN ACCORDANCE WITH |
| | 7.1.3.2. |
| | |
| | 7.1.3.2 EXITS. |
| | 7.1.3.2.1 WHERE THIS CODE REQUIRES AN EXIT TO BE |
| | SEPARATED FROM OTHER PARTS OF THE BUILDING, THE |
| | SEPARATING CONSTRUCTION SHALL MEET THE REQUIREMENTS OF |
| | SECTION 8.2 AND THE FOLLOWING: |
| | (1)* THE SEPARATION SHALL HAVE A MINIMUM 1-HOUR FIRE |
| | RESISTANCE RATING WHERE THE EXIT CONNECTS THREE OR |
| | FEWER STORIES. |
| | |
| | (9)* OPENINGS IN EXIT ENCLOSURES SHALL BE LIMITED TO |
| | DOOR ASSEMBLIES FROM NORMALLY OCCUPIED SPACES AND |
| | CORRIDORS AND DOOR ASSEMBLIES FOR EGRESS FROM THE |
| | ENCLOSURE, UNLESS ONE OF THE FOLLOWING CONDITIONS |
| | EXISTS: |
| | |
| | (10) PENETRATIONS INTO, AND OPENINGS THROUGH, AN EXIT |
| | ENCLOSURE |
| | ASSEMBLY SHALL BE LIMITED TO THE FOLLOWING: |
| | |
| | A WINDOW IS NOT LISTED UNDER ANY OF THE 9 ITEMS. |
| | |
| | THE WINDOW OPENING SHALL BE RATED OR REMOVED AS IT IS |
| | NOT ESSTENITIAL FOR THE FUNCTION OF THE STAIR. |
| | |
| | |
| | |
| | 3) LS 1.1 - THE WALLS SURROUNDING THE STORAGE ROOM |
| | 1-111 ARE NOT INDICATED AS BEING FIRE RATED EQUAL TO |
| | THE STAIR ENCLOSURE. |
| | |
| | 7.2.2.5.3* USABLE SPACE. ENCLOSED, USABLE SPACES WITHIN |
| | EXIT ENCLOSURES SHALL BE PROHIBITED, INCLUDING UNDER |
| | STAIRS, UNLESS OTHERWISE PERMITTED BY 7.2.2.5.3.2. |
| | 7.2.2.5.3.2 ENCLOSED, USABLE SPACE SHALL BE PERMITTED |
| | UNDER STAIRS, PROVIDED THAT BOTH ALL OF THE FOLLOWING |
| | CRITERIA ARE MET: |
| | (1) THE SPACE SHALL BE SEPARATED FROM THE STAIR |
| | ENCLOSURE BY THE SAME FIRE RESISTANCE AS THE EXIT |
| | ENCLOSURE. |
| | (2) ENTRANCE TO THE ENCLOSED, USABLE SPACE SHALL NOT BE |
| | FROM WITHIN THE STAIR ENCLOSURE. (SEE ALSO 7.1.3.2.3.) |
| | (3) THE SPACE IS NOT USED FOR THE STORAGE OF FLAMMABLE, |
| | OR OTHERWISE HAZARDOUS MATERIALS. |
| | |
| | PLEASE PROVIDE DETAIL FOR THIS REQUIREMENT |
| | |
| | |
| | |
| | 4) SHEET A 19.1 & A 14.1 - THE SHEETS WERE PLACED |
| | UPSIDE DOWN. |
| | |
| | PLEASE CORRECT TO PROPER PLACEMENT. |
| | |
| | |
| | |
| | 5) SHEET A 14.1 - THE DOOR SCHEDULE APPEARS TO ONLY |
| | INDICATED DOORS ON THE 2ND LEVEL, THERE APPEARS TO BE |
| | NO DOOR SCHEDULE FOR THE 1ST FLOOR. |
| | |
| | PLEASE REVIEW AND ENSURE THE IS A DOOR SCHEDULE FOR THE |
| | 1ST FLOOR AND ALL DOORS ARE ACCOUNTED FOR. |
| | |
| | |
| | |
| | 6) SHEET A 14.1 - DOORS , BUT NOT LIMITED TO, 203, 008, |
