| 2015-04-01 12:29:31 | 1) LIFE SAFETY SHEETS - THE BUILDING INFORMATION BOX |
| | SHOWS THE OCCUPANCY REQUIREMENTS FOR EDUCATION AT 20 |
| | SQUARE FEET PER PERSON YET LIFE SAFETY PLAN LS1.1 SHOWS |
| | THE OCCUPANT LOAD AS 35 SQUARE FEET PER PERSON. CLARIFY |
| | AND ENSURE THAT THE OCCUPANT LOADS OF THE AREAS ARE |
| | BASED ON TABLE 1004.1.1 OF THE 2010 FBC. |
| | 2) SHT. T1 & PLUMBING SHEETS OF THE PLANS I REVIEWED |
| | REFER TO CIVIL DRAWINGS. THERE WERE NO CIVIL DRAWINGS |
| | IN THE SET OF PLANS I REVIEWED. CLARIFY. |
| | 3) SHT.LS 1.2 IS MISSING FORM THE SET OF PLANS I |
| | REVIEWED. SUBMIT SHEET FOR REVIEW. |
| | 4) SHT. A8.2 - ENLARGED RESTROOM PLANS 02 03, 04, DO |
| | NOT COMPLY WITH THE 2010 FL. ACCESSIBILITY CODE SEC. |
| | 604.3, 606. THE MINIMUM REQUIRED WIDTH IS 85" IF BUILT |
| | PERFECT. 86 INCHES ALLOWS FOR CONSTRUCTION TOLERANCES. |
| | 5) SHT. A8.2 - DETAIL # 06 - IT APPEARS THAT THE DOOR |
| | MAY SWING INTO THE CLEAR FLOOR SPACE FOR THE LAVATORY |
| | IN ACCESSIBLE STALL IN THE MALE AND FEMALE RESTROOM. |
| | FAC SEC.604.8.1.2. |
| | 6) CLEARLY SHOW THE DIMENSIONS OF THE LENGTH AND WIDTH |
| | OF THE CLEAR FLOOR SPACES FOR THE LAVATORIES AND THE |
| | WATER CLOSETS IN THE ACCESSIBLE TOILET COMPARTMENTS AND |
| | TOILET ROOMS. FAC SECS.604.3 & 606.2. |
| | 7) VERTICAL ACCESSIBILITY IS REQUIRED TO THE SECOND |
| | FLOOR PER THE 2010 FAC SEC.201.1.1. |
| | 8) FLOOR DRAINS AND HOSE BIBBS ARE REQUIRED IN THE |
| | GROUP TOILET ROOMS PER THE 2010 FBC SEC.443.3.5.6. |
| | 9) SHT. P4.1 - CLINIC RESTROOM - THERE IS AN ARROW THAT |
| | POINTS TO "2 " SANITARY UP" BUT NOTHING IS SHOWN. |
| | CLRIFY. |
| | 10) SHT.P4.1 - ADULT RESTROOM # 1-103 - THE LAYOUT ON |
| | THE RISER DOESN'T CORRELATE WITH THE FLOOR PLAN. |
| | CLARIFY. |
| | 11) SHT. P4.1 - THE 2" LINE ON RISER BY EWC SAYS 2" |
| | SANITARY UP BUT IS NOT CONNECTED TO THE BUILDING DRAIN |
| | & TERMINATES NOWHERE. CLARIFY. |
| | 12) SHT. P4.1 - A WATER CLOSET IS MISSING FROM THE |
| | RISER FOR TOILET ROOMS 1-106 & 1-107A. |
| | 13) THE SANITARY RISER APPEARS TO MISSING PIPING FROM |
| | RESTROOMS 106-A & 107-A. |
| | 14) SHT. P4.1 - SINK SK-1 IN THE ART LAB IS NOT |
| | CONNECTED TO THE SANITARY SYSTEM. |
| | 15) SUBMIT SPECIFICATIONS ON THE SOLIDS INTERCEPTOR |
| | ZURN ZA - 1184. WPB AMEND. TO 2010 FBC SEC. 107.2.1. |
| | 16) SHT. P4.1 - SIZE THE VENT FOR SINK SK-1 IN THE ART |
| | LAB. |
| | 17) SHT.P4.1 - THE ARE NUMEROUS SECTIONS OF THE |
| | SANITARY RISER WHERE PIPNG HAS NO CONNECTION POINTS AND |
| | TERMINATES NOWHERE. SUBMIT A SANITARY RISER DIAGRAM |
| | THAT CLEARLY REFLECTS ALL AREAS OF THE INSTALLATION. |
| | EXPAND THE CONDENSED AREAS OF THE RISER DIAGRAM SO IT |
| | IS CLEAR AND LEGIBLE. WPB AMEND. TO 2010 FBC SEC. |
| | 107.3.5.1.3. |
| | 18) SHT. P4.1 - PLUMBING FIXTURE SCHEDULE - THE MINIMUM |
| | TRAP SIZE FOR SINKS SHALL BE 1 1/2" NOT 1 1/4" AS SHOWN |
| | PER FPC TABLE 709.1. |
| | 19) SHT. P4.2 - SIZE ALL SECTIONS OF THE WATER RISER. |
| | WPB AMEND. TO 2010 FBC SEC. 107.3.5.1.3. |
| | 20) SHT. P4.2 HAS NOTATION "WC-1" BUT NOTHING IS SHOWN. |
| | REFER TO SHT. P3.1 FOR LOCATION. SEE AREA BY GRID LINE |
| | H11. |
| | 21) SIZE THE WATER RISERS TO THE 2ND FLOOR. |
| | 22) SHT. P5.3 - A COMPLETE AND THOROUGH REVIEW CANNOT |
| | BE ACCOMPLISHED ON THE STORMWATER RISER BECAUSE IT IS |
| | INCOMPLETE; LINES TERMINATE NOWHERE, LINES ARE MISSING, |
| | ETC. SUBMIT A COMPLETE, CLEAR AND LEGIBLE STORMWATER |
| | RISER DIAGRAM FOR REVIEW. WPB AMEND. TO 2010 FBC SEC. |
| | 107.3.5.1.3. |
| | 23) SHT. P5.2 - THE DESIGN OF THE STORMWATER SYSTEM |
| | SHALL INCLUDE 1/2 THE AREA OF ANY VERTICAL WALL THAT |
| | DIVERTS WATER TO THE ROOF. SHOW THAT THE AREA OF THE |
| | PARAPET WALL HAS BEEN ADDED INTO THE STORMWATER DESIGN |
| | PER THE 2010 FPC SEC.1106.4. |
| | 24) SHT. P7.1 - THE PLAN SHOWS THE WATER HEATER BEING |
| | BOTTOM FED BY THE RECIRCULATING LINE. A VACUUM RELIEF |
| | VALVE IS REQUIRED ON THIS LINE PER SEC. 504.2 OF 2010 |
| | FPC. |
| | 25) SHT. P7.2 - THE DOMESTIC WATER DEMAND TABLE REFERS |
| | TO TABLE E103.2(2). THERE IS NO SUCH TABLE . CLARIFY. |
| | 26.) DOES THIS SCHOOL ALSO HAVE DAYCARE OR WILL IT BE |
| | USED AS A DAYCARE FACILITY AT ANY TIME? DAYCARE |
| | FACILITIES SHALL COMPLY W/ 2010 FBC SEC. 436. |
| | |
| | |
| | PLUMBING PLAN REVIEW |
| | TIM LARGE |
| | CHIEF PLUMBING INSPECTOR |
| | 561-805-6692 |
| | [email protected] |
| | |
| | |
| | |
| | |
| | |
| | |
| | |