| 2016-12-03 11:29:26 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL |
| | BUILDING PLANS EXAMINER |
| | [email protected] |
| | 561-805-6724 |
| | |
| | FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014) |
| | FBC B = FBC BUILDING |
| | FBC EB = FBC EXISTING BUILDING |
| | FBC A = FBC ACCESSIBILITY |
| | FBC EC = FBC ENERGY CONSERVATION |
| | |
| | 1. LS1.0, LS1.1 STATE THIS IS A TWO STORY OFFICE |
| | BUILDING, BUT OCCUPANCY CLASSIFICATION IS PRIMARILY |
| | EDUCATIONAL, REVISE OR CLARIFY. |
| | |
| | 2. LS1.0 EXISTING BUILDING #2 INFORMATION INCLUDES A |
| | HEADING ?NEW BUILDING?, REVISE OR CLARIFY. |
| | |
| | 3. FBC A 201.1.1, ACCESSIBLE ROUTE TO SECOND FLOOR IS |
| | NOT CLEAR. THE ROUTE SHOWN INCLUDES STAIRS IN THE |
| | EXISTING BUILDING. STAIRS ARE NOT A COMPONENT OF AN |
| | ACCESSIBLE ROUTE, SEE FBC 402.2. |
| | |
| | A RAMP IN THE EXISTING BUILDING IS SHOWN, BUT THE ROUTE |
| | IS NOT CLEAR. A1.01 AND OTHER SHEETS DO NOT CLEARLY |
| | SHOW HOW AN OCCUPANT ENTERS THE BUILDING FROM THE RAMP. |
| | THE RAMP DOES NOT APPEAR TO LEAD TO AN ENTRANCE TO THE |
| | BUILDING. |
| | |
| | THE WIDTH OF THE ROUTE (BASE OF STAIRS TO BUILDING) IS |
| | NOT CLEAR IF THE RAMP IN THE BACK OF THE BUILDING IS |
| | THE ACCESSIBLE ROUTE. THIS ROUTE APPEARS CUMBERSOME AND |
| | MORE DIFFICULT THAN THE ROUTE THROUGH THE FRONT; |
| | LONGER, GOES THROUGH AN EXIT STAIR, TWO DOORS, AND AN |
| | UNIDENTIFIED AREA. IF THIS IS PROPOSED AS THE |
| | ACCESSIBLE ROUTE, PLEASE GET THIS APPROVED VIA EMAIL |
| | PRIOR TO RESUBMITTAL BY SENDING ADDITIONAL INFORMATION |
| | VIA EMAIL. |
| | |
| | 4. A 1.6, THE TEXT IDENTIFYING THE MECHANICAL EQUIPMENT |
| | IS NOT LEGIBLE, PLEASE RELOCATE, FBC 107. |
| | |
| | 5. LS 1.2, THE AREA WHICH APPEARS TO BE A LIBRARY IS |
| | NOT IDENTIFIED, FBC 107. |
| | |
| | 6. LS PAGES, GENERAL INFORMATION, APPEAR TO INCLUDE |
| | INFORMATION NOT RELEVANT TO THIS PROJECT. IT IS NOT |
| | CLEAR WHICH DO APPLY, SUCH AS SCIENCE LABS, |
| | WOODWORKING. REVISE TO CLARIFY WHICH USES ARE |
| | APPLICABLE, OR REMOVE THOSE NOT APPLICABLE. |
| | |
| | 7. FBC 107, AS THIS PERMIT WAS READY FOR ISSUANCE, |
| | SUPPLEMENTARY INFORMATION WHICH IS NO LONGER APPLICABLE |
| | IS IN THE PACKAGE (SUCH AS ENERGY CALCS). PLEASE TREAT |
| | THESE THE SAME AS PLANS; THE ONES WHICH SHOULD BE |
| | REMOVED SHOULD BE MARKED VOID AND RETAINED SEPARATELY, |
| | WITH THE VOIDED PLAN SHEETS. ASSEMBLE TWO SETS OF |
| | SUPPLEMENTARY DOCUMENTS FOR REVIEW. |
| | |
| | 8. IT IS NOT CLEAR IF THE STRUCTURAL CALCS PREVIOUSLY |
| | REVIEWED AND APPROVED ARE TO BE A PART OF THE PERMIT |
| | PACKAGE. THE BUILDING SIZE CHANGED, BUT NEW CALCS WERE |
| | NOT PROVIDED. IS IT THE INTENT THAT THE CALCS ALREADY |
| | PROVIDED BE UTILIZED AS THEY ARE MORE CONSERVATIVE, OR |
| | ARE THEY NOT TO BE INCLUDED IN THE PERMIT RECORD? |
| | |
| | 9. THE STRUCTURAL CALCS PREVIOUSLY SUBMITTED USE 180MPH |
| | AS DESIGN CRITERIA, PAGE S1.2 STATES 181MPH. CALCS |
| | STATE RISK CATEGORY III, S1.2 IS CATEGORY II (SEE FBC |
| | TABLE 1604.5). CALCS USE EXPOSURE D, S1.2 STATES DESIGN |
| | CRITERIA IS EXPOSURE C (THIS APPEARS TO BE EXPOSURE D, |
| | FBC 1609.4.3). |
| | |
| | REVISE S1.2 TO RISK CATEGORY III, EXPOSURE D, OR SEND |
| | JUSTIFICATION FOR PROPOSED WIND DESIGN CRITERIA VIA |