| | 200, 206A, 206(STAFF LOUNGE) 003, ALL APPEAR TO BE |
| | MISSING FROM THE SCHEDULE. |
| | |
| | PLEASE REVIEW ALL DOORS AND ENSURE THEY ARE CONTAINED |
| | WITHIN THE DOR SCHEDULE. |
| | |
| | |
| | |
| | |
| | 7) LS 1.2 - THERE ARE MULTIPLE CANOPY'S THAT COVER THE |
| | EXIT EGRESS TO A PUBLIC WAY. THESE CANOPY'S ARE |
| | INDICATED WITH ANY FIRE PROTECTION RATING OR FIRE |
| | SPRINKLER PROTECTION. |
| | |
| | PER NFPA 101 EXIT DISCHARGE SHALL BE PROVIDED TO A |
| | PUBLIC WAY. |
| | |
| | 3.3.83 EXIT DISCHARGE. THAT PORTION OF A MEANS OF |
| | EGRESS BETWEEN THE TERMINATION OF AN EXIT AND A PUBLIC |
| | WAY. |
| | |
| | 7.1.9 IMPEDIMENTS TO EGRESS. ANY DEVICE OR ALARM |
| | INSTALLED TO RESTRICT THE IMPROPER USE OF A MEANS OF |
| | EGRESS SHALL BE DESIGNED AND INSTALLED SO THAT IT |
| | CANNOT, EVEN IN CASE OF FAILURE, IMPEDE OR PREVENT |
| | EMERGENCY USE OF SUCH MEANS OF EGRESS, UNLESS OTHERWISE |
| | PROVIDED IN 7.2.1.6 AND CHAPTERS 18, 19, 22, AND 23. |
| | |
| | 7.1.10 MEANS OF EGRESS RELIABILITY. |
| | 7.1.10.1* GENERAL. MEANS OF EGRESS SHALL BE |
| | CONTINUOUSLY MAINTAINED FREE OF ALL OBSTRUCTIONS OR |
| | IMPEDIMENTS TO FULL INSTANT USE IN THE CASE OF FIRE OR |
| | OTHER EMERGENCY. |
| | |
| | 7.2.3.5 DISCHARGE. |
| | 7.2.3.5.1 EVERY SMOKEPROOF ENCLOSURE SHALL DISCHARGE |
| | INTO A PUBLIC WAY, INTO A YARD OR COURT HAVING DIRECT |
| | ACCESS TO A PUBLIC WAY, OR INTO AN EXIT PASSAGEWAY. |
| | SUCH EXIT PASSAGEWAYS SHALL BE WITHOUT OPENINGS, OTHER |
| | THAN THE ENTRANCE TO THE SMOKEPROOF ENCLOSURE AND THE |
| | DOOR OPENING TO THE OUTSIDE YARD, COURT, OR PUBLIC WAY. |
| | THE EXIT PASSAGEWAY SHALL BE SEPARATED FROM THE |
| | REMAINDER OF THE BUILDING BY A 2-HOUR FIRE RESISTANCE |
| | RATING. |
| | |
| | PROTECTION SHALL BE PROVIDED UNTIL A PERSON HAS ACCESS |
| | TO A PUBLIC WAY. THE CANOPY STRUCTURE CAN BE AFFECTED |
| | BY THE PRODUCTS OF COMBUSTION WHICH COULD LEAD TO |
| | FAILURE AND TRAP EXTING PERSONS. |
| | |
| | PLEASE PROVIDE FOR THE REQUIRED PROTECTION LEADING TO A |
| | PUBLIC WAY. |
| | |
| | |
| | |
| | 8) SHEET S 6.1 - THERE APPEARS TO BE LIGHT WEIGHT TRUSS |
| | CONSTRUCTION OF BOTH THE FLOOR AND ROOF OF THE PROPOSED |
| | BUILDING. |
| | |
| | PLEASE PROVIDE FOR THE APPLICABLE FLOOR & TRUSS SIGN |
| | REQUIRED BY FLORIDA STATUTUE. |
| | |
| | PER FLORIDA 69A-60.0081; NOTICE SIGNAGE IS REQUIRED FOR |
| | STRUCTURES WITH LIGHT-FRAME TRUSS-TYPE CONSTRUCTION. |
