| 2015-03-06 16:55:11 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | 1) SHEET LS 1.1 DOOR 1-004; DOOR 1-191; SHEET LS 1.2 |
| | DOOR1-209; EXIT DOOR LEAF ENCROACHMENT. |
| | NFPA 101 CHAPTER 7, MEANS OF EGRESS |
| | 7.2.1.4.3 DOOR LEAF ENCROACHMENT |
| | 7.2.1.4.3.1 DURING ITS SWING, ANY DOOR LEAF IN A MEANS |
| | OF EGRESS SHALL LEAVE NOT LESS THAN ONE-HALF OF THE |
| | REQUIRED WIDTH OF AN AISLE, A CORRIDOR, A PASSAGEWAY, |
| | OR A |
| | LANDING UNOBSTRUCTED AND SHALL NOT PROJECT NOT MORE |
| | THAN 7 IN. INTO THE REQUIRED WIDTH OF AN AISLE, A |
| | CORRIDOR, A PASSAGE WAY, OR A LANDING, WHEN FULLY OPEN, |
| | UNLESS BOTH OF THE FOLLOWING CONDITIONS ARE MET: |
| | (1) THE DOOR OPENING PROVIDES ACCESS TO A STAIR IN AN |
| | EXISTING BUILDING. |
| | (2) THE DOOR OPENING MEETS THE REQUIREMENTS THAT LIMITS |
| | PROJECTION TO NOT MORE THAN 7 IN. INTO THE REQUIRED |
| | WIDTH OF THE STAIR LANDING WHEN THE DOOR |
| | LEAF IS FULLY OPEN. |
| | 2) SHEET LS 1.1 THE WALLS OF ROOMS 1-112, 1-190 AND |
| | 1-290 ARE REQUIRED TO BE 1 HOUR FIRE RATED. |
| | |
| | 3) SHEET LS1.1 & 1.2 STAIRWELL 1-003 ENCLOSURE AND |
| | PROTECTION OF STAIRS. THE UNPROTECTED WINDOW OPENINGS |
| | OF THIS STAIRWELL AND/OR ASSOCIATED EXTERIOR WALLS |
| | WITHIN 10 FT SHALL BE PROTECTED WITH AN 1 HOUR FIRE |
| | RATING. |
| | 7.2.2.5.2 EXPOSURES. |
| | 7.2.2.5.2.1 WHERE NONRATED WALLS OR UNPROTECTED |
| | OPENEINGS ENCLOSE THE EXTERIOR OF A STAIRWAY, OTHER |
| | THAN AN EXISTING STAIRWAY, AND THE WALLS OR OPENINGS |
| | ARE EXPOSED BY |
| | OTHER PARTS OF THE BUILDING AS AN ANGLE OF LESS THAN |
| | 180 DEGREES, THE BUILDING ENCLOSURE WALLS WITHIN 10 FT |
| | HORIZONTALLY OF THE NONRATED WALL OR UNPROTECTED |
| | OPENING SHALL BE |
| | CONSTRUCTED AS REQUIRED FOR STAIRWAY ENCLUSRES, |
| | INCLUDING OPENING PROTECTIVES. |
| | |
| | 4) A DOOR SCHEDULE INDICATING ALL DOOR FIRE RATINGS, |
| | HARDWARE, FINISH, AND/OR LOCKING DEVICES IS NOT |
| | ATTACHED TO THIS SUBMITTED PLAN OR IS NOT READILY |
| | IDENTIFIABLE. THE FIRE RATING OF DOORS CAN NOT BE |
| | REVIEWED, CONFIRMED OR APPROVED. |
| | |
| | 5) THE CURVED STAIR SHALL BE PROTECTED WITH THE |
| | REQUIREMENTS OF NFPA 101 8.6 AND NFPA 13, 8.15 SPECIAL |
| | SITUATIONS INCLUDING, BUT NOT LIMITED TO, SPRINKLER |
| | PROTECTION UNDER THE STAIRS. |
| | |
| | 6) SHEET FS 2.1 & 2.2 , FIRE SPRINKLER PROTECTION WAS |
| | NOT INDICATED IN THE COMMON HALLWAYS, WITHIN THE |
| | STAIRWELLS AND THE OPEN ATIURM. A COMPLETE FIRE |
| | SPRINKLER IS REQUIRED IN THIS OCCUPANCY. |
| | |
| | 7) AN EXIT SIGN IS REQUIRED AT THE BOTTOM OF THE CURVED |
| | STAIR AT DOOR 1-005 LEADING TO THE EXIT CORRIDOR. |
| | |
| | 8) SOME OF THE CURRENT FIRE CODE LISTINGS INDICATED |
| | WITHIN THE SUBMITTED PLAN ARE INCORRECT AND NEED TO BE |
| | UPDATED WHERE APPLICABLE. THE PROPOSED PROJECT SHALL |
| | MEET THE REQUIREMENTS OF THE 5TH EDITION OF FLORIDA |
| | FIRE PREVENTION CODE INCLUDING THE 2012 EDITION OF NFPA |
| | 1 AND NFPA 101 AND ALL OTHER APPLICABLE CODES OR |
| | STANDARDS. |
| | FIRE SPRINKLER WORK SHALL COMPLY WITH THE REQUIREMENTS |
| | OF NFPA 13, 2010 EDITION. |
| | FIRE ALARM WORK SHALL COMPLY WITH THE REQUIREMENTS OF |
| | NFPA 72, 2010 EDITION. |
| | CONSTRUCTION WORK SHALL COMPLY WITH THE REQUIREMENTS OF |
| | NFPA 241, 2009 EDITION. |
| | FIRE EXTINGUISHERS SHALL COMPLY WITH THE REQUIREMENTS |
| | OF NFPA 10, 2010 EDITION. |
| | ELECTRIC WORK SHALL COMPLY WITH NFPA 70, 2011 EDITION. |
| | |
| | 9) ADDITIONAL COMMENTS MAY BE APPLIED IN THE FUTURE |
| | BASED ON THE RESUBMITTAL OF THE ABOVE. |
| | |
| | |