| | EMAIL IN ORDER TO GET THIS ISSUE RESOLVED PRIOR TO |
| | RESUBMITTAL. |
| | |
| | 10. 2 A3.4, NO HANDRAIL SHOWN ON THE STAIRS, FBC |
| | 1009.15. PLEASE ADVISE WHERE THE DETAIL FOR THE STAIR |
| | RAIL CAN BE FOUND (OR ADD DETAIL). |
| | |
| | 11. SEE PLUMBING COMMENTS REGARDING ACCESSIBILITY; ALL |
| | ARE APPLICABLE FOR BUILDING REVIEW. |
| | |
| | 12. P5.1 CONFLICTS WITH A1.6 ROOF DRAIN SIZES, FBC |
| | 1503.4. A1.6 APPEARS COMPLIANT BUT SIZING (3 IN) DOES |
| | NOT APPEAR ADEQUATE ON P5.1, PLEASE REVISE. |
| | |
| | 13. SEE THRESHOLD REVIEW. THREE SETS OF PLANS ARE |
| | REQUIRED FOR RESIDENT INSPECTOR PROJECTS. THIS ITEM HAS |
| | NOT BEEN ADDRESSED. IT IS NOT CLEAR WHETHER APPLICANT |
| | AGREES WITH RESIDENT INSPECTOR REQUIREMENT. PLEASE |
| | ADVISE PRIOR TO RESUBMITTAL OR ENSURE THAT THREE |
| | COMPLETE SETS OF PERMIT DOCUMENTS ARE PROVIDED AT TIME |
| | OF RESUBMITTAL. |
| | |
| | RESIDENT INSPECTOR DOCUMENTS (RESUMES, AGREEMENT) MAY |
| | BE SENT SEPARATELY FROM THE RESUBMITTAL VIA EMAIL. AS |
| | THIS REQUIRES A REVIEW BY PLAN REVIEW (VERIFICATION OF |
| | LICENSES, COMPLETENESS OF SUBMITTAL) AND THE CHIEF |
| | BUILDING INSPECTOR (APPROVAL OF PROPOSED INSPECTORS), |
| | APPLICANT IS ENCOURAGED TO SUBMIT DOCUMENTS AS SOON AS |
| | THEY ARE AVAILABLE. |
| | |
| | 14. IMPACT FEE ASSESSMENT BY PALM BEACH COUNTY IS |
| | REQUIRED PRIOR TO PERMIT ISSUANCE. THIS MAY BE DONE |
| | AFTER ALL PLAN REVIEWS ARE COMPLETE AND PASSED. THE |
| | PLANS STAMPED BY PALM BEACH COUNTY AND THE RECEIPT |
| | SHOWING THAT FEES DUE HAVE BEEN PAID IS REQUIRED TO BE |
| | SUBMITTED. |
| | |
| | 15. PROVIDE PRODUCT APPROVALS FOR ALL COMPONENTS AND |
| | CLADDING. ANY PRODUCT APPROVALS NOT SUBMITTED PRIOR TO |
| | PERMIT ISSUANCE WILL BE REQUIRED TO BE SUBMITTED AS A |
| | REVISION PRIOR TO INSTALLATION. |
| | |
| | 16. OPTIONAL, PROVIDE UPDATED VALUE OF PROJECT, FBC |
| | 109. |
| | |
| | 17. ADVISORY ONLY: THE PROPOSED FLOOD MAPS (CURRENTLY |
| | SCHEDULED TO TAKE EFFECT IN EARLY 2017), SHOW A THE BFE |
| | FOR THIS LOCATION OF 8.519 NGVD29 (CONVERTED FROM 7.0 |
| | NAVD88). THEREFORE THE PROPOSED CONSTRUCTION (8.46 |
| | NGVD29) IS LOWER THAN THE 100 YEAR FLOOD EVENT BASED ON |
| | THE MOST RECENT DATA. AS FIRMS (AKA FEMA FLOOD MAPS) |
| | ARE ROUNDED TO THE NEAREST FOOT, IT IS POSSIBLE THAT |
| | THE ACTUAL BFE IS UP TO .4 FEET HIGHER. APPLICANT IS |
| | ENCOURAGED TO INVESTIGATE THIS ISSUE, FBC 1612. PLEASE |
| | FEEL FREE TO CONTACT ME IF YOU WOULD LIKE ADDITIONAL |
| | INFORMATION. |
| | |
| | THE PROPOSED MAPS ARE AVAILABLE AT THE FEMA WEBSITE |
| | (MAP SERVICE CENTER) AND ON THE PALM BEACH COUNTY GIS. |
| | THE RELATED PROPOSED FLOOD INSURANCE STUDY (FIS) IS |
| | AVAILABLE ON THE FEMA WEBSITE. |
| | |
| | HTTP://MSC.FEMA.GOV/PORTAL/SEARCH#SEARCHRESULTSANCHOR |
| | |
| | SEARCH FOR THE ADDRESS, |
| | SELECT "SHOW ALL PRODUCTS FOR THIS AREA" |
| | SELECT "PRELIMINARY PRODUCTS" |
| | PRELIMINARY FIS REPORTS AND PRELIMINARY FIRM PANELS |
| | |
| | 18. THIS PERMIT WILL BE ISSUED WITH THE FOLLOWING |
| | PROVISOS: |
| | |
| | BUILDING UNDER CONSTRUCTION ELEVATION CERTIFICATE OR |
| | FORM BOARD SURVEY SHOWING PROPOSED ELEVATIONS IS |
| | REQUIRED PRIOR TO CONCRETE POUR |
| | FINISHED CONSTRUCTION ELEVATION CERTIFICATE IS REQUIRED |
| | PRIOR TO FINAL INSPECTION. |
| | |
| | |