| | ANY COMMERCIAL, INDUSTRIAL, OR ANY MULTIUNIT |
| | RESIDENTIAL STRUCTURE OF THREE UNITS OR MORE WHICH USES |
| | HORIZONTAL OR VERTICAL LIGHT-FRAME TRUSS-TYPE |
| | CONSTRUCTION IN ANY PORTION SHALL BE MARKED WITH A |
| | MALTESE CROSS SIGN MEASURING 8 INCHES HORIZONTALLY AND |
| | 8 INCHES VERTICALLY, OF A BRIGHT RED REFLECTIVE COLOR. |
| | THE APPROVED SYMBOL SHALL BE PLACED WITHIN 24 INCHES TO |
| | THE LEFT OF THE MAIN ENTRY DOOR. |
| | 1. STRUCTURES WITH LIGHT-FRAME TRUSS ROOFS SHALL BE |
| | MARKED WITH THE LETTER "R". |
| | 2. STRUCTURES WITH LIGHT-FRAME TRUSS FLOOR SYSTEMS |
| | SHALL BE MARKED WITH THE LETTER "F". |
| | 3. STRUCTURES WITH LIGHT-FRAME TRUSS FLOOR AND ROOF |
| | SYSTEMS SHALL BE MARKED WITH THE LETTERS "R/F". |
| | |
| | |
| | |
| | 9) SHEETS LS 1.1 & LS 1.2 - A KITCHEN IS INDICATED |
| | WITHIN THE NOTES OF THE LIFE SAFETY PLAN. |
| | |
| | PER NFPA 101, CHAPTER 14, NEW EDUCATIONAL OCCUPANCIES |
| | |
| | 14.3.2.2 COOKING FACILITIES SHALL BE PROTECTED IN |
| | ACCORDANCE WITH 9.2.3. OPENINGS SHALL NOT BE REQUIRED |
| | TO BE PROTECTED BETWEEN FOOD PREPARATION AREAS AND |
| | DINING AREAS. |
| | |
| | 9.2.3 COMMERCIAL COOKING EQUIPMENT. COMMERCIAL COOKING |
| | EQUIPMENT SHALL BE IN ACCORDANCE WITH NFPA 96, STANDARD |
| | FOR VENTILATION CONTROL AND FIRE PROTECTION OF |
| | COMMERCIAL COOKING OPERATIONS, UNLESS SUCH |
| | INSTALLATIONS ARE APPROVED EXISTING INSTALLATIONS, |
| | WHICH SHALL BE PERMITTED TO BE CONTINUED IN SERVICE. |
| | |
| | PLEASE PROVIDE DETAILS AND THE LOCATION OF THE TYPE OF |
| | KITCHEN BEING PROPOSED. |
| | |
| | |
| | |
| | 10) SHEETS LS 1.1 & 1.2 - SCIENCE LAB IS INDICATED |
| | WITHIN THE NOTES OF THE LIFE SAFETY PLAN. |
| | |
| | 14.3.2.5 EDUCATIONAL OCCUPANCY LABORATORIES USING |
| | CHEMICALS SHALL BE IN ACCORDANCE WITH 8.7.4. |
| | |
| | 8.7.4 LABORATORIES. |
| | 8.7.4.1 LABORATORIES THAT USE CHEMICALS SHALL COMPLY |
| | WITH NFPA 45, STANDARD ON FIRE PROTECTION FOR |
| | LABORATORIES USING CHEMICALS, UNLESS OTHERWISE MODIFIED |
| | BY OTHER PROVISIONS OF THIS CODE. |
| | |
| | PLEASE PROVIDE DETAILS AND THE LOCATION OF THE SCIENCE |
| | LAB BEING PROPOSED. |
| | |
| | |
| | |
| | 11) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | |
| | 12) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |
| | 561-804-4709 |
| | [email protected] |
| | |
| | |
| | |
| | |