| Plan Review Notes For Permit 15020917 |
| Permit Number |
15020917 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-03-13 15:29:38 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | 1. APPLICATION IS FOR IMPACT WINDOWS, NON IMPACT SINGLE | | | HUNG WINDOW PRODUCT APPROVAL PROVIDED. THIS PRODUCT HAS | | | A LIMITATION OF -45PSF, WHICH IS NOT ADEQUATE FOR | | | STATED DESIGN PRESSURES. | | | | | | 2. REVISE FLOOR PLAN TO INCLUDE ROOM DESIGNATIONS. | | | | | | FOR BEDROOM WINDOWS WHICH ARE LESS THAN 51" IN HEIGHT, | | | NOTE EXISTING CONDITIONS (TYPE OF WINDOW) AND OPENING | | | SIZE FOR BEDROOMS, FBC R310, FBC EB 604.1. THE CLEAR | | | OPENING CANNOT BE REDUCED BY MORE THAN 5%. | | | | | | TO PROVIDE FURTHER CLARIFICATION REGARDING INFORMATION | | | NEEDED FOR BEDROOM WINDOWS WHICH ARE LESS THAN 51" IN | | | HEIGHT: | | | | | | STATE WHAT TYPE OF WINDOW IS THERE NOW IN THE BEDROOMS | | | - AWNING, CASEMENT, SINGLE HUNG? | | | | | | STATE WHAT THE EXISTING CLEAR OPENING DIMENSIONS ARE. | | | CLEAR OPENING IS THE OPENING WHICH EXISTS WHEN THE | | | WINDOW IS FULLY OPEN. | | | | | | STATE WHAT THE PROPOSED CLEAR OPENING DIMENSIONS ARE. | | | THIS CAN BE OBTAINED FROM THE MANUFACTURER. | | | | | | | | | | | | | | | |
|